Welcome to VRF System Design Training Course for. System & Sales engineer Pin CAI Akimasa SHIRAI. 1. EQUIPMENT SELECTION. 1-1 EQUIPMENT SELECTION PROCEDURE / LINE-UP 1-2 MODEL SELECTION AND CAPACITY CALCULATION 1-3 RESTRICTIONS ON EQUIPMENT SELECTION.
E N D
Welcome to VRF System Design Training Course for System & Sales engineer Pin CAI Akimasa SHIRAI
1. EQUIPMENT SELECTION 1-1 EQUIPMENT SELECTION PROCEDURE / LINE-UP 1-2 MODEL SELECTION AND CAPACITY CALCULATION 1-3 RESTRICTIONS ON EQUIPMENT SELECTION
1-1 EQUIPMENT SELECTION PROCEDURE / LINEUP ■ INDOOR UNIT LINEUP (1/2)
1-1 EQUIPMENT SELECTION PROCEDURE / LINEUP ■ INDOOR UNIT LINEUP (2/2)
1-1 EQUIPMENT SELECTION PROCEDURE / LINEUP ■ REQUIRED OPTIONAL PARTS
1-1 EQUIPMENT SELECTION PROCEDURE / LINEUP ■ OUTDOOR UNIT LINEUP Controller Box
1-1 EQUIPMENT SELECTION PROCEDURE / LINEUP ■ OUTDOOR UNIT COMBINATION ■ CAPACITY RANGE
1-1 EQUIPMENT SELECTION PROCEDURE / LINEUP ■ CONTROLLER UNIT LINEUP
1-1 EQUIPMENT SELECTION PROCEDURE / LINEUP ■ ADAPTOR / CONVERTOR LINEUP
1-1 EQUIPMENT SELECTION PROCEDURE / LINEUP ■ OPTIONAL PARTS (OTHERS) (1/2)
1-1 EQUIPMENT SELECTION PROCEDURE / LINEUP ■ OPTIONAL PARTS (OTHERS) (2/2)
1-1 EQUIPMENT SELECTION PROCEDURE / LINEUP 7 to 84 14 to 90 7 to 60 174 to 560 181 to 567 7 to 252 ■ OPTIONAL PARTS (BRANCH KIT) (1/3) 90, 91, 180 and 181 are the total values for the indoor unit model code connected downstream. 84 to 173 91 to 180 7 to 90
1-1 EQUIPMENT SELECTION PROCEDURE / LINEUP ■ OPTIONAL PARTS (BRANCH KIT) (2/3) 2 branches Separation tube 90, 91 180 are the total values for the indoor unit model code connected downstream.
1-1 EQUIPMENT SELECTION PROCEDURE / LINEUP ■ OPTIONAL PARTS (BRANCH KIT) (3/3)
1-2 MODEL SELECTION AND CAPACITY CALCULATION COOLING HEAT LOAD : 120W / m2
1-2 MODEL SELECTION AND CAPACITY CALCULATION (TCin)f From capacity table
1-2 MODEL SELECTION AND CAPACITY CALCULATION Compensation coefficient = 0.903 H = 20m L = 67m
1-2 MODEL SELECTION AND CAPACITY CALCULATION Room 5 (TCin)e < Heat load Change indoor unit
1-2 MODEL SELECTION AND CAPACITY CALCULATION AU30 8.80 9.43 8.52 (TCin)e > Heat load
1-2 MODEL SELECTION AND CAPACITY CALCULATION ① ② Sum of ① 68.4 Sum of ② 73.3
1-2 MODEL SELECTION AND CAPACITY CALCULATION 22HP(AJ*126LATF + AJ*A72LATF) 62.4 68.4 / 62.4 = 109.6%
1-2 MODEL SELECTION AND CAPACITY CALCULATION 22HP(AJ*126LATF + AJ*A72LATF) 62.4 68.4 / 62.4 = 109.6% 68.99 0.903 69.88 x 0.903 = 63.1
1-2 MODEL SELECTION AND CAPACITY CALCULATION (i) Total indoor unit capacity at design temperature 73.3 (ii) Compensated capacity of outdoor unit63.1 The smaller one of (i) and (ii) 63.1 22HP (AJ*126LATF + AJ*A72LATF) 69.88 0.903 69.88 x 0.903 = 63.1
1-2 MODEL SELECTION AND CAPACITY CALCULATION I. U.capacity System capacity x Total of I. U. capacity 11.7 11.711.7 11.7 8.12 8.12
1-2 MODEL SELECTION AND CAPACITY CALCULATION Smaller than heat load
1-2 MODEL SELECTION AND CAPACITY CALCULATION 22HP ⇒ 24HP 24HP(AJ*126LATF + AJ*A90LATF) 68.0 68.4 / 68.0 = 100.6%
1-2 MODEL SELECTION AND CAPACITY CALCULATION 22HP ⇒ 24HP 24HP(AJ*126LATF + AJ*A90LATF) 68.0 68.4 / 68.0 = 100.6% 73.10 0.903 66.0 Total of indoor unit : 73.3 kW 66.0 12.3 12.3 12.3 12.3 8.49 8.49 12.0 12.0 12.0 12.0 7.44 8.40 Actual capacity ⇒ Heat load
1-2 MODEL SELECTION AND CAPACITY CALCULATION (System capacity characteristic) Cooling
1-2 MODEL SELECTION AND CAPACITY CALCULATION (System capacity characteristic) Cooling Indoor temp 19℃WB
1-2 MODEL SELECTION AND CAPACITY CALCULATION (System capacity characteristic) Cooling Rated capacity ratio 100%
1-2 MODEL SELECTION AND CAPACITY CALCULATION (System capacity characteristic) Heating
1-2 MODEL SELECTION AND CAPACITY CALCULATION (System capacity characteristic) Heating Indoor temp 20℃DB
1-2 MODEL SELECTION AND CAPACITY CALCULATION (System capacity characteristic) Heating Rated capacity ratio 100%
1-3 RESTRICTIONS ON EQUIPMENT SELECTION ■ CONNECTABLE UNIT IN ONE REFRIGERANT SYSTEM Master Unit Slave Unit Slave Unit
1-3 RESTRICTIONS ON EQUIPMENT SELECTION ■ MAXIMUM CONNECTABLE INDOOR UNIT (1/2)
1-3 RESTRICTIONS ON EQUIPMENT SELECTION ■ MAXIMUM CONNECTABLE INDOOR UNIT (1/2) ΣIndoor units capacityOutdoor unit capacity Based on rated cooling capacity