OLTC Failure. 45MVA 132kV. Manufacturer Takaoka Japan. 16 positions No change-over switch. Linear design of tap winding. Bucholz tripped the unit. OLTC oil sample. Bucholz relay oil sample. Phase U. Even positions higher resistance. Odd and Even contacts. Burned contacts.
E N D
OLTC Failure 45MVA 132kV
ManufacturerTakaoka Japan 16 positions No change-over switch Linear design of tap winding
Bucholz tripped the unit OLTC oil sample Bucholz relay oil sample
Phase U Even positions higher resistance
Phase W PROBLEM