An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. EN-60849 EMERGENCY PURPOSES Voice Alarm SYSTEMS. NORM DESCRIPTION

  2. APLICATION • Object • PA systems used to alarm in emergency situations. • Main performances. • A sound system for emergency purposes shall permit the broadcasting of intelligible information of measures to be taken for the protection of lives within one or more specified areas.“ EN-60849

  3. ~ ~ Alarm generation Ampli-fiers Lines Loudspeaker DEFINITIONS • Terms • Alarm • a signal, or condition, warning of an emergency” • e.g.: evacuation advice • Warning • important notice concerning any change of status which demands attention or activity “ • e.g. hint that an emergency may happen • Critical Signal Path • all components and interconnections between every emergency broadcast initiation point and the input terminals on, or within, each loudspeaker enclosure.” FDS EN-60849

  4. Requirements on equipments Concerning the manufacturer EN-60849

  5. FUNCTIONS AVAILABILITY • Continuous Availability [4.1b] • The PA system shall be available all times • Availability within 10 seconds after supplying power to the system [4.1c] • primary or secondary power • Maximum 3 Seconds from initiation until first emergency broadcast [4.1d] • including reaction time of the detection system EN-60849

  6. CD FDS PA central ALARMING PRIORITY • Highest Priority for Alarming [4.1a] • disabling all other (general) PA functions FDS: Fire Detection System EN-60849

  7. EMERGENCY PRIORITIES [4.3] • Manual Alarming/Warning/Restoration • >Automatic Alarming (evacuation) • >Automatic Warning • >no emergency: operational messages(e.g. for system check) EN-60849

  8. MANUAL INTERVENTION • If the voice alarm system is capable of operation in fully automatic mode, a manual intervention shall always be possible: [4.3.2] • starting and stopping of prerecorded alarm messages [4.3.2a] • selection of appropriate prerecorded alarm messages [4.3.2b] • when using specific emergency messages, indication of which message and their relation to zones must be displayed [5.2.d] • paging by using the emergency microphone (if any) [4.3.2d] • selection of zones for prerecorded message or paging [4.3.2c] EN-60849

  9. Automatic Status Indication • “A clear indication shall automatically be given at the designated control locations of:“ [5.2] • (the designated control location can be the fireman‘s microphone) • “system availability“ [5.2 a] • “power supply availability“ [5.2 b] • “any fault condition“ [5.2 c] • systems with several zones: current message broadcast into which zones:Alert, Evacuation, paging EN-60849

  10. Failure Indication (1) • Indication of Failures [5.3] • Failures must be indicated automatically at an designated place (e.g. main system) • The failure shall be indicated within 100 seconds after occurance. • The failure shall be indicated acoustically and visually. • A receipt button and a reset button must be available. EN-60849

  11. Failure Indication (2) • Indication [5.3] • Visual and acoustic indication • tone of 0.5 seconds duration, min. once within 5 seconds • permanent or flashing visual indicator • Manual reception by personal • tone disappears • visual indicator remains / changes to permanent on • Reset of failure indication after failure recovery • visual indicator extinguishes automatically - or - • visual indicator extinguishes after manual reset • visual indicator shall extinguish after failure recovery ! • Acoustic tone must start again when other failure detected EN-60849

  12. Surveillance (1) • An automatic Surveillance must indicate each detected failure • The surveillance system tests • Components of the “critical signal path “ (sources, amplifiers, cables etc.) • the power supply • primary supply [5.3a] • secondary supply [5.3b] • battery charger [5.3c] • failure of protection circuits which may prevent the an emergency broadcast • e.g. fuse, circuit breaker, isolator [5.3d] • control circuits (processor etc.) EN-60849

  13. Surveillance (2) • Failure of elements of the critical signal path • failure of microphone [5.3e] • (voice coil, pre-amplifier, wiring) • failure of the critical signal path through amplifiers [5.3f] • missing of amplifiers or critical modules [5.3g] • failure of standby amplifier [5.3h] • failure of tone generator or message memory [5.3i] • failure of speaker circuits [5.3j] • (short circuit, break) • failure of connection between decentralised systems [5.3 o] • failure of connection between PA system and emergency detection system • usually this surveillance is done by the emergency detection system [5.5] EN-60849

  14. Monitoring of the Microphone • Microphone monitoring methods • Electrical monitoring : • Disadvantage: conversion from sound to voltage can not be monitored, e.g. when the diaphragm is damaged • Acoustic monitoring • a sound generator sends an acoustic signal to the capsule • the acoustic and electric function of the capsule is monitored  very safe method ! EN-60849

  15. MonitoringSpeaker Circuits (1) • Methods of Speaker Circuit Surveillance • (remind that the critical signal path ends at the speaker’s connector) • 1. Monitoring with DC current advantage:star wiring possible. disadvantage:speakers must be modified or special speakers must be used; not suitable for existing speaker circuits EN-60849

  16. Signal + Test signal (low frequency) Monitoring Speaker Circuits (2) • 2. Impedance Monitoring(used often) Impe-dance measuring Advantage:connection of different 100 volts speakers possible; star wiring possible; expansion of old systems possible Disadvantage:Restriction when many speakers are connected on a line: a line break causing a few speakers to be cut off can not be detected because practically only high impedance deviation can be detected correctly (the speakers impedance can become 30% higher when the voice coil is hot !) EN-60849

  17. Signal + Test signal (high frequency) Monitoring Speaker Circuits (3) • 3. Loop Back Pilot tone detector Advantage:connection of different 100 volts speakers possible; very safe method Disadvantage:star wiring not possible or difficult (line must be installed from speaker to speaker); expansion of old systems complicated when star wiring was used, line back necessary EN-60849

  18. end of line unitf1f2 Signal + Test signal f1(high frequency) Pilot tone detector f1, f2 Monitoring Speaker Circuits (4) • 4. Back Signal on Same Line Advantage: connection of different 100 volts speakers possible, no line back necessary;very safe method Disadvantage: star wiring not possible (line must be installed from speaker to speaker); expansion of old systems complicated when star wiring was used; practical problem: installation site of the end of line unit often not in documents (can not be found) EN-60849

  19. Evacuation Message Memory • Safety Against External Influence • Pre-recorded messages and eventually attention-drawing signals • must be stored in a non-volatile memory (solid state memory, no mechanical devices) [4.2i] • availability must be monitored continuously • external sources shall not be able to corrupt or derange the store or its contents EN-60849

  20. Requirements On The Installation Concerning the Installer EN-60849

  21. Interface With Emergency Detection System [5.5] • Continuous Monitoring • The communication link between the emergency detection system and the sound system is normally monitored by the emergency detection system • Notifications to the Emergency Detection System • The sound system must transfer minimum one fault information (any failure) to the emergency detection system EN-60849

  22. Security Functions • Redundant Facilities • Keeping the Power [4.1m] • an emergency power supply must be installed always • Keeping the Broadcast [4.1g] • “Failure of a single amplifier or loudspeaker circuit shall not result in total loss of coverage in the loudspeaker area served.” • architecture of the speaker circuit • configuration power amplifiers • Exception: regional directives for small buildings EN-60849

  23. Emergency Power Supply • Battery’s Capacity [5.6] • Loss of AC mains at evacuation: • double evacuation time • minimum 30 minutes for emergency mode • Loss of AC mains without evacuation: • minimum 24 hours (normal operation) • When a building is not used for a longer period (e.g. weekend), then the system must be capable to operate the emergency mode for minimum 30 minutes after re-occupation of the building(e.g. 72 hours standby plus 30 minutes emergency mode). • Refer to British Standard BS5839: part 8, for battery capacity calculation. EN-60849

  24. A B standby switch line cut switch standby amplifier Keeping of Broadcast (1) • Electric Solution: A/B-Wiring • Two-Line System • In case of failure of one line, the other line still serves the remaining speakers A/B-wiring with 2amplifiers A/B-wiring with standby amplifier EN-60849

  25. A B A B Keeping of Broadcast (2) Example: wide area • Acoustic Solution: • Connection of speakers by turns on the lines A and B in each direction • In case of a line’s failure, the speaker area keeps served adequate (small gaps of coverage only) Example: corridor EN-60849

  26. Divided Emergency Speaker Zones • Emergency Speaker Zones [4.1k] • Division into areas depending on evacuation method • responsible: authorities • Criterias for Division [4.1l] • 1) neighbour zones shall not disturb • 2) maximum one loudspeaker zone per emergency detection zone • responsible: authorities, planer . EN-60849

  27. Sound pressure level 120 dBA Max. Alarm signal level 6 - 20 dBA Noise level 75 dBA Quiet level 65 dBA Min. level Sound Pressure Level -1- • Attention-Drawing Signals[Annex C] • minimum: 65 dBA, in rest areas: 75 dBA • 6 - 20 dBA above background noise • maximum: 120 dBA • the sound pressure levels of all relevant areas must be confirmed and being documented [7.2 a] z.B. 100 dBA z.B. 90 dBA EN-60849

  28. Sound Pressure Level -2- Messages • The standard does not write specific value for the sound pressure level of the reports. Instead it prescribes a specific value of the intelligibility . EN-60849

  29. Intelligibility • Intelligibility of Messages • The Intelligibility of messages must be equal or higher than 0.7 CIS (common intelligibility scale; STI: 0,5) [5.1] • This value must be obtained in each area [5.1] • In a difficult acoustic environment, it is preferable to carry out an acoustical simulation • Measuring and Documentation of Intelligibility • Confirmation of intelligibility must be documented [7.2 a] • Application of acknowledged with restrictions [Anhang A] • Correlation curves to CIS in [Annex B] • A specialised company may measure the intelligibility EN-60849

  30. Alarm Signals -1- • Attention-Drawing Signal • minimum one suitable attention-drawing signal before message (refer to EN 457) [4.1 e] • Distinguishable attention-drawing signals at different emergency cases [4.1 h] • Attention-Drawing Signals and Messages [4.1 h] • attention-drawing signal before message, 4-10 seconds • duration of attention-drawing signal and messages until change or end of evacuation • max. 30 seconds between different messages • pauses > 10 seconds: attention-drawing signal EN-60849

  31. Alarm Signals -2- • Pre-recorded messages • All messages must be clear, short and pre-planned. • Lenguage • Buyer should specify the used language(s). EN-60849

  32. Documentation -1- • Operation Manual [7.1] • must be quickly available(preferable at each operation place) • Contents: • practical operation of the system • action to be taken in case of system failure • Performance • graphically if possible • in preferred language • bound document (copy) EN-60849

  33. Documentation -2- • System Documentation [7.2a] • To be kept by User or Maintenance Company • Contents: • locations of each part of the devices • measuring results of the system • Impedance of each speaker circuit • set values (when adjustable, e.g. volume) • sound pressure level(s) • intelligibility EN-60849

  34. Documentation -3- • Maintenance Instructions [7.3.2] • To be kept by User or MaintenanceCompany • Contents: • Maintenance procedures (order of works) • Maintenance intervals • Parts for maintenance, spare parts, special tools • Suppliers • eventually test certificates EN-60849

  35. Requirements on the Operation Concerns the user EN-60849

  36. Documentation -4- • Log Book [7.2b] • Responsible person must take care on it • Contents: • details of all emergency cases • details of tests and routine checks • details of occurred failures and the repair EN-60849

  37. Security of Operation • Maintenance [7.3.1] • should be done twice a year (maintenance and test) • to be carried out by competent person • Responsible person [4.2] • nominated by owner • is responsible for maintenance • must be trained • manages the log book EN-60849