1 / 58

Course Summary

Learn how to find and control active constraints, optimize variables, manipulate throughput, select stabilizing control variables, and design a supervisory layer in plantwide control systems. Explore case studies in distillation and understand the dos and don'ts of distillation column control.

Download Presentation

Course Summary

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Course Summary • Find active constraints + self-optimizing variables (CV1). (Economic optimal operation) • Locate throughput manipulator (TPM) • “Gas pedal” • Select stabilizing CV2 + tune regulatory loops • SIMC PID rules • Design supervisory layer (control CV1) • Multi-loop (PID) ++ • MPC Difficulties: • Optimization! May need to guess active constraints (CV1) • Handling of moving active constraints • Want to avoid reconfiguration of loops

  2. Summary: Sigurd’s plantwide control rules Rules for CV1-selection: 1. Control active constraints • Purity constraint on expensive product is always active (overpurification gives loss):   2. Unconstrained degrees of freedom (if any): Control “self-optimizing” variables (c). • The ideal variable is the gradient of J with respect to the inputs (Ju = dJ/du), which always should be zero, independent of disturbances d, but this variable is rarely available • Exception (if available!): Parallel systems (stream split, multiple feed streams/manifold) with given throughput (or given total gas flow, etc.) • Should have equal marginal costs Jiu = dJi/du, so Ju = J1u - J2u, etc. • Heat exchanger splits: equal Jächke temperatures, JT1 = (T1 – Th1)^2/(T1-T0) • In practice, one prefers to control single variables, c=Hy (where y are all available measurements and H is a selection matrix), which are easy to measure and control, and which have the following properties: • Optimal value for c is almost constant (independent of disturbances): Want small magnitude of dcopt(d)/dd. • Variable c is sensitive to changes in input: Want large magnitude of gain=dc/du (this is to reduce effect of measurement error and noise). • If the economic loss with single variables is too large, then one may use measurement combinations, c=Hy (where H is a “full” matrix). 3. Unconstrained degrees of freedom: NEVER try to control a variable that reaches max or min at the optimum (in particular, never control J) • Surprisingly, this is a very common mistake, even (especially?) with control experts Ruke for TPM location: Locate TPM at thenextconstraint to becomeactive as throughput is increased (bottleneck) Rules for inventory control: 1. Use Radiation rule (PC, LC, FC ++) 2. Avoid having all flows in a recycle system on inventory control (this is a restatement of Luyben’s rule of “fixing a flow inside a recycle system” to avoid snowballing) Rules for selecting stabilizing CVs (CV2): Control sensitive variablkes Rules for pairing: 1. General: “Pair close” (large gain and small effective time delay) 2. CV1: Sigurd’s pairing rule: “Pair MV that may (optimally) saturate with CV that may be given up” 3. CV2 (stabilizing loop): Avoid MV that may saturate

  3. PLANTWIDE CONTROLCASE STUDIES • Distillation: regulatory control • Distillation: Economics (CV1) • Single column • Two columns in series • Reactor/separator/recycle problem • Economics (CV1) • TPM location • Max. throughput (Bottleneck)

  4. Case study: Distillation control • S. Skogestad, ``The dos and don'ts of distillation columns control'', Chemical Engineering Research and Design (Trans IChemE, Part A), 85 (A1), 13-23 (2007).

  5. Typical “LV”-regulatory control Assume given feed 5 dynamic DOFs (L,V,D,B,VT) Overall objective (CV1): Control compositions (xD and xB) “Obvious” stabilizing loops (CV2): • Condenser level (M1) • Reboiler level (M2) • Pressure (p) + “non-obvious” CV2 4. Column temperature (T)

  6. L Ts TC TC V Issues distillation control • The “configuration” problem (level and pressure control) • Which are the two remaining degrees of freedom? • e.g. LV-, DV-, DB- and L/D V/B-configurations • The temperature control problem • Which temperature (if any) should be controlled? • Composition control problem • Control two, one or no compositions? • Always control valuable product at spec

  7. Configurations Control “configurations” (pairing u2-y2 for level control) • “XY-configuration” X: remaining input in top after controlling top level (MD): X= L (reflux), D, L/D,… Y: remaining input in bottom after controlling MB: Y = V (boilup, energy input), B, V/B, ...

  8. Configurations LC Top of Column cooling VT LS “Standard” : LY-configuration (“energy balance”) L+D D L Set manually or from upper-layer controller (temperature or composition) Set manually or from upper-layer controller VT DS LC “Reversed”: DY-configuration (“material balance”) D L

  9. Configurations Top of Column VT LC D L D Ls Set manually or from upper-layer controller (L/D)s x Similar in bottom... XV, XB, X V/B

  10. Configurations How do the configurations differ? • Has been a lot of discussion in the literature (Shinskey, Buckley, Skogestad, Luyben, etc.). • Probably over-emphasized, but let us look at it • Level control by itself (emphasized by Buckley et al., 1985) • Interaction of level control with composition control • Related to “local consistency” (Do not want inventory control to depend on composition loops being closed) • “Self-regulation” in terms of disturbance rejection (emphasized by Skogestad and Morari, 1987) • Remaining two-point composition control problem (steady-state RGA - emphasized by Shinskey, 1984)

  11. LV-configuration (most common) “LV-configuration”: • D and B for levels (“local consistent”) • L and V remain as degrees of freedom after level loops are closed Other possibilities: DB, L/D V/B, etc….

  12. BUT: To avoid strong sensitivity to disturbances: Temperature profile must also be “stabilized” D feedback using e.g. D,L,V or B LIGHT TC F HEAVY B Even with the level and pressure loops closed the column is practically unstable - either close to integrating or even truly unstable ( e.g. with mass reflux: Jacobsen and Skogestad, 1991) • To stabilize the column we must use feedback (feedforward will give drift) • Simplest: “Profile feedback” using sensitive temperature

  13. Stabilizing the column profile • Should close one “fast” loop (usually temperature) in order to “stabilize” the column profile • Makes column behave more linearly • Strongly reduces disturbance sensitivity • Keeps disturbances within column • Reduces the need for level control • Makes it possible to have good dual composition control • P-control usually OK (no integral action) • Similar to control of liquid level

  14. Regulatory layer Stabilizing the column profile (T) . loop LV LV LV T T T s s s TC TC TC (a) Common: Control T using V (b) If V may saturate: Use L • T at which end? Prefer “important” end with tightest purity spec, • T at which stage? Choose “sensitive” stage (sensitive to MV change) • Pair T with which input (MV)? Generally “pair close” • But avoid input that may saturate • Dynamics: V has immediate effect, whereas L has delay • Prefer “same end” (L for Ttop, V for Tbtm) to reduce interactions • Note: may not be possible to satisfy all these rules TC TC TS

  15. TC Bonus 1 of temp. control: Indirect level control Disturbance in V, qF: Detected by TC and counteracted by L -> Smaller changes in D required to keep Md constant!

  16. Bonus 2 of temp. control: Less interactive Setpoint T: New “handle” instead of L Ts TC

  17. Less interactive: RGA with temperature loop closed

  18. Less interactive: Closed-loop response with decentralized PID-composition control Interactions much smaller with “stabilizing” temperature loop closed … and also disturbance sensitivity is expected smaller %

  19. Integral action in inner temperature loop has little effect %

  20. Note: No need to close two inner temperature loops % Would be even better with V/F

  21. Would be even better with V/F: Ts TC F (V/F)s x V

  22. x (L/F)s Ts TC A “winner”: L/F-T-conguration Only caution: V should not saturate

  23. TC Temperature control: Which stage?

  24. Binary distillation: Steady-state gain G0 = ΔT/ΔL for small change in L T /  L BTM TOP

  25. Summary: Which temperature to control? • Rule 1. Avoid temperatures close to column ends (especially at end where impurity is small) • Rule 2. Control temperature at important end (expensive product) • Rule 3. To achieve indirect composition control: Control temperature where the steady-state sensitivity is large (“maximum gain rule”). • Rule 4. For dynamic reasons, control temperature where the temperature change is large (avoid “flat” temperature profile). (Binary column: same as Rule 3) • Rule 5. Use an input (flow) in the same end as the temperature sensor. • Rule 6. Avoid using an input (flow) that may saturate.

  26. Ls Ts TC Conclusion stabilizing control:Remaining supervisory control problem Would be even better with L/F With V for T-control + may adjust setpoints for p, M1 and M2 (MPC)

  27. Summary step 5: Rules for selecting y2 (and u2) Selection of y2 • Control of y2 “stabilizes” the plant • The (scaled) gain for y2 should be large • Measurement of y2 should be simple and reliable • For example, temperature or pressure • y2 should have good controllability • small effective delay • favorable dynamics for control • y2 should be located “close” to a manipulated input (u2) Selection of u2 (to be paired with y2): • Avoid using inputs u2 that may saturate (at steady state) • When u2 saturates we loose control of the associated y2. • “Pair close”! • The effective delay from u2 to y2 should be small

  28. CASE STUDIES

  29. Example (TPM location): Evaporator(with liquid feed, liquid heat medium, vapor product) PROBLEM: • Objective: “Keep p=ps (or T=Ts) if possible, but main priority is to evaporate a given feed” • CVs in order of priority: • CV1 = level, CV2 = throughput, CV3 = p • MV1 = feed pump, MV2 = heat fluid valve, MV3= vapor product valve • Constraints on MVs (in order of becoming active as throughput is increased): • Max heat (MV2), Fully open product valve (MV3), Max pump speed (MV1) • Where locate TPM? Pairings? Present structure has feed pump as TPM: May risk “overfeeding”

  30. Pairing based on Sigurd’s general pairing rule**: • CV1=level with MV1 (top-priority CV is paired with MV that is least likely to saturate) • CV2=throughput with MV3 (so TPM =gas product valve) • CV3=p with MV2 (MV2 may saturate and p may be given up) • Note: Fully open gas product valve (MV3) is also the bottleneck • Rules agree because bottleneck is last constraints to become active as we increase throughput * General: Do not need a FC on the TPM **Sigurd’s general pairing rule: “Pair MV that may (optimally) saturate with CV that may be given up”

  31. CASE STUDY: Recycle plant(Luyben, Yu, etc.)Part 1 -3 Recycle of unreacted A (+ some B) 5 Feed of A 4 1 2 Assume constant reactor temperature. Given feedrate F0 and column pressure: 3 Dynamic DOFs: Nm = 5 Column levels: N0y = 2 Steady-state DOFs: N0 = 5 - 2 = 3 Product (98.5% B)

  32. Part 1: Economics (Given feed) Recycle plant: Optimal operation mT 1 remaining unconstrained degree of freedom, CV=?

  33. J=V as a function of reflux L Optimum = Nominal point With fixed active constraints: Mr = 2800 kmol (max), xB= 1.5% A (max)

  34. Control of recycle plant:Conventional structure (“Two-point”: CV=xD) LC TPM LC xD XC XC xB LC Control active constraints (Mr=max and xB=0.015) + xD

  35. Luyben law no. 1 (to avoid snowballing): “Fix a stream in the recycle loop” (CV=F or D)

  36. Luyben rule: CV=D (constant) LC LC XC LC

  37. “Brute force” loss evaluation:Disturbance in F0 Luyben rule: Conventional Loss with nominally optimal setpoints for Mr, xB and c

  38. Loss evaluation: Implementation error Luyben rule: Loss with nominally optimal setpoints for Mr, xB and c

  39. Conclusion: Control of recycle plant Active constraint Mr = Mrmax Self-optimizing L/F constant: Easier than “two-point” control Assumption: Minimize energy (V) Active constraint xB = xBmin

  40. Modified Luyben’s law to avoid snowballing • Luyben law no. 1 (“Plantwide process control”, 1998, pp. 57): “A stream somewhere in all recycle loops must be flow controlled” • Luybenruleis OK dynamically (short time scale), • BUT economically (steady-state): Recycle should increase with throughput • Modified Luyben’s law 1 (by Sigurd): “It must be a TPM or flow controlled on an intermediate time scale”

  41. Part 2: TPM location Example Reactor-recycle process:Given feedrate (production rate set at inlet) TPM

  42. Part 2: TPM location PC D L F0 F TC V B Note: Temperature and pressure controllers shown; Otherwise as before

  43. TPM Alt.1 Alt.2 TPM TPM Alt.3 More? Alt. 5? Alt.6? Alt. 7? Alt.4 TPM=xAr TPM

  44. T fixed in reactor Alt.1 Alt.2 Follows Luyben law 1: TPM inside recycle Alt.4 Alt.3 More? Alt. 5? Alt.6? Alt. 7? Not really comparable since T is not fixed Unconventional TPM

  45. PC Alt. 5 What about TPM=D (Luyben rule)? • Control xB, xD, Md • Not so simple with liquid feed….. TPM LC LC ? XC TC LC XC

  46. PC Alt. 5 What about TPM=D (Luyben rule)? Another alternative: • Top level control by boilup • Get extra DOF in top • OK! TPM LC LC XC TC LC XC

  47. PC NOTE: There are actually two recycles • One through the reactor (D or F) • One through the column (L) • One flow inside both recycle loops: V • Alt.6: TPM=V if we want to break both recycle loops! TC

  48. PC Alt. 6 TPM = V LC LC L XC TC F TPM XC LC Simulations (to be done) confirm This is the best! L and F for composition control: OK!

  49. PC Alt. 7 What about keeping V constant?(in addition to having another TPM) LC TPM L LC TC F0 F V XC LC With feedrate F0 fixed (TPM) L for compostioncontrol in bottom (xB) Topcompositionfloating NO! Never control cost J=V

  50. Reactor-recycle process: Want to maximize feedrate: reach bottleneck in column Bottleneck: max. vapor rate in column TPM