170 likes | 355 Views
Lt. Commercial Product Updates. 2013 Zone Service Manager’s Meeting. Light Commercial Product Support Matrix. Robin Craft SRT’s Robin.Craft@carrier.utc.com 317-240-5329 Bill Sircy MRT’s/Software Bill.Sircy@carrier.utc.com 317-240-5336. Joe Long Splits Joe.Long@carrier.utc.com
E N D
Lt. Commercial Product Updates 2013 Zone Service Manager’s Meeting
Light Commercial Product Support Matrix • Robin Craft • SRT’s • Robin.Craft@carrier.utc.com • 317-240-5329 • Bill Sircy • MRT’s/Software • Bill.Sircy@carrier.utc.com • 317-240-5336 • Joe Long • Splits • Joe.Long@carrier.utc.com • 317-240-5114 • John Ferrel • Back-up • John. A.Ferrel@carrier.utc.com • 315-708-8313
SERIAL NUMBER SEARCH UTC Climate | Controls | Security Confidential and Proprietary Information Not for Further Distribution
SERIAL NUMBER SEARCH UTC Climate | Controls | Security Confidential and Proprietary Information Not for Further Distribution
SERIAL NUMBER SEARCH SRT & MRT UTC Climate | Controls | Security Confidential and Proprietary Information Not for Further Distribution
CMX–C and CMX-DSERIAL NUMBER INFORMATION • SERIAL NUMBERS WITH “C” OR “P” • Click on the link • new screen appears with a text box • Type in serial number/s • Click submit • Option for more than one exists by use of the “add” button UTC Climate | Controls | Security Confidential and Proprietary Information Not for Further Distribution
ETPSERIAL NUMBER INFORMATION SERIAL NUMBERS WITH “G” CLICK ON THE LINK NEW SCREEN APPEARS TYPE NUMBER IN SUBJECT LINE ( SN * 2013Gxxxxx) CLICK SEND A SHORT TIME LATER … RECEIVE AN EMAIL WITH ATTACHMENTS… UNIT WIRING DIAGRAMS UNIT CHARGE CHARTS UNIT BOM tylapps@carrier.utc.com UTC Climate | Controls | Security Confidential and Proprietary Information Not for Further Distribution
KNOCKOUTS ISSUE: Knockouts falling off panels during shipment ROOT CAUSE: Excessive force used in press Dies not balanced UTC Climate | Controls | Security Confidential and Proprietary Information Not for Further Distribution
KNOCKOUTS CORRECTIVE ACTION Factory: Adjustments made to the Die balancing process Tab size was increased at CMX-D Containment 5/23/2013 Long term corrective action: Units ordered with NFD’s will have knockout panels only, as well as RC replacements. UTC Climate | Controls | Security Confidential and Proprietary Information Not for Further Distribution
48TC 3-12.5 TON Humidi-Mizer® System Update UPDATE: Freeze protection thermostat wired in series with the solenoid valves and not the compressor(s), keeping the compressors running, causing the evaporator coil to freeze up and possible overcooling the space. UTC Climate | Controls | Security Confidential and Proprietary Information Not for Further Distribution
Humidi-Mizer® System Update Locate FPT sensor wiring. If necessary, move to the compressor contactor to allow the compressor(s) to shutdown to prevent coil freeze up and overcooling the space. Field instructions are being completed and will become available thru RC Factory wiring revision implemented on 8/28/2013 UTC Climate | Controls | Security Confidential and Proprietary Information Not for Further Distribution
48TC Humidi-Mizer® System PIPING UPDATE • Units Affected:48/50 TC04,05,06,07,08,09,12,14 HGRH • Factory Modification:REPLACE EQUALIZER FLARED TUBE & SUCTION LINE SIDE PORT WITH A STRAIGHT END TUBE & BRAZE JOINT. (SAME AS HC UNITS) to assist with error proofing • Reason for Modification:MFG ADDING SCHRADER CORES • Implemented 8/28/2013 UTC Climate | Controls | Security Confidential and Proprietary Information Not for Further Distribution
SRT RTU-OPEN With Humidi-Mizer® System UPDATE 48/50 TC SIZE 04-14 FIOP RTU-OPEN with Humidi-Mizer The connection of the humidistat to the control board was a field required connection of the 2 pink wires provided in the control box (loose) • Humidistat will be wired to the RTU-OPEN board at J11, terminals 7 & 8 at the factory when both FIOP’s are installed • Factory wiring revision implementation - 8/28/2013 UTC Climate | Controls | Security Confidential and Proprietary Information Not for Further Distribution
48/50 LC with RTU OPEN • COMING SOON! SRT 48/50LC 3-5 TON Units will have RTU OPEN as a factory installed option Electro-mechanical with a new ICS board # HK50AA054 (RCD Service Replacement)
48/50 LC with Humidi-Mizer® System • COMING SOON! SRT 48/50LC 3-5 TON Units will have Humidi-Mizer as a factory installed option Electro-mechanical with a new ICS board # HK50AA054 Integrated logic for Humidi-Mizer Available – Release Q1 2014 (TBA)
CMX-C Coil Improvement D I V E UTC Climate | Controls | Security Confidential and Proprietary Information Not for Further Distribution
2013 CMX-C Coil Improvements UTC Climate | Controls | Security Confidential and Proprietary Information Not for Further Distribution