An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Heat Pump Research Project Sponsored by the Heat Pump Working Group June 7, 2005

  2. Project Goals • Assess energy use and savings from heat pumps installed under C&RD/ConAug and EWEB. • Assess base case installation practices. • Assess heat pump performance under laboratory conditions to identify optimal settings. • Assess the general approach of installers to control, sizing and performance issues, and of manufacturers to new technologies, etc.

  3. Billing Results

  4. EWEB Billing Analysis Results

  5. C&RD / ConAug Billing Analysis Results Revised Results Previous Results

  6. Billing Analysis Results by System Type

  7. C&RD SF Cases NAC Saved by System C&RD MH Cases NAC Saved by System Type with 90% C.L., n= 549 Type with 90% C.L., n= 124 9,000 10,000 9,000 8,000 8,000 7,000 7,000 6,000 6,000 kWh/year 5,000 kWh/year 5,000 4,000 4,000 3,000 3,000 2,000 2,000 1,000 1,000 0 0 Zonal Zonal Heat Pump FAF w/CAC Heat Pump FAF w/CAC FAF w/oCAC All C&RD SF All SysTypes All SysTypes All C&RD MF FAF w/oCAC Billing Analysis Results by Building Type

  8. MH NAC Saved with 90% C.L. by Vintage Bin, n= 114 7,000 6,000 5,000 4,000 kWh/year 3,000 2,000 1,000 0 1 2 3 All C&RD Billing Analysis Results by Vintage Legend: 1 Pre 1981 2 1981 – 1994 3 Post 94

  9. Realization Rates by Program Year Base

  10. Realization Rates for C&RD Calculator, Initial

  11. Realization Rates, Revised

  12. kWh Savings estimates

  13. Laboratory Results

  14. HSPF: Fixed Orifice & TXV

  15. Summary of Lab Results • Impacts of refrigerant charge minimal except at very reduced levels (70% of specification) • Impacts of air flow also limited to cases with very low air handler flow (less than 300 CFM/ton). • Low air flow appears to occur in about 25% of “base case” installation practice • TXV improves overall performance but has minimal impacts on the effects of low charge and low air flow • Cd higher than modeling assumptions for fixed orifice, lower than assumption for TXV • Defrost degradation factors largely stable at values near the modeled and manufacturer’s assumptions.

  16. Field Data Summary

  17. Field Study Overview • 160 field sites in 4 regions (Central Oregon, Kitsap Peninsula, Clark Co., Yakima/Walla Walla) started September 2004 • “Base case” sites, chosen at random to represent non-PTCS installations • Combine field findings with billing data to recalibrate performance assumptions used in RTF calculations • On-site review consists of two visits • Duct/house review (complete) • Heat pump review by service tech. (110 sites now in, additional 15 sites expected)

  18. Site Selection • Sites selected via random telephone dial to have air-source heat pump and be within appropriate utility territory • Sites might have basements/interior ducts • Clark County chosen vs. Portland because of paucity of HPs in PDX Pacific Power svc territory • Clark actually has HP inspection program so non-typical vs other areas

  19. Key Audit Outputs(house/duct) • House heat loss rate (UA) • Integral part of modeling house performance vs bills • Includes infiltration component (blower door test) • System airflow (CFM) • System capacity & efficiency • Duct system insulation and leakage • System operating pressures also measured • Duct leakage fraction (%) • Effect on overall delivery efficiency/energy use • Homeowner interaction with system (via survey)

  20. Key Audit Outputs (heat pump review) • HP control strategy • Indoor thermostat type, setting and staging • Outdoor thermostat presence, setting and operation • Compressor low ambient cut out • Refrigerant charge level

  21. Building Characteristics – Heat Loss Rate

  22. Blower Door Results • Median ACH50 is 7.6 for 149 clean cases; mean is 8.3 • This converts to median ACHnat of 0.38 • Highest ACH50 19.0 • Lowest ACH50 1.6

  23. Blower Door Results by Vintage Bin

  24. Duct Leakage Fraction (all sites)

  25. Duct Leakage by Vintage Bin Supply Side Return Side

  26. Supply vs. Return Leakage

  27. System Fan Flow • Median flow is 340 CFM/ton (n=126) • Lower quartile is <=292 CFM/ton • ECM cases (n=21*), median flow is 338 CFM/ton *final # will be larger

  28. Airflow Distribution

  29. System airflow by size of outdoor unit Tons

  30. Refrigerant Charge Evaluation • Review predominantly done in swing seasons • Heating season evaluation combined tech’s review of operating pressures and sensible split in context of ambient temp., system airflow, coil match • About 1/3 of systems evaluated in cooling only mode or in addition to heating mode • Superheat/subcooling evaluation

  31. Charge Results • 60% of cases evaluated as having correct charge • 28% of cases evaluated as being overcharged • 10% of cases evaluated as being undercharged • 2 had serious leaks (no refrigerant)

  32. Refrigerant Charge Digest • Over/undercharge amounts likely under-reported vs weigh-in approach • However, cases of severe undercharge were very limited • ½ of overcharged cases had an accumulator • 2/3 of remaining overcharged cases were units with Trane compressors or scroll compressors

  33. Heat Pump Efficiency HSPF by Region HSPF by Equipment Size

  34. HVAC Usage(from median low bill analysis of 124 bills) Heating - Annual kWh Cooling - Annual kWh

  35. Normalized Heating Load by Vintage and Region Heating - Annual kWh/sf Total Usage - Annual kWh/sf

  36. Normalized Heating Usage Impact of wood – Annual kWh/sf Percentage of Sample Using Wood

  37. Modeled Duct Efficiency(efficiency of 1 is perfect ducts) By Region By Vintage

  38. Duct Insulation Supply vs. Return UA R-Value of Supply Ducts

  39. TXV Summary (Outdoor Unit)

  40. TXV Summary (Indoor Unit)

  41. Thermostat/Homeowner Interaction • ~80% of systems have programmable stats… • ~1/3 of occupants say they understand their thermostat and/or like how it keeps their house comfortable • ~1/3 say they tolerate their thermostat (but wish they understood it better) • ~1/3 have thrown up their hands and use the HOLD feature

  42. Controls: Indoor Thermostat • 78% programmable • Median heating setpoint: 70 F • Median setback: 65 F • 55% of systems with setback > 5 F • Estimated 75% of programmable stats have adaptive recovery

  43. Controls: Outdoor Thermostat • About 35% of sites visited had an operating ODT (75% of Clark sites have ODT) • Average setting 40° F • About 2/3 of sites without ODTs had the extra wires needed to install one without fishing new wire • Only 15% of systems had elements on in Stage 1 heating • Median on-time 5 minutes

  44. Market Actor Interviews

  45. HVAC Installer Interviews(detailed results) • 32 shops throughout region in urban, suburban, rural areas (29 full interviews) • Shops range from 2 trucks to 30, median of 6 • Median 50% new construction • Participants install all major (and some secondary) brands of equipment • Almost all participants report use of non-intuitive heat pump and duct sizing tools (Manual J, Manual D, etc.) • Wide range of experience with utility, state, national incentive/marketing campaigns and installation procedures

  46. Technician Certification

  47. Installer System Sizing Criteria

  48. Characteristics of Efficient Line

  49. Installation Characteristics - TXVs

  50. Availability/cost of Outdoor Unit TXV