360 likes | 632 Views
Equations for sensible energy transport by air . Energy per unit of mass ?hsensible = cp
E N D
1. Objectives Lean about energy transport by air
Calculate Cooling and Heating loads
Solve 1-D conduction
Design whether condition
Use knowledge of heat transfer to calculate
Solar gains
Internal gains
3. Equations for latent energy transport by air Energy per unit of mass ?hlatent = ?w × hfg [Btu/lbda]
hfg - specific energy of water phase change (1000 Btu/lbw)
Heat transfer (rate) Ql = m × ?w × hfg [Btu/h]
Ql = 1000 × WaterFloowRate (only for IP units)
4. Total energy transport calculation using enthalpies from chat Energy per unit of mass ?h=h1-h2 [Btu/lbda]
Heat transfer (rate) Qtotal = m × ?h [Btu/h]
Qtotal = Qsensible + Qlatent
5. Why do we calculate heating and cooling loads? To estimate amount of energy used for heating and cooling by a building
To size heating and cooling equipment for a building
Because my supervisor request that
6. Introduction to Heat Transfer Conduction
Components
Convection
Air flows (sensible and latent)
Radiation
Solar gains (cooling only)
Increased conduction (cooling only)
Phase change
Water vapor/steam
Internal gains (cooling only)
Sensible and latent
7. 1-D Conduction
8. Material k Values
9. R = l/k
Q = (A/Rtotal)?T
Add resistances in series
Add U-values in parallel
13. Which of the following statements about a material is true? A high U-value is a good insulator, and a high R-value is a good conductor.
A high U-value is a good conductor, and a high R-value is a good insulator.
A high U-value is a good insulator, and a high R-value is a good insulator.
A high U-value is a good conductor, and a high R-value is a good conductor.
14. Example Consider a 1 ft × 1 ft × 1 ft box
Two of the sides are 2 thick extruded expanded polystyrene foam
The other four sides are 2 thick plywood
The inside of the box needs to be maintained at 120 °F
The air around the box is still and at 80 °F
How much heating do you need?
15. The Moral of the Story Calculate R-values for each series path
Convert them to U-values
Find the appropriate area for each U-value
Multiply U-valuei by Areai
Sum UAi
Calculate Q = S(UAi)?T
16. Heat transfer in the building Not only conduction and convection !
17. Infiltration Air transport Sensible energy
Previously defined
Q = m × cp × ?T [BTU/hr, W]
?T= T indoor T outdoor
or Q = 1.1 BTU/(hr CFM °F) × V × ?T [BTU/hr]
18. Latent Infiltration and Ventilation Can either track enthalpy and temperature and separate latent and sensible later:
Q total = m × ?h [BTU/hr, W]
Q latent = Q total - Q sensible = m × ?h - m × cp × ?T
Or, track humidity ratio:
Q latent = m × ?w × hfg
19. Ventilation Example Supply 500 CFM of outside air to our classroom
Outside 90 °F 61% RH
Inside 75 °F 40% RH
What is the latent load from ventilation?
Q latent = m × hfg × ?w
Q = ? × V × hfg × ?w
Q = 0.076 lbair/ft3 × 500 ft3/min × 1076 BTU/lb × (0.01867 lbH2O/lbair - .00759 lbH2O/lbair) × 60 min/hr
Q = 26.3 kBTU/hr
20. What is the difference between ventilation and infiltration? Ventilation refers to the total amount of air entering a space, and infiltration refers only to air that unintentionally enters.
Ventilation is intended air entry into a space. Infiltration is unintended air entry.
Infiltration is uncontrolled ventilation.
21. Where do you get information about amount of ventilation required? ASHRAE Standard 62
Table 2
Hotly debated many addenda and changes
Tao and Janis Table 2.9A
22. Ground Contact Receives less attention:
3-D conduction problem
Ground temperature is often much closer to indoor air temperature
Use F- value for slab floor [BTU/(hr °F ft)]
Note different units from U-value
Multiply by slab edge length
Add to SUA
Still need to include basement wall area
Tao and Janis Tables 2.10 and 2.11
More details in ASHRAE handbook -Chapter 29
23. Ground Contact 3-D conduction problem
Ground temperature is often much closer to indoor air temperature
Use F- value for slab floor
Multiply by slab edge length
and Add to SUA
24. Summary of Heating Loads Conduction and convection principles can be used to calculate heat loss for individual components
Convection principles used to account for infiltration and ventilation
25. Where do you get information about amount of ventilation required? ASHRAE Standard 62
Table 2
Tao and Janis Table 2.9A
26. Weather Data Table 2-2A (Tao and Janis) or
Chapter 28 of ASHRAE Fundamentals
For heating use the 99% design DB value
99% of hours during the winter it will be warmer than this Design Temperature
Elevation, latitude, longitude
27. For cooling use the 1% DB and
coincident WB for load calculations
1% of hours during the summer will be warmer than this Design Temperature
Use the 1% design WB for specification of equipment
28. Solar Gain Affects conductive heat gains because outside surfaces get hot
Use Q = UˇAˇ?T
Replace ?T with TETD total equivalent temperature differential
Q = UˇAˇ TETD
Tables 2-12 2-14 in Tao and Janis
Replace ?T with CLTD (Tables 1 and 2 Chapter 29 of ASHRAE Fundamentals)
29. Solar Gain
TETD depends on:
orientation,
time of day,
wall properties
surface color
thermal capacity
30. Glazing Q = UˇAˇ?T+A×SC×SHGF
Calculate conduction normally Q = UˇAˇ?T
Use U-values from NFRC National Fenestration Rating Council
ALREADY INCLUDES AIRFILMS
http://cpd.nfrc.org/pubsearch/psMain.asp
Use the U-value for the actual window that you are going to use
Only use default values if absolutely necessary
Tao and Janis - no data
Tables 4 and 15, Chapter 31 ASHRAE Fundamentals
31. Shading Coefficient - SC Ratio of how much sunlight passes through relative to a clean 1/8 thick piece of glass
Depends on
Window coatings
Actually a spectral property
Frame shading, dirt, etc.
Use the SHGC value from NFRC for a particular window
SC=SHGC/0.87
Lower it further for blinds, awnings, shading, dirt
32. More about Windows Spectral coatings (low-e)
Allows visible energy to pass, but limits infrared radiation
Particularly short wave
Tints
Polyester films
Gas fills
All improve (lower) the U-value
33. Low-? coatings
34. Internal gains What contributes to internal gains?
How much?
What about latent internal gains?
35. Internal gains
ASHRAE Fundamentals ch. 29 or handouts
Table 1 people
Table 2 lighting, Table 3 motors
Table 5 cooking appliances
Table 6 -10 Medical, laboratory, office
36. Readings:
Tao and Janis 2.4-2.8.10