Vacuum circuit breaker’s solenoid force evaluation 29/12/2009
Deliverable 1 • Report on the compliance of the brand new trip coil and close coil to specification and their safety factors as derived from the laboratory experiments
EPE Switchgear -11 & 33KV Closing and Opening Coil coil Stopper block Pull gauge Trip hook/strike Plunger 32 mm
EPE solenoid Force and Stroke Relationship! μois the Permeability of free space N is the number of coil turns A is the effective cross sectional i is the max current x is the stroke length of the plunger N.B. Data sheet of the coil attached in appendix ! A. E. Fitzgerald, Electric Machinery: The process, devices and systems of electromechanical energy conversion, McGraw Hill 1971
ETAH solenoid Force and Stroke Relationship! μois the Permeability of free space N is the number of coil turns A is the effective cross sectional i is the max current x is the stroke length of the plunger N.B. Data sheet of the coil attached in appendix ! A. E. Fitzgerald, Electric Machinery: The process, devices and systems of electromechanical energy conversion, McGraw Hill 1971
EPE Solenoid Force & Amps vs Plunger position Force in Kgf Stroke length (x) mm
TAMC) (ETAH) Solenoid Force & Amps vs Plunger position Force in Kgf Stroke length (x) mm
Photo Gallery Force test for EPE 11KV New Solenoid testing
Force test for EPE 33KV Force test for TAMCO 11KV