Modbus to DNP3 Protocol Converter. Group 24: Joshua Daly, CpE Daniel Doherty, CpE Mac Lightbourn , EE Joseph Wilkinson, EE. Controllers like this one alternate which pumps in the lift station are active to maintain the desired flow rate and water level.

alban
Download Presentation

Modbus to DNP3 Protocol Converter

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Modbus to DNP3 Protocol Converter Group 24: Joshua Daly, CpE Daniel Doherty, CpE Mac Lightbourn , EE Joseph Wilkinson, EE

  2. Controllers like this one alternate which pumps in the lift station are active to maintain the desired flow rate and water level. • Other functions include ventilation control and alarms for high water or odor levels. • Many controllers are networked together and there is no industry-standard network protocol.

  3. Modbus vs. DNP3 Project motivation: MPE needs to allow for communication between network nodes that are using these different protocols.

  4. Four-Semester Plan Phase I Device Build User Interface Initialization Phase II Network Communications Security

  5. Key Specs • Operates between -10 and 80 degrees Celsius • Protects against surges of 120 V • MCU clock has a backup battery that can power the MCU for 12 hours if power is lost • Sends alarm to master device when power is lost • Takes Ethernet input and gives Ethernet output • Allows user to view and change networking parameters • Logs 20,000 events, even when power is lost, with 98% fidelity • Records date and time of each event to millisecond accuracy • Notifies master device of all events with 95% fidelity

  6. Four-Layer PCB Design

  7. Choosing an MCU

  8. Ethernet Integration • Ethernet jacks include integrated magnetic isolation modules • Input and output both feature a dedicated Ethernet controller • Modbus input and DNP3 output interface with the MCU via SPI ports for high speed communications

  9. ENC28J60 J00-0045NL

  10. Noise Due to SPI Lines • MOSI and MISO signals transmit at frequencies of 10-100 MHz • Rapid logic transitions on these signals combined with the effective series inductance of the traces lead to a field effect • The result is noise

  11. Noise Due to SPI Lines • To reduce the noise, we took three measures • We placed pull-up resistors close to the microcontroller • We used large-value resistors for the pull-ups and large-value bypass capacitors • We isolated the MOSI and MISO lines with copper ground

  12. Push Buttons and LEDs

  13. Coding Environments • Visual Studio • Used while PCB board was in development • Familiar environment • Code Warrior • Freescale MCU • Optimization of .s19 file

  14. Firmware Overview • Creation of data Structs to maintain parameters • Menu system • Allows user to adjust stored parameters • Strict requirements from the sponsor • Initialize all components on the PCB • Handle all button functionality

  15. Firmware Challenges • Project requirements changed midway through • Integration of all parts on PCB • Delayed action based on buttons • Code must be well documented and easily modified

  16. Data Storage • Stored in contiguous blocks • Storage requirements • Factory defined • User defined

  17. Buttons • Required Guidelines • Button Functionality • Menu Navigation • Time Delayed press

  18. Screen • Display Screen • 3 7-segement displays • Mimic the current display used by MPE • Allows user to visually navigate and set parameters

  19. Power Subsystem

  20. Power Supply Requirements Takes in 24 V DC • This supply is shared with other components in the lift station control panel • This is a low voltage in comparison to other devices being used in industrial applications • The low voltage bypasses some of the testing requirements for meeting UL standards

  21. Power Supply Requirements Surge Protection • Must handle currents up to 80 A • Must correct irregular voltages • Multiple devices are connected in a shunt configuration for combined benefits

  22. Power Supply Requirements

  23. Input Surge Protection

  24. Power Supply Requirements Must be fed through a DIN rail mount • All devices in the lift station control panel attach to one rail • Mount also serves as chassis ground for added surge protection

  25. DC/DC Converter • Voltage is stepped down to 3.3 V and then fed to the power plane • To conserve power, a passive switching regulator was chosen • Our configuration is a common circuit with extensive application notes

  26. Financials