Intelligent Control Panel SLC. Branch Line Resistor from End of Line to FACP Shall Not Over 50 ohms per Branch. M. M. M. M. M. M. M. M. M. FACP. NFPA Style 4 SLC. Twisted Unshielded Pair 12 to 18 AWG SLC Distance 12 AWG 3180 M 16 AWG 1486 M
E N D
Branch Line Resistor from End of Line to FACP Shall Not Over 50 ohms per Branch M M M M M M M M M FACP NFPA Style 4 SLC Twisted Unshielded Pair 12 to 18 AWG SLC Distance 12 AWG 3180 M 16 AWG 1486 M 14 AWG 2438 M 18 AWG 986 M
M M M M M M M M M FACP Style 4 with Isolators
M M M M M M M M M NFPA Style 6 SLC Loop Resistor from End of Line to FACP Shall Not Over 50 ohms
M M M M M M M M M Style 6 with Isolators • SLC address capacity of loop is reduced by 2 addresses for every isolator device in excess of 200.
SLC address capacity of loop is reduced by 2 addresses for every isolator device in excess of 200. ISO ISO ISO ISO M ISO ISO C ISO ISO M ISO ISO ISO ISO ISO ISO Style 7
(+) SLC Channel A no connection (-) SLC Channel A NFS-640 Floating Shield
SLC Data Formats FlashScan is an algorithm that greatly enhances the speed of communication between the Analog intelligent devices. If one of the devices within a single group has new information, The panel CPU stops the group poll and concentrates on single points. The net effect is a response speed greater than five times that of earlier designs.
9 0 8 7 9 6 10 5 11 8 4 1 12 3 13 2 7 1 14 2 0 15 TENS 8 7 9 6 5 6 3 4 3 2 5 4 1 0 ONES ADDRESS LOOP FlashScan Modules Break-off address stop for panels with FlashScan Mode.
FZM-1 接點3、4需接可復歸( Resettable) DC 24電源接線採用Class B時,終端電阻為3.9KΩ
FCM-1 輸出接線採用Class B時 接點6、7之終端電阻為47KΩ、1/2W
FRM-1 外接負載應小於模組之接點容量 接 點 容 量 電阻性元件 30VDC @ 2A 電感性元件 30VDC @ 1A交流元件 125VAC @ 0.5A
1 2 3 4 Devices - Modules • Isolator Module (ISO-X) • Supervises loop wiring for short circuit conditions • Allows critical component functions • Required for Style 7 operation • Supported by FlashScan and CLIP systems
9 0 8 1 7 2 8 7 9 6 8 10 6 5 6 3 11 4 4 12 3 2 5 13 4 2 0 1 14 ONES 0 15 TENS ADDRESS LOOP FDM-1 Wiring Class B The circuit connected to terminals 6 & 7 are assigned the base address. The circuit connected to terminals 8 & 9 are assigned the base address plus 1. RED LED lights for either circuit 1 or circuit 2 alarm.
Control Module FCM-1 Class A or B NAC, Speaker or Telephone 2A @ 30VDC 43.75W @ 25 Vrms 43.75W @ 70.7 Vrms 40 Ohm telephone riser Relay Module FRM-1 Dual Form-C operation (DPDT) 8 7 9 6 10 5 11 4 12 3 13 2 1 14 0 15 TENS 8 7 9 6 5 4 3 2 1 0 ONES 9 0 8 1 7 2 6 3 5 4 ADDRESS LOOP FCM-1 Control Modules
1 2 3 4 Devices - Modules • Isolator Module (ISO-X) • Supervises loop wiring for short circuit conditions • Allows critical component functions • Required for Style 7 operation • Supported by FlashScan and CLIP systems
Wiring the B224BI Isolator Base Twisted Pair Recommended Listed FACP Isolator bases prevent an entire communication loop from being disabled when a short circuit occurs, by isolating that part from the remainder of the circuits. OTHER INTELLIGENT DEVICES
Wiring the B710HD Base AUX POWER SUPPLY SLC
Wiring an NBG-12LX Pull Station + SLC - + SLC -
Building 2 Building 1 P P P = Primary S= Secondary S P S P Wiring Surge Suppressor