ADS / PHX SERIES SYSTEMS DESIGN

ADS / PHX SERIES SYSTEMS DESIGN. What is the ADS / PHX Series?. FM-200 Stored under its own vapor pressure. 44 psig. Kidde. FM-200. What is the ADS / PHX Series?. Separate nitrogen storage. N 2. 1800 psig. N 2. What is the ADS / PHX Series?. Continuous Supply of Nitrogen.

vance-wynn
Download Presentation

ADS / PHX SERIES SYSTEMS DESIGN

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. ADS / PHX SERIES SYSTEMS DESIGN

  2. What is the ADS / PHX Series? • FM-200 Stored under its own vapor pressure 44 psig Kidde FM-200

  3. What is the ADS / PHX Series? • Separate nitrogen storage N2 1800 psig

  4. N2 What is the ADS / PHX Series? • Continuous Supply of Nitrogen Acts as a Gas Piston - “Piston Flow”

  5. N2 360 psig Why do we need the ADS / PHX Series? • FM-200 superpressurized with nitrogen Dissolved Nitrogen FM-200

  6. ADS Series ECS / 9300 Series System Performance Comparison 400 psig Pressure 0 Time 10 Sec

  7. Why do we need the ADS / PHX Series? • Longer Pipe Runs • More Efficient Use of Cylinder Fills • Difficult Pipe Networks • Greater Flexibility • Smaller Diameter Pipe

  8. ADS / PHX Nozzles • Two nozzle types • 180° Nozzle • 360° Nozzle • Nozzle sizes • 1/2” through 2”

  9. ADS / PHX Nozzle Locations • Proximity of nozzles to significant obstructions • At least 3 ft. to 4 ft. of clearance between nozzle and wall (or significant obstruction) • Proximity of multiple nozzles • At least 6 ft. of clearance between nozzles

  10. ADS / PHX Nozzle Coverage • Tested 46 ft. x 56 ft. Rectangle • Actual coverage area defined as rectangle with diagonal, d • 180° - d = 60.5 ft. 360° - d = 36.2 ft.

  11. ADS / PHX Nozzle Height • Maximum height for single nozzle is 16 ft. • Nozzle tiers are allowed • Minimum height • 1 ft. for UL Listed systems • 6” for Kidde Approved • Must reduce coverage area for height, 6” to 12” • 30 ft. x 30 ft. • 180° - d = 33.5 ft. • 360° - d = 21.2 ft.

  12. ADS / PHX Piping Network: Tees • Any orientation is allowed • Horizontal and vertical outlets, as well as inlets • 1 inlet, 2 outlets

  13. OUT OUT IN ADS / PHX Piping Network: Tees • Bull tee flow split • Minimum imbalance: 50/50 • Maximum imbalance: 85/15

  14. RUN OUTLET (65 to 85) IN SIDE OUTLET (15 to 35) ADS / PHX Piping Network: Tees • Side tee flow split • Minimum imbalance: 65/35 • Maximum imbalance • Horizontal feed: 85/15 • Vertical feed: 84/16

  15. ADS / PHX Piping Network: Pipe Sizes • Pipe sizes 1/2” through 6” are Listed/Approved • Largest nozzle size is 2”

  16. ADS / PHX Piping Network: Nozzles • Minimum nozzle pressure: 72 psi

  17. ADS / PHX Piping Network: Hydraulic Calculation • Enter: • Enclosure info • Agent quantity • Agent Source • Pipe network • Run main calculations • Verify system acceptance

  18. ECS / 9300/ 9300 vs. ADS / PHX:Design Comparison

  19. ECS / 9300 vs. ADS / PHX • Available Container Sizes: • ECS / 9300 • 10 lb. to 900 lb. • ADS / PHX • 225 lb. to 1010 lb.

  20. ECS / 9300 vs. ADS / PHX • Tees: • ECS / 9300 • Outlets horizontal • Bull Split: 50/50 to 70/30 • Side Split: 70/30 to 90/10 • ADS / PHX • Any orientation • Bull Split: 50/50 to 85/15 • Side Split: 65/35 to (85/15 or 84/16)

  21. ECS / 9300 vs. ADS / PHX • Nozzles: • ECS / 9300 • Coverage area: 40 ft. x 44 ft. • Max. height: 16 ft. • Min. height: 1 ft. (6”) • ADS / PHX • Coverage area: 46 ft. x 56 ft. • Max. height: 16 ft. • Min. height: 1 ft. (6”)

  22. ECS / 9300 vs. ADS / PHX • Nozzles: • ECS / 9300 • Min. clearance to wall/obstruction: 6 ft. • Min. clearance between nozzles: 10 ft. • ADS / PHX • Min. clearance to wall/obstruction: 3 to 4 ft. • Min. clearance between nozzles: 6 ft.