1 / 33

UPS Battery Battery Sizing

UPS Battery Battery Sizing. Paolo Frisoni Application Engineer, DPG Liebert Hiross UPS. Battery Sizing. Type of batteries used in DPG UPS Batteries for extended runtime How to assess backup times and size extra batteries Special requirements (NiCd, 10 Years) Other requirements.

blenda
Download Presentation

UPS Battery Battery Sizing

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. UPS BatteryBattery Sizing Paolo Frisoni Application Engineer, DPG Liebert Hiross UPS

  2. Battery Sizing • Type of batteries used in DPG UPS • Batteries for extended runtime • How to assess backup times and size extra batteries • Special requirements (NiCd, 10 Years) • Other requirements

  3. Battery Sizing Battery Used for micro UPS / On-Line For GXT2-3000RT230 a 15 Amp. 72V Battery Charger (same look) is available its PN is: GXT2-1000RBC.072

  4. Battery Sizing Battery Used for micro UPS - Off Line

  5. Battery Sizing Battery Used for small UPS

  6. Battery Sizing • Battery Used for Micro & Small UPS • The most part of our products use : • Valve regulated lead-acid battery 5 Years of life • Blocks of 12Volt (6 cell on each) with 7-7.2Ah • The dimension are standard for different supplier but the terminals must be Fast-on 6,3 mm • Hinet and its Batt.Cab. can be supplied without internal batteries. The internal Batt.Charger provide 1 - 3.5 -7Amp • A complete Kit of Battery cable can be provided for the internal connections (HNBATTCABLE) • The GXT 5&10kVA can be supplied without internal Batteries the PN is GXT5000T-230NB & GXT10000T-230NB with improved Battery Charger (4,5Amp)

  7. Battery Sizing • Battery Used for 10 Years Applications • For special requirements like 10 Years Battery • for 12V 7Ah Blocks • The NP7-12 (Yuasa) can be replaced with the RE7-12 the increasing cost is 70% • for 12V 38Ah Blocks • The NP38-12 (Yuasa) can be replaced with NPL38-12 cost increase 15% • for 12V 65Ah Block • The NP65-12 (Yuasa) can be replaced with NPL65-12 cost increase 15%

  8. Battery Sizing Key Factors in Battery Life There are 4 factor that strongly affect the Battery Life • Ambient Temperature • Number of Charge/Discharge Cycles • Deep discharge • Floating Charge Voltage @ Temperature

  9. Battery Sizing • AMBIENT TEMPERATURE Effect of the Temperature on Lifetime

  10. Battery Sizing • Number of Charge/Discharge Cycles • Depend on number of Deep Discharge Cycles (%) • We will reach the DDL only when the Main fail last more than the UPS autonomy

  11. Battery Sizing • Deep Discharge • The lowest recommended Voltage Under Load were the Battery can works or Cut off Voltage • Below this limit Battery will be damaged • UPS Topology also lead to cycle on to battery operation frequently • OFF-LINE Worse • LINE INTERACTIVE Less Worse • ON-LINE Best Behaviour

  12. Battery Sizing • Deep Discharge • Some UPS the Cut Off voltage can be adjusted, like Hinet (The default Value is 1.66 V/cell) • Some others UPS this Limit change automatically with the load (all GXT series)

  13. Battery Sizing • Float Charge Voltage versus Temperature • Float Charge Voltage need to be maintained between 2.275V/cell +/- 0.005 (at 20°C) • For Hinet is adjustable (factory set to 2.25 V) • For GXT is Fixed to 2.3V • Optimisation will be reached when this value is adjusted with temperature : • at 0°C V/cell = 2,35V • at 40°C V/cell = 2,15V • Hinet --> next step • Improvement

  14. Design Criteria Run Time Calculator • This Tool perform the calculation of Run Time of the UPS for a given: • Power of Load (kW) • Battery Capacity (Ah) • It work on Excel • It is based on the Lead Acid Discharge Curves • it optimise the calculation of autonomy time for the battery that is considered working down to Deep Discharge limit for a given current • gives tested results

  15. Design Criteria Run Time Calculator • The Standard Capacity nominal value of a battery is for 20 Hours of discharge time to a final voltage of 1.75V per cell • The nominal capacity of a battery is reduced when is discharged at value of current that exceed the 20-Hour discharge rate • That means the real Capacity you can extract from the Battery is: k * C where is a reduction coefficient k < 1 How does the Calculator works: • Input: • Load Power (kW) • Battery Capacity (Ah) • Nominal Battery Voltage • Output : • the Run Time for the assigned Capacity (Ah)

  16. Design Criteria Run Time Calculator

  17. Design Criteria Run Time Calculator It performs the calculation of the Battery Current: Then the Ratio of the Battery Current and the Battery Capacity This value is Located On the Deep Discharge Characteristic this is a non linear passage , the K coefficient is so detected

  18. Design Criteria Run Time Calculator Finally the Run time is calculated Like : Output

  19. Design Criteria Run Time Calculator • Accuracy GXT Internal Deep. Disch. Char.

  20. Battery Sizing • Some Autonomy Data

  21. Battery Sizing • Some Autonomy Data

  22. Battery Sizing • Some Autonomy Data

  23. Battery Sizing • Some Autonomy Data for GXT + 2x 240VBATT Batt.Cab.

  24. Battery Sizing • Some Autonomy Data for GXT + 240VLRT Batt.Cab.

  25. Battery Sizing • GXT6000 (1x1 & 3x1) can be extended with the limitation of two Cabinet 240VBATT max - for Thermal reason • GXT8000 3X1 & GXT10000 (1x1 & 3x1) can be extended either with Cabinet 240VBATT and Cabinet 240VLRT • The max numbers of Cabinets depend by the allowed recharging time ( the Batt. Charger rating is 1.5Amp) • If more than two Cabinets 240VLRT are necessary then is recommended to use the GXT5000T-230NB & GXT10000T-230NB with improved Battery Charger (4,5Amp) . But they are not CE certified

  26. Battery Sizing • Some Autonomy Data for Hinet with Batt.Cab.

  27. Battery Sizing • Ni-Cd Battery • Some application require high life despite of the price (Very High Price !!) • The Voltage/Cell for Ni-Cd Batt. change like this: • 1,4 V/el in Floating • 1,07 V/el in end of Discharge • If you have an UPS design with Lead Acid Battery to switch with Ni-Cd is necessary to increase the Number of Cells in the same ratio as the V/el • For instance Hinet requires 192 Cells in Pb and for Ni-Cd 192* (2,25/1,4) = 308 Ni-Cd Cells

  28. Battery Sizing • Ni-Cd Battery • The Low Battery Limit must be adjusted in the same way • 308* 1,07 = 329 Volt • Hinet allow to easily adjust these limits so it’s open to be supplied with Ni-Cd Batteries. • The recharge current for Ni-Cd Battery must be well regulated • The Hinet Battery charger feed a constant current that can be 1- 3.5 - 7 Amp up to Floating Point were the Float voltage will be held Fixed.

  29. Nfinity Extended Batt. Cabinet • This Cabinet Allow to use the same Intelligent Battery Module of Nfinity frame • P/N is N900Exx00000 • It is a Matching Cabinet • Need two Intellislot Battery Card (IBC), • 1on Nfinity, 1 on the Cabinet + serial cable for communication • 2 shipped with each Extended Battery Cabinet • The DC Power connection cable • P/Ns: NPNPEXTBC3, NPNPEXTBC15 • These include specially designed connectors • In the UPS configuration Menu select : • Change Settings (press <Return>) • Intellislot Battery Cabinet (press <Return>) • enter the quantity of extended Battery Cabinet installed • press Return and ESC

  30. Nfinity External Batt. Cabinet • Can 10 years batteries be used? • Not inside the main UPS Frame • Only 5 years Battery Modules are designed for Nfinity UPS • By using the External Battery Cabinet: • New version has same front bezels as Nfinity • Cabinet type: CZ1 Size 90Ah/120V with Battery Charger • Batteries Used are Power Batteries SLF12105 • Note the difference between: External Battery Cabinet and Extended Battery Cabinet • External BC is not an “Intelligent” backed up Battery • does not use Nfinity Battery Modules • the Battery Module will not disconnect from the others when a failure is detected

  31. Battery Sizing • EXTERNAL BATTERY CABINET CZ1 the Old and New one

  32. Battery Sizing • Where is the Battery charger ? • located in the Power Module • the charger has a temperature compensation with a current limited to 3,2A • Others functions of the Power Module are: • Power Factor Correction Circuit working with PWM at 20kHz. • Input Power Factor close to 0,99 (see following slide) • Output Inverter • Starting from version G3 (mid-2002) : Able to accept three phase and single phase input line • Older G2 modules cannot be fitted in new 3x1 frames

  33. Thank you for your attention For more questions contact: Product Support Desk on http://my.liebert-hiross.com