150 likes | 456 Views
Instrument Cave – Fire Protection and Explosion Safety. Fredrik Jörud Fire Protection Engineer European Spallation Source ERIC 2019-02-12. Background. Fire and Explosion Safety Programme. Requirement is not only about evacuation. Each instrument is unique.
E N D
Instrument Cave – Fire Protection and Explosion Safety Fredrik Jörud FireProtectionEngineer European Spallation Source ERIC 2019-02-12
Background Fire and Explosion Safety Programme
Each instrument is unique – it is foreseen that fire and explosion protection have to be adjusted to the actual circumstances
Automatic water suppression inside the instrument cave Metallic heads (or Cage protection)
Sprinkler water supply is prepared for in the instrument halls
First responder unit needs to quickly identify position of fire or water leakage Water flow Flow alarm valve First Responder Unit
Automatic water suppression in office cubicles placed inside the instrument hall
Paraffin fill holes on inside of instrument cave ! Automatic extinguishing system inside cave
Polyethylene shielding – fire rated cladding to protect ignition from external source
Explosion safety Keep flammables outside the cave ? HYDROGEN
Explosion safety Example on hydrogen bottle Exhaust pipe 200 bar = 16 mradius • Zone 1: 0.5 maround connection valve • Zone 2: 1.5 m outside zone 1. If the space has a floor area of less than 8 m2, zone 2 is extended to include the entire compartment.