1.01k likes | 1.88k Views
2. Fire Protection System Design Strategy. Comprehensive StrategyPrevent fires from starting in the first placeEducationAdministrative proceduresSignageInspectionsFire safety programFire alarm and detection systemsDetect fires early to initiate quick evacuationDesign safe egress from buildi
E N D
1. 1 FIRE PROTECTION SYSTEMS
2. 2 Fire Protection System Design Strategy Comprehensive Strategy
Prevent fires from starting in the first place
Education
Administrative procedures
Signage
Inspections
Fire safety program
Fire alarm and detection systems
Detect fires early to initiate quick evacuation
Design safe egress from building
Exits, Stairwells, Corridors
Emergency lighting and ventilation
3. 3 Design Strategies (cont’d) Fire suppression systems
Sprinkler
Standpipe and Hose
Chemical
Smoke Control systems
Remove smoke from exits
Provide fleeing occupants with breathable air
4. 4 Design Strategies (cont’d) Compartmentalization
Break a building into small compartments to contain fire and smoke
Fire Separation
Fire rated wall, floor, ceiling assemblies that impede the spread of fire
Use of non-combustible materials
Use of low flame spread and smoke developed finish material
5. 5 Flame Spread ASTM E84 – Test Method for Surface-Burning Characteristics of Building Materials (Steiner tunnel test). Rates surface-burning characteristics of building materials and interior finishes, and provides data on smoke density.
Flame spread classifications:
Class A: 0-25
Class B: 26-75
Class C: 76-200
Local building codes generally restrict use of materials in different occupancies based upon flame spread and smoke developed ratings.
For example, NYSED Manual of Planning Standards requires finishes in corridors, passageways, stairways to be Class A.
6. 6 Sources of Ignition Spontaneous Combustion
Electrical Sources
Arcing
Lightning
Mechanical
Friction
Other
Intentional (arson)
Cigarettes
7. 7 Fire Issues Products of combustion – CO, CO2, other gases
Fire quickly consumes oxygen
Lack of oxygen
Rapid deterioration of human capabilities
Muscle control
Thinking, consciousness, etc.
Poor visibility
8. 8 Fire Issues (cont’d) Vertical shafts promote spread of smoke, heat
Elevators
Escalators
Atriums
HVAC systems can spread smoke
Windowless buildings – prevent entry by firefighters
Interior finishes – can spread fire, give off smoke
High rise buildings (g.t. six stories) – complicate firefighting, rescue
9. 9 Fire Alarm and Detection Systems
Design Standards
Fire Code of NYS – defines minimum standards where fire alarm and detection system is required, general design requirements
NFPA 72 – National Fire Alarm Code – defines specific design standards
Functions of a fire alarm and detection system:
Initiate alarm
Manually
Automatically
Notify occupants
Audible alarms
Visual alarms
10. 10 Functions (cont’d) Automatically signal fire department or central station
Recall elevators
Supervise special systems:
Fire pump operation, power availability
Sprinkler system status
Unlock doors
Automatically close doors that are part of fire separations
Automatically release smoke relief hatches
Control operation of HVAC supply and exhaust fans
Total shut down
Special smoke management systems
11. 11 Typical Fire Alarm System
12. 12 Fire Alarm Control Panel
13. 13 Fire Alarm Systems (cont’d) Types
Conventional (off/on “dumb” devices)
Addressable
Analog
Digital
Equipment
Manual Fire Alarm Boxes (Pull Stations)
Mounting – not less than 3.5 and not more than 4.5 ft above floor level (ADA requires maximum 48” high forward reach)
Spacing:
At exit doorways within 5’ of each exit doorway on each floor; on both sides of opening 40 feet and wider, and within 5 feet each side
Additional boxes such that distance of travel to any box less than 200 feet on same floor
14. 14 Manual Alarm Station at Exit
15. 15 Fire Alarm Systems (cont’d) Heat Detectors
Applications
Where smoke is ordinarily present
Top of elevator shafts where sprinklers are present
Types
Fixed
Combination fixed/rate of rise
Location
On ceiling not less than 4” from sidewall, or on sidewall between 4” and 12” of ceiling
16. 16 Fixed Type Heat Detector
17. 17 Fire Alarm Systems (Cont’d) Heat Detectors (cont’d)
Typical Spacing
Fixed: 15’x15’
Combination fixed/rate of rise: 50’x50’
All points on ceiling within 0.7 x listed spacing
Special considerations – beam construction, sloped ceilings – refer to NFPA 72 for spacing requirements.
18. 18 Smoke From Cooking Appliances Can Set Off Smoke Detector
19. 19 Stages of a Fire Incipient – invisible combustion gases, without smoke or flame, no appreciable heat release
Smoldering – heat still absent, combustion gases now visible as smoke
Flame – actual fire is produced, a column of gases made luminous by intense heat
Heat – follows concurrently or just after flame stage – tremendous amounts of heat released
20. 20 Smoke Detectors Types
Spot
Beam
Design:
Ionization
Photoelectric
Spot Detector Accessories
Integral alarm
Typical use – motels and similar sleeping spaces
21. 21 Photoelectric Spot Smoke Detector with Integral Alarm Photoelectric detectors operate using principle of “smoke obscuration”
Smoke interposed in light beam between small emitter and detector
Decreased light intensity at detector causes alarm to sound
Device in photo also includes integral alarm – used in motels and similar sleeping spaces.
22. 22 Principle of Operation – Ionization Detector
23. 23 Smoke Detectors (cont’d) Applications
Spot detectors
For general fire detection
Close doors, operate smoke dampers
Beam detectors
High ceilings where spot detectors impractical
Location
On ceiling not less than 4” from sidewall, or on sidewall between 4” and 12” of ceiling
24. 24 Smoke Detector Mounted on Wall
25. 25 Smoke Detectors (cont’d) Typical Spacing (spot)
30’x30’
All points on ceiling within 0.7 x listed spacing
g.t. 3’-0” from HVAC diffusers, supply grilles
Special considerations – beam construction, sloped ceilings – refer to NFPA 72 for spacing requirements.
26. 26 Typical “Listed” Smoke Detector Spacing
27. 27 Incorrect Application of Smoke Detector Area covered = 60’ x 15’ = 900 s.f.
Distance to corner exceeds 0.7 x listed spacing (0.7 x 30 = 21’)
Two smoke detectors would be required for this room.
28. 28 Beam Smoke Detector Smoke rising to ceiling will obscure light beam.
Receiver will detect change in beam intensity and cause alarm to sound.
Often used in atrium spaces, high “cathedral ceilings”, similar spaces.
29. 29 Notification Appliances Audible
Refer to NFPA 72 for sound pressure levels
Mounting
Wall – top not less than 90” a.f.f., not less than 6” below ceiling (where ceiling heights allow)
If combined with visual appliances, entire lens of visual appliance not less than 80” nor greater than 96” a.f.f.
Spacing
Such that they can be heard throughout building
Refer to NFPA 72 for specific requirements
30. 30 Audible Visual Device in School Cafeteria
31. 31 Audible Visual Fire Alarm Appliance
32. 32 Notification Appliances (cont’d) Visual Appliances
Location
Wall mounted – entire lens 80” -96” a.f.f.
Ceiling mounted permitted when device is specifically listed for this application.
Spacing
Refer to NFPA 72
When two or more in same field of view, must be synchronized (can be harmful to persons with epilepsy)
33. 33 Remote Annunciator Panel at School 80
An annunciator panel displays at remote entries and other locations the zone or device that is in alarm – generally located at main entries.
34. 34 FIRE SUPPRESSION SYSTEMS
35. 35 Types of Fire Suppression Systems Standpipe and Hose Systems
A reliable water supply, piping, hose connections to permit manual extinguishing of a fire.
Sprinkler Systems
A reliable water supply, piping, sprinklers, to permit automatic extinguishing of a fire.
Chemical Extinguishing Systems
Both manual and automatic systems
Use a chemical extinguishing agent where water is not effective, or cannot be used.
36. 36 Standpipe and Hose Systems Classification:
Class I – 2-1/2” hose connections for firefighter’s use, 100 psi at uppermost hose connection.
Class II – 1-1/2” hose connections for occupant use, 100 psi at uppermost hose connection.
Class III – 2-1/2” and 1-1/2” hose connections for both firefighter’s and occupant use.
37. 37 Diagram of a Typical Standpipe System
38. 38 Standpipe Hose Valve at Intermediate Stairwell Landing
39. 39 Typical Backflow Preventer for Fire Protection Service A backflow preventer prevents water contained in building piping systems from flowing back into the community water main.
Water piping in buildings may contain foul and/or hazardous materials.
40. 40 Classification (cont’d) Type I and III standpipes are the most common.
Design Standard
NFPA 14 Standard for the Installation of Standpipe, Private Hydrant, and Hose Systems.
Current edition is 2003
As of 2004, NYS Building Code adopts the 2000 edition.
41. 41 Combined Systems
A combined system is a standpipe that also supplies automatic sprinklers on each floor.
Combined systems were first permitted by NFPA in 1976 to encourage owners of high rise buildings that already had standpipes to install sprinkler systems.
A sprinkler crossmain is connected to the standpipe at each floor. A typical connection detail is contained in NFPA 14 Figure A-5-9.1.3.1 (a) and (b).
42. 42 Diagram of a Typical Combined Sprinkler and Standpipe System
43. 43 A Typical Flow Control Assembly Located in a Stairwell
44. 44 Buildings that Require Standpipeand Hose Systems Buildings where standpipes and hose systems are required:
Any building where the highest floor level is 30 ft. or more above the lowest level of fire department vehicle access.
Places of Assembly
Covered Mall Buildings (e.g. Shopping Malls)
Stages
Underground Buildings
Check the applicable building ordinance for specifics (NYS 905.3)
45. 45 Water Supplies Water supply must be among the following:
Public waterworks with adequate pressure
Automatic fire pump connected to public waterworks
Manually controlled fire pump in combination with pressure tanks.
Pressure tanks installed in accordance with NFPA 22
46. 46 Water Supplies (cont’d.) Manually controlled fire pumps operated by remote control devices at each hose station.
Gravity tanks in accordance with NFPA 22
Automatic fire pumps connected to the public waterworks are the most common.
47. 47 Water Supply Capacity Water supply capacity
The capacity of the supply is calculated as follows:
500 gpm for the first standpipe
250 gpm for each additional standpipe
Not to exceed 1250 gpm
Water supply must have minimum 30 minutes duration for calculated flow
48. 48 Additional Classification of Standpipes Wet
The standpipe system is always filled with water.
Dry
The standpipe system contains no water.
Generally used only in unheated buildings (e.g., parking garages.)
Automatic
Water supply capable of supplying system demand automatically.
Most common type
49. 49 Additional Classification of Standpipes (Cont’d) Manual
Connected to small water supply to maintain water in the system, but inadequate to meet demand.
Relies on fire department pumper to supply necessary system demand.
Other types: semi-automatic dry, manual-dry (see NFPA 14 for explanations.)
The Building Ordinance (NYS Building Code) prescribes which type is required.
50. 50 Fire Pumps Fire Pumps
Since most water main pressures are generally less than 100 psi at the street, a fire pump is usually required to provide adequate pressure.
Fire pumps must be provided with an emergency power source.
Fire pumps generally require a separate, fire rated (2 hr.) room or enclosure.
51. 51 Typical Electric Fire Pump Installation
52. 52 Location of Hose Connections Location of Hose Connections
Height: not less than 3 ft and not more than 5 ft above floor (usually 4 ft).
Class I Systems
In exit stairways at each intermediate landing between floor levels.
Each side of wall adjacent to exit openings of horizontal exits.
Each exit passageway at entrance from building areas into passageway.
53. 53 Location of Hose Connections (Cont’d) In covered mall buildings at entrance to each exit passageway or exit corridor, and exterior public entrances to mall.
At highest landing of stairways with access to roof, and on roof where stairways do not access the roof.
Additional 2-1/2” hose connection at hydraulically most remote riser to facilitate testing.
See NFPA 14 for more requirements.
54. 54 Location of Hose Connections (Cont’d) Class II Systems
1-1/2” hose stations so that all portions of each floor level are within 130 ft of a hose connection.
Class III Systems
As required for both Class I and Class I Systems
55. 55 Drainage of Standpipes Each standpipe to be equipped with a means for draining
Usually a drain valve is located at lowest point of standpipe, downstream of isolation valve
Drain to an approved location
Often drained to spill at grade
56. 56 Fire Department Connections At least one fire department connection for each zone of each Class I and Class III system
High rise buildings require two remotely located fire department connections for each zone
Height: +18” to +48” above adjoining grade
57. 57 Fire Department Connections (Cont’d) A check valve is required downstream.
No shutoff valve is permitted between the fire department connection and the system.
Dry piping between connection and check valve should be galvanized steel.
Signage is required at each connection. See NFPA 14, Ch. 4-3.5.2 for details.
58. 58 Sprinkler Systems Definition and purpose – a reliable water supply, piping, sprinklers, valves and accessories for the purpose of automatically extinguishing a fire.
Governing Design Standards
Local building code or ordinance – prescribes where sprinkler systems are required
NFPA 13 Standard for the Installation of Sprinkler Systems – prescribes how sprinkler systems are to be designed and constructed
Factory Mutual (FM) – An insurance company standards organization; it may, through the building owner’s insurance company, impose additional restrictions/requirements for overall building fire protection systems.
59. 59 Sprinkler Systems (cont’d) Types of sprinkler systems:
Wet
Dry
Pre-action
Deluge
60. 60 Sprinkler Systems (cont’d) Wet system
Piping is filled with water under pressure at all times.
When one or more sprinkler heads open, water is automatically discharged.
Used in heated buildings or portions of buildings that are heated.
Most common type of system.
61. 61 Diagram of a Wet Pipe Sprinkler System with Water Motor Alarm
Both pendant and upright sprinklers may be used.
During operation, the alarm check valve diverts a small portion of water to the water motor alarm – does not rely on electricity to sound alarm.
62. 62 A Typical Wet Pipe Sprinkler Alarm Valve Installation
63. 63 Wet Pipe Alarm Valve
64. 64 Wet Pipe Sprinkler with Electric Alarm An electric alarm bell is operated through a water flow switch inserted into the main riser.
When a sprinkler opens, water flow activates flow switch, and alarm sounds.
Requires a reliable source of power from an emergency source.
65. 65 Sprinkler systems (cont’d) Dry system
Piping is filled with compressed air.
A dry system valve blocks the entry of water into the piping. Air pressure in the piping holds the valve closed.
When one or more sprinkler heads open
Air is first released through the head(s)
Air pressure in the piping system drops.
Dry system valve swings open.
Water floods the piping system.
Used in unheated buildings, or portions of buildings that are not heated, e.g., attics.
66. 66 Diagram of a Dry Pipe Sprinkler System Upright heads must be used, in order to allow the piping to drain completely.
67. 67 Sprinkler systems (cont’d) Pre-action system
Requires operation of both a fire detector and a sprinkler head opening before water is released.
Piping is filled with pressurized air.
A fire detection system (smoke, heat detectors, manual pull station) is wired to the pre-action valve; valve is opened only when fire detection system is activated.
Water floods piping.
68. 68 Pre-action system (cont’d) Water is released from each sprinkler head that opens.
Used for rooms that contain valuable equipment or materials that could be damaged be release of water, where fire detection must be verified independently.
Main frame computer rooms
Laboratories
69. 69 Diagram of a Pre-Action System
70. 70 Sprinkler Systems (cont’d) Deluge System
All sprinklers are open
When water fills the piping system, all sprinklers discharge water simultaneously
Diagram is similar to pre-action system
Applications:
Where severe fire hazard exists that can be extinguished safely with water
E.g. – a Fireworks Factory
71. 71 Sprinkler systems (cont’d) Where required:
Governed by the local building code or ordinance
If not required by code, insurance companies often offer reduced rates, or won’t insure buildings without sprinkler systems.
72. 72 Some Sprinkler Types Recessed Pendant Sprinkler
Glass tube holds metal disc seated in valve seat
Glycerin in glass tube expands when heated and will shatter glass
Water is released
Spray pattern is established by deflector
73. 73 Recessed Pendant Sprinkler with Brass Finish
74. 74 Old Style Sprinkler with Fusible Link, (Upright Style Shown)
75. 75 Sprinkler with Wire Guard and Deflector Disk (Pendant Style Shown) This sprinkler would be used to protect combustible materials in storage racks
Wire guard protects sprinkler from damage as racks are loaded/unloaded
Deflector plate prevents water may be discharged from above from cooling this sprinkler and preventing its operation
76. 76 Concealed Sprinkler Decorative white disk is soldered to the sprinkler body – solder melts first, plate falls to floor, exposing sprinkler
Exposed sprinkler will now operate like a standard sprinkler - releases water as temperature increases
Can be used in Light Hazard Occupancies
77. 77 Partial Data Sheet for a Typical Concealed Sprinkler
78. 78 Sidewall Sprinkler
79. 79 Sprinkler systems (cont’d) Requirements for water supply capacity and spacing of sprinklers depend upon the building’s occupancy classification
Occupancy Classes:
Light
Ordinary Group 1
Ordinary Group 2
Extra Group 1
Extra Group 2
80. 80 Light Hazard
Quantity and/or combustibility of contents is low; fires with relatively low rates of heat release are expected.
Examples:
Churches
Libraries
Restaurant seating areas
81. 81 Ordinary Hazard Group 1 – combustibility is low, quantity of combustibles is moderate, stockpiles of combustibles do not exceed 8 ft, fires with moderate rates of heat release expected.
Examples:
Automobile parking and showrooms
Bakeries
Restaurant service areas
82. 82 Ordinary Hazard (cont’d) Group 2 – quantity and combustibility of contents moderate to high, stockpiles do not exceed 12 ft, fires with moderate to high rates of heat release expected.
Examples:
Chemical plants - ordinary
Dry Cleaners
Library large stack room areas
83. 83 Extra Hazard Group 1 – combustibility is low, quantity of combustibles is very high, dust, lint or other materials are present, possibility of rapidly developing fires with high rates of heat release, but little or now combustible or flammable liquids.
Examples:
Aircraft hangers
Plywood and particle board manufacturing
Printing
84. 84 Extra Hazard (cont’d) Group 2 – moderate to substantial amounts of flammable or combustible liquids
Examples:
Flammable liquids spraying
Plastics processing
Varnish and paint dipping
In all cases, refer to NFPA 13 and AHJ (Authority Having Jurisdiction) for quidance in assessing occupancy classification
85. 85 Sprinkler systems (cont’d) Maximum Area of Coverage (Standard Spray Upright and Pendant Sprinklers)
Light hazard: 225 s.f., maximum 15’ between sprinklers
Ordinary hazard: 130 s.f., maximum 15’ between sprinklers
Extra hazard: 90 s.f., maximum 12’ between sprinklers (see NFPA 13 for exceptions)
Protection Area per sprinklers:
S x L, where S = spacing between sprinklers or twice distance to end wall, whichever is greater.
L = spacing between branch lines or twice the distance to end wall, whichever is greater.
86. 86 Sprinkler systems (cont’d) Maximum distance from walls: less than ˝ spacing.
Minimum distance to walls: 4”
Where walls are angled or irregular, the maximum distance to any point on floor – 0.75 spacing, with maximum perpendicular distance to wall not exceeded.
Minimum distance between sprinklers: 6’ (see exceptions NFPA 13)
87. 87 Sprinkler Location Deflector position
Standard spray pendant or upright heads: minimum 1” to maximum 12” from ceiling.
Standard spray sidewall sprinklers: minimum 4” to maximum 6” from ceiling. (In special situations, 6 to 12” – see NFPA 13)
Critical point – the farther the sprinkler is from the ceiling, the longer it will take for the heat to collect at the ceiling plane and set off the sprinkler.
88. 88 Typical Symbols
89. 89 Sprinkler Spacing Examples Light Hazard Occupancy
225 s.f. per sprinkler
Maximum 15’ between branch lines and between sprinklers on branch lines
Maximum 15/2 = 7.5 from wall to outermost sprinkler and branch lines
Here, S=L=15’
90. 90 Sprinkler Spacing Example No. 2
Occupancy Hazard:
Ordinary Group 1
Maximum coverage per sprinkler: 130 s.f.
Maximum spacing: 15’
91. 91 Example No. 2 – Proposed Solution
Area of coverage is 10’x 13’ = 130 s.f.
Maximum spacing is 13’, which is less than the maximum 15’ allowed
Maximum distance to wall is 6.5’, which is ˝ the largest spacing (13’)
Yet this solution does not comply with NFPA 13!
92. 92 Example No. 2 (cont’d) Area of coverage of sprinkler in NW corner is: (6+5) x 13 = 141 s.f.
The number of sprinklers required is actually (41’ x 39’)/130 s.f. per sprinkler = 12.3; the proposed solution has just 12
93. 93 Example No. 2 (cont’d) Here is one correct solution.
More sprinklers are required in order to comply with both spacing and area of coverage requirements.
S=12’ (2 x 6); L=9’-8”
A=12’ x 9’-8” = 116.04 s.f
94. 94 Example No. 2 (cont’d) If a 2’x2’ suspended tile ceiling is used, the sprinklers will not be centered within the tiles.
95. 95 Example No. 2 (conclusion) Since we have more sprinklers than are needed, we can shift the centerlines slightly to achieve center of tile placement of sprinklers.
In this example, the dashed area represents greatest coverage, = (5’-6” +5’-0”) x (5’-0” + 6’-0”) = 126.5 s.f.
96. 96 Sprinkler Systems (cont’d) Sprinkler Classifications
Design and performance
Area of coverage
Speed of response
Standard response
Fast response
Orientation
Concealed
Flush
Pendent
Recessed
Sidewall
Upright
97. 97 Sprinkler Classifications (cont’d) Special service conditions
Dry
Corrosion resistant
Intermediate level sprinkler/rack storage sprinkler