Physical Scaling for Performance Evaluation of Water Mist Systems in Enclosures

Physical Scaling for Performance Evaluation of Water Mist Systems in Enclosures. Hong-Zeng (Bert) Yu, FM Global Research Jonathan Carpenter, FM Approvals Fire Sprinkler International May 20-21, 2014 London, United Kingdom. Outline. Motivation Review of the scaling laws

shamus
Download Presentation

Physical Scaling for Performance Evaluation of Water Mist Systems in Enclosures

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Physical Scaling for Performance Evaluation of Water Mist Systems in Enclosures Hong-Zeng (Bert) Yu, FM Global Research Jonathan Carpenter, FM Approvals Fire Sprinkler International May 20-21, 2014 London, United Kingdom

  2. Outline • Motivation • Review of the scaling laws • Scaling law validations • A test case for scaling up water mist protection • Approval process of FM Approval Standard 5560 using scaling approach • Summary

  3. Why scale water mist fire suppression? • To reduce the development cost of water mist fire protection systems in enclosures. • Currently, full-scale testing is required for system development and listing. • Often times it is a trial-and-error process • Full-scale fire testing costs are often prohibitive for niche applications. • Goal: To replicate water mist fire protection with scaled-down facilities.

  4. In geometrically similar control volumes, • Conserve: • Froude number of gas flow Froude-Based Physical Scaling Principles • Momentum transfer characteristics between water droplets and gas flow. • Droplet vaporization characteristics. • Scalar quantities in the control volumes.

  5. Froude-Based Scaling Relationships * Fire Safety Journal, 2012.

  6. A Scaling Illustration for Red <1 Full Scale 20 x 20 x 10 m high Enclosure 4 x 4 m Door Opening 1/4 Scale 5 x 5 x 2.5 m high Enclosure 1 x 1 m Door Opening Fire size 6000 kW 188 kW (S2.5) Water mist discharge rate 100 liters/min 3.1 liters/min (S2.5) Droplet size 90 microns 64 microns (S0.25) Water mist discharge time 30 s 15 s (S0.5)

  7. Validations of Scaling Relationships • Droplet size dependence on Red (Scale ratio = 9 :1) (Fire Safety Journal, 2008) • Spray cooling in open space (Scale ratio = 9:1) (Fire Safety Journal, 2008) • Fire radiation effect (Scale ratio = 9:1) (Fire Safety Journal, 2012) • Fire suppression and extinguishment for different fuel types in enclosures (Scale ratio = 3:1) • Gas fires (propane) (9th IAFSS Symposium, 2008) • Pool fires (heptane) (10th IAFSS Symposium, 2011) • Solid combustible fires (wood cribs) (11th IAFSS Symposium, 2014)

  8. Pool Fire Suppression in Enclosures Scale-3 Enclosure: 3.66x3.66x3.66 m Door Opening: 0.91x1.83 m high 1.83x1.83 m high Scale-1 Enclosure: 1.22x1.22x1.22 m Door Opening: 0.30x0.61 m high 0.61x0.61 m high

  9. Scaling Pool Fires in Open Space -1 Scale-3 Heptane Pool Fires ( Scale-1 Rate x 32.5):0.55-m pool  390 kW 0.74-m pool  900 kW Scale-1 Heptane Pool Fires:Smaller fire: 0.23-m diameter pool  25 kW Larger fire: 0.32-m diameter pool  58 kW

  10. Test Conditions

  11. Fire Locations and Measurements • Fire heat release rate • Floor-level oxygen concentrations

  12. Scalability Evaluation for Pool Fire Suppression Replicate • Fire extinguishability. • Fire heat release rate with time. • Oxygen concentrations.

  13. Ignitable Liquid Cut-Off Room Challenges: 1) low flash point liquids. 2) large door openings. 3) high ceilings. 4) ceiling nozzles only. 5) obstructed fires.

  14. Ignitable Liquid Cut-Off Room Protection* Targeted cut-off room and fire hazard: 1) Cut-off room size: 7.47x7.47x7.47 m high (6 times the Scale-1 enclosure) 2) Door opening: 3.66x3.66 m high (6 times the Scale-1 enclosure’s larger opening) 3) Heptane storage tank: 1.83 m diameter x 2.74 m high, 0.91 m above floor. 4) Fire scenario: Cascading heptanespill from the top of tank at 38 liters/min . (~ 8 MW > 5.1 MW = 58 kW of Scale-1 fire x 62.5) Based on the water mist protection for the Scale-1 enclosure,the water mist requirement for the cut-off room is: *Journal of Fire Protection Engineering, 2013.

  15. Key Components for the Scaling Approach Three key components: • Nozzle spray characterization (droplet size and distribution, spray discharge rate and momentum, spray angle and flux distribution pattern, etc.) • Well mixed model – a predictive tool to assess the total water mist discharge rate and droplet size for full-scale protection, for screening purpose. • Scaling methodology to scale down the large-scale fire tests.

  16. Approval Process for the Scaling Approach After implementing the scaling approach to FM Approval 5560 – Water Mist Systems: • Manufacturer applies for FM Approval with parameters for full-scale protection and supplies scaled-down nozzles to FM Approvals. • FM Approvals assesses the adequacy of the intended full-scale protection parameters with the well-mixed model using data from the scaled-down nozzle characterization activity. This is a screening approach to identify a potential solution that works. • Conduct testing in the scaled-down mockup with the scaled-down protection parameters and nozzles to ensure fire extinguishment results. • Manufacturer submits the full-scale nozzle for spray characterization to ensure meeting the scaled-up requirement. • Approval granted for full-scale protection by scaling up the scaled-down test results according to the scaling relationships.

  17. Current Approach – Full Scale Testing

  18. New Approach – Reduced Scale Testing

  19. Benefits to Industry • Potential reduction in approval cost and time • Potential reduction in internal cost to the manufacturer could be significant due to the screening test availability. • Potential reduction in required number of reduced-scale tests in the future (after gaining some experience) • Ultimately increase the number of certified applications!

  20. Summary • The Froude-based scaling laws have been validated with laboratory experiments for the effects of droplet size, fire radiation, enclosure and different types of combustibles. • The protection of an ignitable liquid cut-off room has been successfully developed by scaling up the known protection requirements for smaller enclosures. • The approval process based on the scaling approach is to be implemented in FM Approval Standard 5560 – Water Mist Systems, to help reduce the system development and approval cost and increase applications.

  21. Questions ?