150 likes | 378 Views
2010 MOTION SENSOR FORUM. SYSTEM INTEGRATION Gerry Cornwell, LC. Overview. Technical Issues TAF LightSavers Pilot Matrix. Technical Issues. Technical Issues Lamp issues Ballast issues Wiring issues. Technical Issues. Lamp Issues Incandescent Short life (2,000 hrs)
E N D
2010 MOTION SENSOR FORUM SYSTEM INTEGRATIONGerry Cornwell, LC
Overview • Technical Issues • TAF LightSavers Pilot • Matrix Gerry Cornwell Lighting
Technical Issues • Technical Issues • Lamp issues • Ballast issues • Wiring issues Gerry Cornwell Lighting
Technical Issues • Lamp Issues • Incandescent • Short life (2,000 hrs) • Low efficacy (15 LPW) • Instant ‘on’ • Not affected by frequent switching • Lowest first cost upgrade to CFL • Savings 60-75% Gerry Cornwell Lighting
Technical Issues • Lamp Issues • CFL (Compact Fluorescent) • Longer life (6,000-10,000 hrs) • Higher efficacy (60 LPW) • OK for frequent switching • Somewhat affected by cold temperatures • Requires appropriate fixture Gerry Cornwell Lighting
Technical Issues • Lamp Issues • Linear Fluorescent • Long life (+20,000 hrs) • Higher efficacy (+90 LPW) • Can be affected by frequent switching • Depends on lamp wattage • Very affected by cold temperatures • Light loss • Starting, particularly 25W lamps Gerry Cornwell Lighting
Technical Issues • Lamp Issues • Induction • Very long life (+70,000 hrs) • Higher efficacy (+80 LPW) • Not affected by frequent switching • Not affected by cold temperatures • Assuming appropriate luminaire Gerry Cornwell Lighting
Technical Issues • Lamp Issues • HID: High Pressure Sodium • Long life (+24,000 hrs) • Higher efficacy (+90 LPW) • Cannot be frequent switched • Not affected by cold temperatures Gerry Cornwell Lighting
Technical Issues • Lamp Issues • HID: Metal Halide • Long life (+16,000 hrs) • Higher efficacy (+80 LPW) • Cannot be frequent switched • Not affected by cold temperatures Gerry Cornwell Lighting
Technical Issues • Lamp Issues • LED • Long life (+70,000 hrs) • Higher efficacy (+80 LPW) • Can be frequent switched • Not affected by cold temperatures • High initial cost Gerry Cornwell Lighting
TAF LightSavers Pilot • Parking Garages • Two underground garages in residential buildings • Using HPS luminaires on 24/7 • New T8 fluorescent luminaires with integral occupancy sensors, 2 light levels • New LED luminaires with integral occupancy sensors, 2 light levels Gerry Cornwell Lighting
TAF LightSavers Pilot • Results • Light levels lower but within IES standards • Appearance brighter due to improved light colour (white light) • No negative reaction to sensor operation by residents • Energy savings for lights only +57% • Energy savings for OS +13% • Total energy savings +70% Gerry Cornwell Lighting
Matrix Gerry Cornwell Lighting
Conclusion • System Integration • This is not an easy retrofit project • Essential that lighting, security and life safety systems are integrated • Example: in the event of a fire alarm, all sensors are by-passed or activated ‘on’ • Garage projects typically incorporate renewal issues Gerry Cornwell Lighting
Questions? • Thank you… Gerry Cornwell Lighting