SmartWire. Less wiring by shifts the I/O level to the contactor. Today : Expensive wiring of the I/Os from the PLC. PLC xyz. Moeller PLC. NOW : Simple wiring and shifting the I/O level to the contactor. easynet CANopen. Profibus DP. System overview. 2x Status DIL and PKZ.
E N D
SmartWire Moeller Holding GmbH Seite - 1
Less wiring by shifts the I/O level to the contactor Today :Expensive wiring of the I/Os from the PLC PLC xyz Moeller PLC NOW :Simple wiring and shifting the I/O level to the contactor easynet CANopen Profibus DP Moeller Holding GmbH Seite - 2
System overview 2x StatusDIL and PKZ up to16 Motor starter 1x command SmartWire Gateway 24 VDC for monitoring 24 VDC Control power (with Emergency Stop) Moeller Holding GmbH Seite - 3
SmartWireSystem modules of the assortment • For connection to the automation level • 1 Gateway easyNet/CANopen • 2 Gateway PROFIBUS DP • 3 XI/ON-Gateway with SmartWire slice (www.microinnovation.com) • For system extension • 4 I/O module • For switching an protection • 5 Direct starter MSC up to 15 kW based on standard switch gear • For building groups of motor starters(Emergency stop, repowering the control power) • 6 SmartWire Power moduleFor connection of motor starter MSC • 7 SmartWire module for fitting at the contactor • 8 SmartWire cable – Connect, don‘t wire • 9 Direct starter MSC-D with SmartWire module • 10 Reverse starter MSC-R with SmartWire module 1 2 3 9 10 5 5 6 4 8 7 Moeller Holding GmbH Seite - 4
SmartWire Module for DILM 7 to DILM 32 X1 X2 F Ready G X3 X4 X1, X2 : Monitoring NHI-E-PKZ0 (Switch-on condition for DIL) X3, X4 : Interlocking the contactor coil Ready : LED Ready (green) F : Indication contactor status (mech.) G : Cable guide Status from the contactor Control contactor coil Moeller Holding GmbH Seite - 5
EASY223-SWIRE Gateway easy223-SWIRE 24 VDC Gateway 24 VDC SmartWire LED: - Status Field bus - Status SmartWire - Power SmartWire - Ready Auto addressing Field bus easy-NET DIP-Switch for - easy-NET/CANopen selection - Node-ID at CANopen SmartWire Moeller Holding GmbH Seite - 6
SWIRE-GW-DP Gateway SWIRE-GW-DP 24 VDC Gateway 24 VDC SmartWire LED: - Status Field bus - Status SmartWire - Power SmartWire - Ready Auto addressing Field bus DIP-Switch for PROFIBUS DP address SmartWire Moeller Holding GmbH Seite - 7
I/O Module SWIRE-4DI-2DO-R Applications for: - DIL M 40 to DIL M 150 - SGL - Solid-State-Relays - monitoring MCBs - other digital I/O 2 Inputs 1 Relay Output Status LED SmartWire SmartWire 2 Inputs 1 Relay Output Moeller Holding GmbH Seite - 8
Power Module SWIRE-PF Power supply 24 VDC for: - new emergency stop group - Re-powering 24 VDC Power LED SmartWire SmartWire Moeller Holding GmbH Seite - 9
Communication system • Up to 16 units per gateway • Automatic configuration via push button • Length max. 4 m • Powering the electronic from the gateway (independent from the emergency stop) • Powering the contactor coil is integrated • Failure of one unit has no impact to the other units • Exchange of an unit by disconnecting the communication line • Response times : • 20 ms for commands (all motor starter simultaneously) • 50 ms for status messages (typical value for 8 motor starter) • 80 ms for status messages (worst case for 8 motor starter) Moeller Holding GmbH Seite - 10
easyNet Gateway SmartWire Connection via easyNet XC200 easy800 EC4P MFD-Titan Max. 8 devices SmartWire(up to 16 devices per gateway) SmartWire Moeller Holding GmbH Seite - 11
easyNet SmartWireApplication with easy800 via easyNet easy800 easySoft Moeller Holding GmbH Seite - 12
CANopen Gateway SmartWire Connection via CANopen XC200 EC4P Touch Text SmartWire(up to 16 devices per gateway) SmartWire Moeller Holding GmbH Seite - 13
Profibus-DP Gateway SmartWire Connection via Profibus DP XC200 Siemens S7 … Touch Text SmartWire(up to 16 devices per gateway) SmartWire Moeller Holding GmbH Seite - 14
Configuration of SmartWire in Step 7 SmartWire - DP - Interface as PROFIBUS unit Hardware catalogue of SmartWire units Target configuration of the SmartWire IO mapping of the S7-CPU and SmartWire Moeller Holding GmbH Seite - 15
Field bus connection with additional I/O For future extensions Gateway I/O slices Motor starter Interface for SmartWire MSC with PKZM0 + SmartWire Module for DILM Moeller Holding GmbH Seite - 16
1SWIRE DIA Rdy SW Cfg USW UAUX MOELLER 1 2 3 4 5 6 E R I W S XI/ON XNE-1SWIRE Module Communicationslice for networking motor starter • 1 slice per SmartWire line • max. 3 slices per gateway • 16 SmartWire devices • Per device 4Bit input, 4Bit output • SWIRE-DIL: • DI • Bit 0: Status DIL • Bit 1: Status PKZ • Bit 2: free • Bit 3: free (Slave diagnostic adjustable) • DO • Bit 0: ON command • Bit 1..3: free Moeller Holding GmbH Seite - 17
The kit for all solutions Remote I/O + Motor starter with SmartWire Motor starter with SmartWire Module + Component-adapter for busbar Motor starter with SmartWire Module Motor starter Components Control circuit- wiring and save PLC I/O Reduce wiring of the control circuit and main circuit Plug and play for I/O and Motor starter Save mounting space and wiring of the main circuit Moeller Holding GmbH Seite - 18
SmartWireApplications Motor starter up to 15 kW size I + II Motor starter up to 560 kW, contactors up to 2000 A MCB Soft starter + + + with SmartWire I/O Module with SmartWire I/O Module with SmartWire Module for DILM with SmartWire I/O Module SWIRE-4DI-2DO-R SWIRE-4DI-2DO-R SWIRE-4DI-2DO-R SWIRE - DIL Moeller Holding GmbH Seite - 19
Abstract I • Use standard devices and device accessories (DIL + PKZ) • Substitution of the controlwiring • Simplification of the design and the documentation by less terminals • Less wire ducts at the switchboard Moeller Holding GmbH Seite - 20
Abstract II • Quick mounting and commissioning with toolless plug connection and snap up the SmartWire Module for DILM • Using of all accessories of the xStart system • Re-fitting for all contactors of the xStart line • Free I/O for connection to the system (e.g. incoming breaker) Moeller Holding GmbH Seite - 21
Abstract III • Easy handling with addressing by push button only • Automatic addressing requires no special knowlegth of communication systems Moeller Holding GmbH Seite - 22