An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Installaties

  2. Installaties • interne warmtebelasting Qintern [W]: • Qintern = qp + qverl + qapp+ qtrans + qow • externe warmtebelasting Qextern [W]: • Qextern = qgl + qschil + qtrans + qinfil

  3. Installaties • qp = warmteafgifte personen [W] • afhankelijk van activiteit en kleding: • rustig zittend persoon versus hard werkend persoon [met] • zwemkleding versus poolkleding [clo] • stofwisseling zorgt voor constante temperatuur • Tabel 3.4 , a+b, blz 22

  4. Installaties

  5. Installaties • Qverl = Pe * L1 * L2 * Sb *F [W] • Pe = geïnstalleerd electrisch vermogen [W/m2] • L1 = gelijktijdigheifsfactor [-] • L2 = restwarmtefactor [-] • Sb = accumulatiefactor [-] • F = vloeroppervlak [m2] • Figuur / tabel 3.7, 3.8, 3.9, 3.10

  6. Installaties

  7. Installaties • qapp= warmte afgifte apparatuur [W] • qtrans = warmte uitwisseling tussen ruimten [W] • qow = overige warmtebronnen [W]

  8. Installaties • Maatregelen verlaging interne warmtelast • -verlichting • verlichtingsniveau + kleur • daglicht, % glas, zonwering • rendement lichtbronnen • afzuiging armaturen • zwaar bouwen ivm accumulatie • Voorkomen isolerende afwerking vloer + wand • -apparaatwarmte • -warmtetransmissie

  9. Installaties

  10. Installaties • Qextern = qgl + qschil + qtrans + qinfil • de ontwerper / architect heeft zeer grote invloed op de externe warmtebelasting • warmtebelasting door zonnestraling: • q tot = q diff + q dir + q reflectie [W] • zonnestralingstabellen 3.13 • helderheid van de lucht “trubungsfactor” 3.12.2

  11. Installaties

  12. Installaties • qgl = q gl 1 + q gl 2 [W] • q gl 1 = q tot * F 1 * ZTA * Sz [W] • q tot = totale zonnestraling [W/m2] • F 1 = oppervlak glas door zon beschenen [m2] • ZTA = zontoetredingsfactor zonweringsysteem • Bijlage 3.7 • Sz = accumulatieactor zonnenenergie • Tabel 3.18

  13. Installaties

  14. Installaties • q gl 2 = q diff + reflectie * F 2 * ZTA * Sz [W] • q diff = diffuse zonnestraling [W/m2] • q reflectie = reflecterende zonnestraling [W/m2] • F 2 = oppervlak glas door zon beschenen [m2] • ZTA = zontoetredingsfactor zonweringsysteem • Bijlage 3.7 • Sz = accumulatieactor zonnenenergie • Tabel 3.18

  15. Installaties • Zonweringssystemen • afscherming van directe zoninstraling • bouwkundig door overstekken, balcons, • aanvullend door luiken, markiezen, • Nadelen: • zichtbeperking • geluidhinder, beschadiging, bediening • thermische breuken zon-schaduw

  16. Installaties

  17. Installaties • Lichttoetreding – zontoetreding • LTA : verhouding tussen hoeveelheid doorgelaten en opvallend licht • quotiënt van LTA en ZTA maakt snelle vergelijking tussen zonweringssystemen mogelijk

  18. Installaties

  19. Installaties • Accumulatiefactor S tabel 3.18 • tijdstip maximale warmtebelasting wijzigt door accumulatie. • fase verschuiving • temperatuur demping hfst 2 bf

  20. Installaties • Transmissie door glas • Q tgl = U gl * F gl * (Te – T i) [W] • Transmissie door dak en wanden • Q trans = U con * F con * Teq [W] • Teq = equivalent temperatuurverschil tabel 3.1.42 blz 91 • Teq = temperatuurverschil tussen Teo en T i

  21. Installaties

  22. Installaties • Ventilatielucht rechtstreeks van buiten • q vent = η * V * ρ * c * 1/3600 * (Te – Ti) [W] • q infiltratie = ? • Afhankelijk van dichtheid gebouw zie BB • Samenstellen koellast.