1 / 9

CURRENT LIMITING FUSES FOR OVERHEAD TRANSFORMERS

CURRENT LIMITING FUSES FOR OVERHEAD TRANSFORMERS. Why consider current limiting fuses?. Originally a question on overhead transformer fusing. Led to a suggestion to investigate using smaller fuses to limit oil spills from overhead transformers.

tamyra
Download Presentation

CURRENT LIMITING FUSES FOR OVERHEAD TRANSFORMERS

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. CURRENT LIMITING FUSES FOR OVERHEAD TRANSFORMERS

  2. Why consider current limiting fuses? Originally a question on overhead transformer fusing. Led to a suggestion to investigate using smaller fuses to limit oil spills from overhead transformers. Evolved into a suggestion to utilize current limiting fuses to limit oil spills from internal faults in overhead transformers.

  3. Oil Spills- Causes • Year Overload Internal Fault • 2003 273 133 • 2002 152 147 • 2001 122 124

  4. Current Limiting Fuses Looked at utilizing Cooper NXII CL fuse mounted either at the cutout or on the transformer. Cost ranged from approximately: $ 25/ for up to 12 amp $ 30/ for 15- 25 amp $ 40/ for 30- 40 amp

  5. Survey • Informal survey of SWEDE and EEI member companies. • Only three respondents used current limiting fuses for overhead transformers (CPS, Centerpoint & Exelon). • Among reasons cited included controlling catastrophic failures.

  6. Findings • Current Limiting fuse could alleviate some oil spills due to internal fault. • Number would be limited. • Fault Current limited by reactors • Dependent on degree of protection • The cost of adding CL fuses to all overhead units was greater than the anticipated cost of oil spills. • Possible operating issues.

  7. QUESTIONS?

More Related