An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Spill and Overfill Prevention Alaska Spring 2004

  2. The Basics • Spill Prevention Device • Overfill Prevention Device • A Caution about Ball Float Valves and Alarms • Fuel Deliveries • Periodic Maintenance

  3. 18 AAC 78.040 • Spill and Overfill Control. (a) To prevent spilling and overfilling associated with the transfer of petroleum to a UST, the owner or operator of a UST system shall, subject to (e) of this section, use the following spill and overfill prevention equipment.

  4. (1) spill prevention equipment, such as a spill catchment basin, that will prevent release of the petroleum to the environment when the transfer hose is detached from the fill pipe; and (2) overfill prevention equipment that will (A) automatically shut off flow into the tank when the tank is no more than 95 percent full; or (B) alert the transfer operator when the tank is no more than 90 percent full by restricting the flow into the tank or by triggering a high-level alarm.

  5. Spill Prevention Device • See Operation Inspection Form, Section 4a Spill Device • Spill Bucket – required (#1) • Bucket clean and free of debris and water. (#2) • Bucket has no cracks or holes. (#3)

  6. Periodic Maintenance • A spill bucket full of water, fuel or junk is the second-most common operational violation in Alaska. • A spill bucket full is not really a spill bucket. • Cleanout your buckets periodically • ADEC recommends spring and fall. • Check seal around bucket lid.

  7. Overfill Device Options • Overfill Alarm set at 90% • Overfill Shut-Off set at 95% • Ball Float Valve set at 95%

  8. A Caution about Overfill Alarms • Operators tend to silence them • Or ignore them • Probes can go bad • Alarms might not be situated where the driver can see or hear them.

  9. Vent Restriction Devices • Vent restriction devices are also called “ball-float valves” • The Petroleum Equipment Institute (PEI) added language in 2000 that highlights the incompatibility of ball float valves with certain UST applications and issued warnings. • See PEI/RP 100-2000, 6.3.3 Vent Restriction Devices

  10. A Caution about Ball Float Valves • May actually cause an overfill • Incompatible with • Suction Piping • Remote Fills • Pressurized Deliveries • Emergency Generators

  11. Emergency Generators PEI/RP 100-2000 edition, Page 13, Section 6.3.3 issues this warning: A vent restriction device should not be installed on emergency generator or heating oil tanks. ADEC decided to adopt this restriction to prevent overfills with 18 AAC 78.040(e).

  12. Spill and Overfill Control - 18 AAC 78.040 (e) If a UST system has one or more of the following, the owner or operator of the system shall not use a ball float valve or vent restrictor shut-off device on that system: • A tank that receives a pumped delivery • Suction piping with air eliminators • Remote fill pipes and gauge openings • An emergency generator

  13. Vent Restriction Devices & Emergency Generators Vent restriction devices should not be installed on emergency generator or heating oil tanks. The reason is that typically, these tanks are filled by the gravity method.  So, when the vent restriction device (ball-float valve) closes it creates a static head from the transport/fuel oil or heating oil delivery truck and forces product up the suction line. The liquid is seeking the same level as that in the transport. • For more information, contact PEI • BYoung@pei.org

  14. Fuel Deliveries • Owners and Operators must ensure the following: • the tank is measured immediately before each delivery to make sure there is enough room in the tank • the entire transfer is monitored • overfills do not occur • if overfills do occur, they are reported and cleaned up.

  15. Fuel Delivery Checklist • Post the DEC checklist. • “What To Do Before, During and After a Fuel Delivery.” • A copy of this checklist is in your packet.