1 / 10

Cal Poly San Luis Obispo Water Conservation Best Practices

Cal Poly San Luis Obispo Water Conservation Best Practices. UC/CSU/CCC Sustainability Conference UCSB June 24-27, 2007 Presented by Dennis K. Elliot, PE Manager of Engineering and Utilities. Cal Poly San Luis Obispo Water Conservation Best Practices. Low Flow Fixture Retrofits of over:

teigra
Download Presentation

Cal Poly San Luis Obispo Water Conservation Best Practices

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Cal Poly San Luis ObispoWater Conservation Best Practices UC/CSU/CCC Sustainability Conference UCSB June 24-27, 2007 Presented by Dennis K. Elliot, PE Manager of Engineering and Utilities

  2. Cal Poly San Luis ObispoWater Conservation Best Practices Low Flow Fixture Retrofits of over: 200 low flow urinals – 1.5 gpf 200 low flow toilets – 1.6 gpf 300 lavatory faucets – 1.0 gpm 500 shower heads – 2.5 gpm

  3. Cal Poly San Luis ObispoWater Conservation Best Practices Total project cost $238,000 Water savings: 39,000 CCF or 29 Million gal per year - 15% of campus total Approx 25,000 gal per fixture Utility cost savings $240,000 per year @$3/ccf for water, $3/ccf for sewer

  4. Cal Poly San Luis ObispoWater Conservation Best Practices Waterless vs. Ultra Low Flow Waterless pros & cons: Zero water usage saves 45,000 gpy More housekeeping required Oil seal replacement Do not pour water down drain! Cartridge replacement Supply piping still required by code

  5. Cal Poly San Luis ObispoWater Conservation Best Practices Waterless vs. Ultra Low Flow Ultra Low Flow Urinal pros & cons: 1/8 gpf achieves 90% of waterless savings Less housekeeping required No oil seal or cartridge replacement Works well with sensored flush valves

  6. Cal Poly San Luis ObispoWater Conservation Best Practices LEED EB Pilot Project Faculty Office East Building - 20,000 gsf Retrofit all fixtures to ULF, sensored 1/8 gpf Zurn urinals 0.5 gpm sensored faucets Will achieve 60% reduction in usage Qualifies for two LEED points for water efficiency – Credit 3.1 and 3.2 Project cost $15,000 Payback period 8 years

  7. Cal Poly San Luis ObispoWater Conservation Best Practices Other Conservation Efforts Irrigation controls Eliminate “once through” cooling Public awareness Metering and monitoring Management of boilers, cooling towers, water softeners, closed loops

  8. Cal Poly San Luis ObispoWater Conservation Best Practices Unexpected Consequences: Increased concentration of regulated substances in effluent to city.

  9. Cal Poly San Luis ObispoWater Conservation Best Practices Unexpected Benefits: Conservation eliminated need for previously projected future sewer capacity Resulted in $2M savings to Poly Canyon Village Housing project Funds returned to project to help pay for additional sustainability features

  10. Cal Poly San Luis ObispoWater Conservation Best Practices Questions?