Life Safety in TunnelsESS Design Strategy Björn Yndemark, WSP Fire & Risk www.europeanspallationsource.se January, 2015
FireSafety Accelerator tunnel • Fire separated from the Gallery, the Front End Building and the Target building • Fire alarm, aspirating system • Evacuation alarm • Emergency lighting • Evacuation routes every 135 m • Smoke management system • Fire retardant cables • Manual power cut of high voltage • Stand pipes in emergency stairs
FireSafety Accelerator tunnel Radiation Safety Authority: • Defence in Depth • Prevent fires from starting • Detect and extinguish quickly those fires that do start • Prevent the spread of those fires which have not been extinguished => Fire Alarm and Smoke Management System
FireSafety Accelerator tunnel Building Regulation: • Smoke ventilation in underground facilities • Basements in a building in class Br1 shall be provided with smoke ventilation => Smoke Management System
SmokeManagament System Design fire: Cables, 1 MW (staedy state) Robustness: Cables, Fast growth up to 2 MW
Estimated radiological release Estimated Radiological Release
Design 5 m3/s 5 m3/s 10 m3/s
Design 5 m3/s 5 m3/s 5 m3/s 10 m3/s 15 m3/s