Low Hanging Fruit Low Cost Energy Efficiency Opportunities in Cleanrooms. November 2004. Free Cooling. Psychrometric Chart for San Jose. 3,200 Hours Minimum. Free Cooling Configuration #2 - Series PCW Only. An Innovative Layout Possibility. Dual Temperature Chilled Water Plant.
E N D
Low Hanging FruitLow Cost Energy Efficiency Opportunities in Cleanrooms November 2004
Psychrometric Chart for San Jose 3,200 Hours Minimum
An Innovative Layout Possibility Dual Temperature Chilled Water Plant
Use Variable Speed Drives • Good for fans, even better for pumps, which are typically controlled and balanced by throttling
Close 3-way Valves • B8 has a highly variable load due to air washer capacity, yet a constant flow
Exhaust Optimization • Tool exhaust can be optimized via tracer gas or other accepted test methods • In most cases tool exhaust can be reduced 10 – 50% • Fume containment testing required for optimization also verifies worker safety • Case Study Savings Opportunity:
When replacing broken or worn out equipment Select the most efficient option • Efficiency often has little relationship to cost of equipment • E.G. ----- • Pumps • Electric Motors • Fans • etc.
Variable Speed Drive Compressors and waste heat regen dryers • VSD Compressors address the cycling problem
Commissioning / Retrocommissioning • Retrocommission - on a regular basis commission key components of system • E.G. - Develop standard tests for key control loops
Effect - Supply Air Temperature is Deficient Design Supply Air Temp is 55 deg F with no SAT reset
Cause Chilled Water Temperatures