1 / 13

CMS ventilation system

CMS ventilation system. Air handling units Principle LHC status UX ventilation modes USC ventilation principle Fire detection and smoke extraction Pressurization safe areas Gas extraction Other buildings. Air handling units. SUX. 50 units installed. SH. USC. BTB. PRB. BTA. BTB.

roy
Download Presentation

CMS ventilation system

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. CMS ventilation system • Air handling units • Principle • LHC status • UX ventilation modes • USC ventilation principle • Fire detection and smoke extraction • Pressurization safe areas • Gas extraction • Other buildings Bernard Pirollet TS-CV-EPA

  2. Air handling units SUX 50 units installed SH Bernard Pirollet TS-CV-EPA USC

  3. BTB PRB BTA BTB BTB BLO BLP BTB BLP BLO BTB BRR/T BTB BTB BTA BAY BTT BTT MRE BTA MRM MRM MRE BT2 BT2 BT2 BLO - - N 210 180 + BA6 MRE M BRR/T M BRR/T L L L E E L P E BTO D P - - 210 180 + V BAY M BFY L S L P E BLO BLO BLO BAY BAY BAY MRE MRE MRE BA6 M BAY M M M L L • Air supplied & air extracted • Quality • Pressurization • Temperature • Dew point • Smoke and gas extraction Principle Bernard Pirollet TS-CV-EPA

  4. Principle • LHC status • Cap open / Cap closed • LHC run / Shut down • Purge • Emergency Bernard Pirollet TS-CV-EPA

  5. UX ventilation modes • Supply Extraction (m3/h) Gas • Cap open Shut down 22 500 30 000 (SX) 0 • Cap closed Shut down 22 500 22 500 5 000 • Cap closed LHC run 22 500 22 500 (recycling) 5 000 • Purge (fresh air) 22 500 22 500 (RP control) 5 000 • Emergency Cap closed 90 000 90 000 5 000 • Emergency Cap open 90 000 90 000 (SX) 0 Bernard Pirollet TS-CV-EPA

  6. USC ventilation principle • Supply Extraction (m3/h) Gas • Service area 20 000 20 000 5000 • Post treatment 40 000 • Racks areas 20 000 20 000 5000 • Post treatment 13 000/ 26 000 Bernard Pirollet TS-CV-EPA

  7. Cold smoke extraction Actions Detection Fire men All the air handling units of the concerned area are automatically stopped (Ts/cv) Smoke extraction mode activated by fire men (fire men cubicle) During extraction mode extraction filters will be by-passed End of fire men action No action with RP Air handling units in normal mode restarted by TS-CV Material design 400°C/2h Bernard Pirollet TS-CV-EPA

  8. “Fire cubicle” Bernard Pirollet TS-CV-EPA

  9. Pressurization areas 3 separate & independent areas: • Experimental caverns (-) (UX pts 1/2/8 & UXC55 pt5) • Protected areas- technical caverns (+) (USA 15 pt1,UX 85 pt8 & USC55 pt5) • Safe area (++) (PM/PZ) M M M D N V S L E L E M M M D N V S L E L E M M M D N V S L E L E (-) UXC55 Differential pressure (+) PX56 (+ +) Racks Services Bernard Pirollet TS-CV-EPA USC55 PM54

  10. Pressurization safe areas Bernard Pirollet TS-CV-EPA

  11. Extraction gaz Argon Argon gas Extraction SX5 - 3585 - Espace confié / Confined room M MRE BLO M MRE BLO M A 5 000 m3/h UAEW-519/520-SX5-UXC55 PX56 UXC55 Extraction mélange gazeux / Mixing gas extraction 22/02/2000 C.MARTEL Schéma de principe - Principle schematic Racks Cryogénie SUPERVISEUR : J.ROCHE PM54 INDICE ORGANISATION EUROPEENNE POUR USC55 CERN LHCU.3599.1011.4 LA RECHERCHE NUCLEAIRE EUROPEAN ORGANIZATION FOR NUCLEAR RESEARCH Gas extraction UX 5 000 m3/h BLO standby BLO BLO BAY BAY BAY MRE MRE MRE BA6 M BAY M A M M M L L L V BD1 5 000 m3/h UAEW-519-SX5-UXC55 BT5 BLO BLO BLO BAY BAY BAY MRE MRE MRE BA6 M BAY M M M L L L V UAEW-520-SX5-UXC55 UIAE UIAN Bernard Pirollet TS-CV-EPA

  12. Gas extraction USC Bernard Pirollet TS-CV-EPA

  13. Bernard Pirollet TS-CV-EPA