560 likes | 941 Views
UPS & Power Quality Devices. Ablerex UPS Product. UPS Line - interactive Step Wave UPS Troy Vesta Sine Wave UPS Janus & Janus XL Jupiter & Jupiter XL. Step Wave Line – Interactive UPS (For small office home office users). Advanced Battery Discharge Management AVR Boost and Buck
E N D
Ablerex UPS Product UPS Line - interactive Step Wave UPS Troy Vesta Sine Wave UPS Janus & Janus XL Jupiter & Jupiter XL
Step Wave Line – Interactive UPS (For small office home office users) • Advanced Battery Discharge Management • AVR Boost and Buck • Cold Start Function • Easy Swappable Battery • Smart Microprocessor Control Design • Smart RS232 Interface • Site Wiring Fault Indicator • Easy Overload Recovery Push • Circuit Breaker • USB Connectivity Ablerex TR600 TR800 VT1000 VT 1500
+ - FILT BATT AC AVR DC EMI Filter Battery Inverter Automatic Voltage Regulator 220V 220V 250V 250V CHRG Charger Utility Mode Switch Utility Power 220V Input Output WITH AVR Line Interactive Type( Off Line ) UPS
+ - FILT BATT AC AVR DC EMI Filter Battery Inverter Automatic Voltage Regulator + - Step Wave CHRG Charger Backup Mode Switch City Power 220V Input Output WITH AVR Line Interactive Type( Off Line ) UPS
Trouble Shooting(1) Ablerex 625L CPU OPA Battery Fuse Inverter MOSFET RS232 LED Switch RJ45 Load Sensing Charger & Working Power Input & Output Relay
12V 1 5Vdc LED Lit 2 Inverter Q17-20, Q16, Q21 D15, D16, D18, D19 3 Charger Q12, R30, R39, D20, F1, F2 P1 BAT- CN2 BAT+ CN8 RS-232 Interface SINK3 SINK4 BAT- BAT+ CN2 U7 Q17 Q19 Q20 F1 Q18 CN9 RJ11 Interface BATT U5 CN3 F2 SINK3 SINK4 CN8 + - P1 1 SW1 SW1 CN1 BZ1 T4 CN9 RL3 RL2 RL1 T3 R24 CN3 U4 Q12 R39 RL4 PCB Top view R8 CN1 To inlet/outlet. Front Panel switch Front Panel LED To the JST3.96 type of Main transformer. SINK3/SINK4. To the O type terminal of Main transformer.
Trouble Shooting(3) Ablerex 1000L/1500L CPU OPA Inverter MOSFET Load Sensing Com- USB RJ45 Battery Fuse Charger & Working Power Input & Output Relay
BAT- U5 U7 CN8 Q17 Q18 Q19 Q20 T4 H3 H2 CN10 SW2 P19 T3 Q12 K3 K2 K1 P20 R24 P18 F1 K4 P21 CN1 CN9 BZ1 U4 P1 F2 R8 BAT+ BATT + - 24V BAT- CN8 RS-232 Interface H3 H2 SW2 USB Interface BZZZER CN1 P18-P21 BAT+ Inlet/Outlet To the JST3.96-4PIN type of Main Transformer H3/H2 to the O type terminal of Main transformer .
Sine Wave Line Interactive UPS (For business user) • Line-interactive Topology • Pure Sine-wave Output on Backup Mode • Toroidal Transformer Technology (#) • Double Utility Voltage Correction (#) • Tower/Rack Installation (#) • Convertible LCD Panel (#) • Active both RS-232 & USB, with patented technique • Long Backup Battery Run Time (#) • Fast Charger inside, No External Charger • Hot-swappable Battery Design (#) • (#) For JPX series only Jupiter - Pro Jupiter XL Rack/Tower Convertible Series UPS
AC Input AC Output Input Relay AVRx2 Output Relay CPU Pure Sine-waveInverter Comm. Interface Charger Battery AC Power Flow DC Power Flow Control & Detect • Double Utility Voltage Regulation 2 x Boost + 2 x Buck Wide Input Range +/-32% Precision Output Control +8~-12% Voltage Configuration by DIP Switch on Rear Panel
Display & Control LEDUtility Normal, Backup Mode, Fault LCD with White Backlight Bypass, Boost, Buck, UPS, Battery Low/Replace/Fault, Site Wiring Fault, Overload, UPS Fault, Load Level, Battery Level KeypadTurn-on/Alarm Reset/Self-test, Turn-off, Reading Scroll
Rear Panel • JP Series • 6 x Backup Outlets • Output Breaker • Input Fuse • 1 x RS-232 • 1 x USB • LAN Protection • Output Configuration Dip Switch
Rear Panel • JPXL Series • 6 x Backup Outlets • Output Breaker • Input Breaker • 1 x RS-232 • 1 x USB • 1 x Communication Slot • LAN Protection • Output Configuration Dip Switch • External Battery Connector
AC Input FUSE CN19(AC OUT-N): Blue wire Inlet socket CN16(AC OUT-L): Brown wire CN14(AC IN-N): Blue wire CN15(AC IN-L): Brown wire JP Main Wire Connecting Diagram Output breaker CN6
CN18 (BAT+): Red wire CN17 (BAT-): Black wire JP Transformer and Batteries Connecting Diagram CN20 (XMR2): Blue wire INV -: Black wire INV +: Red wire CN13 (AUX+): Yellow wire CN12 (AUX-): Green wire CN11 (XMR1): Brown wire
JP 1K, 1.5K Charger Check Between CN17 (BAT-) and CN18 (BAT+): +27.4Vdc +/-0.5v wire Condition: must at AC Normal ,W/O Battery
JP 1K, 1.5K Working Power Check Negative of D50 +12Vdc +/- 1v Positive of D40 -12Vdc +/- 1v PIN #2 of U1 (heat sink) +5Vdc +/-0.5v
JP 1K, 1.5K Inverter Check Measure PIN #G,S PIN #D,S and PIN #G,D of MOSFET they don’t short
JP 2K, 3K Charger Check Between CN17 (BAT-) and CN18 (BAT+): +54.6Vdc +/-0.5v wire Condition: must at AC Normal ,W/O Battery
JP 2K, 3K Working Power Check Positive of D40 -12Vdc +/- 1v Negative of D50 +12Vdc +/- 1v PIN #2 of U1 (heat sink) +5Vdc +/-0.5v
JP 2K, 3K Inverter Check Measure PIN #G,S PIN #D,S and PIN #G,D of MOSFET they don’t short
JPX Transformer and Batteries ConnectingDiagram CN6 (AVR+): White wire CN8 (AVR-): Yellow wire CN12 (TR M+): Blown wire CN10 (AVR0): Green wire CN9 (TR M-): Blue wire CN3 (BAT-): Black wire (BAT+): Red wire INV +: Red wire INV -: Black wire
JPX Main Wire Connecting Diagram CN13 (AC OUT-L): Brown wire CN7 (AC OUT-N): Blue wire CN2 (AC IN-L): Brown wire CN1 (AC IN-N): Blue wire
JPX 1K, 1.5K Charger Check Between CN3 (BAT-) and Heat sink (BAT+): 1K/1.5K:+27.4Vdc +/-0.5v Condition: must at AC Normal ,W/O Battery
JPX 1K, 1.5K Working Power Check D board I board PIN #2 of U1 (heat sink) +5Vdc +/-0.5v Positive of D19 -12Vdc +/- 1v Negative of D25 +12Vdc +/- 1v
JPX 1K, 1.5K Inverter Check Measure PIN #G,S PIN #D,S and PIN #G,D of MOSFET they don’t short
JPX 2K, 3K Charger Check Between CN3 (BAT-) and Heat sink (BAT+): 2K/3K:+54.6Vdc +/-0.5v Condition: must at AC Normal ,W/O Battery
JPX 2K, 3K Working Power Check D board I board PIN #2 of U1 (heat sink) +5Vdc +/-0.5v Positive of D19 -12Vdc +/- 1v Negative of D25 +12Vdc +/- 1v
JPX 2K, 3K Inverter Check Measure PIN #G,S PIN #D,S and PIN #G,D of MOSFET they don’t short
Sine Wave Line Interactive UPS (For business user) • Line-interactive Sine Wave Topology • 0.9 Output Power Factor • Configurable Output Voltage Window by DIP Switch • Toroidal Transformer Technology • Built-in AVR Function • Tower/Rack Convertible • Rotatable User’s Friendly LCD Panel • Active RS-232 & USB & SNMP Slot Simultaneously • Remote Emergency Power Off • Fast Charger inside • Hot-swappable Battery Design • Extended Runtime Capability(for JCXL Series) Janus & Janus XL Series
AC Input AC Output Input Relay AVR Output Relay AC Power Flow CPU DC Power Flow Control & Detect Pure Sine-waveInverter Comm. Interface Charger Battery Boost/Buck Design Acceptable Input Range 83~159Vac/165~300Vac Input Voltage Window 110/120/127Vac or 220/230/240Vac +/-25% Voltage Configuration by DIP Switch on Rear Panel
Janus RT Series Rear Panel(120V) RJ45 Connectors Output Configuration DIP Switch USB Port RS232 Port Output Breaker Outlet 10/16A; 15A/20A Input Breaker Inlet EPO SNMP Slot 1000VA/1500VA 2200VA 3000VA
Janus RT Series Rear Panel(230V) RJ45 Connectors Output Configuration DIP Switch USB Port RS232 Port Output Breaker Outlet 10/16A; 15A/20A Input Breaker Inlet EPO SNMP Slot 750/1000/1500VA 2200/3000VA
JCXL Series Rear Panel(120V) RJ45 Connectors Output Configuration DIP Switch USB Port RS232 Port Output Breaker Outlet 10/16A; 15A/20A Cooling Vents Input Breaker Inlet External Battery Connector EPO SNMP Slot 1000/1500VA 2200VA 3000VA
JCXL Series Rear Panel(230V) RJ45 Connectors Output Configuration DIP Switch USB Port RS232 Port Output Breaker Outlet 10/16A; 15A/20A Cooling Vents Input Breaker Inlet External Battery Connector EPO SNMP Slot 1000VA/1500VA 2200VA/3000VA
Communication Interface • SNMP Card • Dry Relay Contact Card • 2nd RS232 Card • 2nd USB Card
Communication Software • Emily • UPSilon 2000
Hot Swappable Battery • Replaced from the Front Panel • Without Hazard Risk to Users
Toroidal Transformer • High Efficiency • Perfect Output Waveform • Quiet Operation • Slim Style
For JCXL Series Extended Backup For JCXL Series Extended Backup