CEN Hazard Classification for Sprinklers and Water Mist

CEN Hazard Classification for Sprinklers and Water Mist. Dr. Maarit Tuomisaari Marioff Corporation Oy. EN 12845:2003 for sprinklers Hazard classification based on long-term experience Given hazard classification reflects the challenge to the

thom
Download Presentation

CEN Hazard Classification for Sprinklers and Water Mist

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. CEN Hazard Classificationfor Sprinklers and Water Mist Dr. Maarit Tuomisaari Marioff Corporation Oy IFSA 2008 / 24 - 25 June, 2008

  2. EN 12845:2003 for sprinklers • Hazard classification based on long-term experience • Given hazard classification reflects the challenge to the • 2-dimensional wetting of traditional water sprays. • prCEN/TS 14972 for water mist systems • No hazard classification specified. • The sprinkler classification does not necessarily reflect the • challenge to water mist systems that do not rely only on • wetting but also on 3-dimensional inerting, cooling of gases • and blocking of radiant heat. IFSA 2008 / 24 - 25 June, 2008

  3. EN 12845:2003 for sprinklers Prescriptive requirements OH1 OH2 OH3 OH4 Design density (mm/min) 5 5 5 5 Area of operation (m2) 72 144 216 360 Nominal number of sprinklers 6 12 18 30 prCEN/TS 14972 for water mist systems Performance-based requirements OH1 OH2 OH3 OH4 Design density ”equivalent” to 5 mm/min Area of operation (m2) 72 144 216 360 Nominal number of sprinklers depends on the coverage area (1 (1 (1 not a requirement but common practice IFSA 2008 / 24 - 25 June, 2008

  4. EN 12845:2003 OH1 Occupancies prCEN/TS 14972 IFSA 2008 / 24 - 25 June, 2008

  5. prCEN/TS 14972 OH1 Occupancies / offices • Reference sprinkler: • Pendent spray sprinkler • Special Response • Nominal K factor 80 • Temperature rating 68 ºC • Fire tests: • Ignition under one sprinkler • Ignition between four sprinklers • Repetition of the worse one • Criteria to be defined: • Fire damage • Temperatures IFSA 2008 / 24 - 25 June, 2008

  6. prCEN/TS 14972 OH1 Occupancies / offices • Water Mist sprinkler: • To be defined in the tests • Fire tests: • Ignition under one sprinkler • Ignition between four sprinklers • Repetition of the worse one • Criteria: • Fire damage as per REF • Temperatures as per REF IFSA 2008 / 24 - 25 June, 2008

  7. prCEN/TS 14972 OH1 Occupancies / offices VdS approval coverage with an extensive number of additional fire tests according to FM, IMO and VdS test procedures • Design criteria System A System B • - water density < 0.6 mm/min 1.5 mm/min • coverage per sprinkler 12.25 m2 25 m2 IFSA 2008 / 24 - 25 June, 2008

  8. prCEN/TS 14972 OH1 Occupancies / offices • Conclusions: • For OH1 type hazards the number of • sprinklers activating is the same for both • the sprinkler and referred water mist • systems. • Number of sprinklers is a more relevant • design parameter than a fixed operation • area. IFSA 2008 / 24 - 25 June, 2008

  9. EN 12845:2003 OH3 Occupancies prCEN/TS 14972 - proposal IFSA 2008 / 24 - 25 June, 2008

  10. prCEN/TS 14972 - proposal OH3 Occupancies IFSA 2008 / 24 - 25 June, 2008

  11. prCEN/TS 14972 OH3 Occupancies VdS approval coverage with REF system operated at 8 mm/min instead of 5 mm/min • Design criteria • - water density 3.8 mm/min • coverage per sprinkler 9 m2 IFSA 2008 / 24 - 25 June, 2008

  12. prCEN/TS 14972 – proposal OH3 Occupancies • Conclusions: • For OH3 type hazards the number • of sprinklers activating is different • for the sprinkler and referred water • mist system. • Number of sprinklers is a more • relevant design parameter than a • fixed operation area. IFSA 2008 / 24 - 25 June, 2008

  13. prCEN/TS 14972 – proposal OH3 Occupancies Aspect that is not taken into account at all: REF17 700 LITRES WATER WATER MIST4100 LITRES WATER IFSA 2008 / 24 - 25 June, 2008

  14. Study on operation areas together with Dr.Jukka Vaari, VTT, Finland 2 MW concealed pallet pile2 MW open pool4 m & 2.5 m ceiling heights IFSA 2008 / 24 - 25 June, 2008

  15. 2 MW concealed pallet pile / 2.5 m ceiling height REF WATER MIST Number of sprinklers activating in the tests REF (5 mm/min) Water Mist System (OH1) 4 – 15 / 184 m2 1 – 4 / 100 m2 IFSA 2008 / 24 - 25 June, 2008

  16. 61.25 m2 - 3 mm/min 80 m2 - 2.3 mm/min 100 m2 - 1.5 mm/min IFSA 2008 / 24 - 25 June, 2008

  17. SUMMARY • Prescriptive requirements of EN 12845 may well be justified • based on the long-term experience with sprinklers. • Prescriptive dimensioning of EN 12845 based on fixed • prescripitive hazard classification should not be mixed with • the performance based design of prCEN/TS 14972 • Number of nozzles is a more relevant design parameter than a fixed area • Relevant design fires – instead of fixed hazard classification – to be developed for defining the design number of nozzles • Experience and dedicated research will lead to performance-based ”hazard classification”, i.e. correspondence between each design fire and different hazard types. IFSA 2008 / 24 - 25 June, 2008

  18. THANK YOU ! IFSA 2008 / 24 - 25 June, 2008