Towards Automatic Spatial Verification of Sensor Placement. Dezhi Hong * + Jorge Ortiz + Kamin Whitehouse * ^ David Culler + * University of Virginia + UC Berkeley ^ Microsoft Research. Evolution of Buildings. Evolution of Buildings. Hypothesis.
E N D
Towards Automatic Spatial Verification of Sensor Placement DezhiHong * + Jorge Ortiz + KaminWhitehouse* ^ David Culler + *University of Virginia +UC Berkeley ^ Microsoft Research
Hypothesis The physical boundary between rooms is detectable as a statistical boundary in the data.
Challenge Temp from different rooms Humidity/CO2 from same room
Approach Temp from different rooms Humidity/CO2 from same room
Approach Temp from different rooms Humidity/CO2 from same room
Data Set • 5 rooms, 3 sensors/room • Sensor type: temperature, humidity, CO2 • Over a one-month period
Inter/Intra Correlation CDF In the same room In different rooms! correlation coefficient correlation coefficient
Threshold Analysis Mid band correlation Raw data traces
Clustering 14/15 correct = 93.3% *A-B-C-D-E is used to denote the ground truth location of sensors
Clustering Mid-band Frequencies 12/15 correct = 80% Raw data traces 8/15 correct = 53.3%
Future Work • Extended from 5 rooms to ~100 rooms • It didn’t work • Open questions: • What new techniques can improve results? • What is the boundary that can be found?
Related Work • Strip, Bind, Search - IPSN’13 • Fontugne, et al • Smart Blueprints - Pervasive’12 • Lu, et al • SMART - Ubicomp’12 • Kapitanova, et al • Wireless Snooping Attack – UbiComp’08 • Srinivasan, et al
Summary • A statistical boundaryemerges in the early study on a small data set • The method may be empirically generalizable • Extensions and modifications to the solution are needed to verify the generalizability
Questions? Thank You
Well… • The early promising results from a small data set are not conclusive due to • Location of the room • Usage of the room • # of rooms
Questions@a large scale • “Noise” from the same type of sensors • Same type of sensors correlate highly Corrcoef across rooms Room ID Room ID Humidity Temperature *Both the X and Y axes are arranged by room ID in the same order