Clarification on Specified Emergency Power (1) Status Proposal Steady State Consumption as given in RDR Table is 1.4 MW Inrush Current of Users must be covered implies a Factor up to 3 Emergency Supply System Design and Costing allows for 5 to 10 MW
E N D
Clarification on Specified Emergency Power (1) • Status Proposal • Steady State Consumption as given in RDR Table is 1.4 MW • Inrush Current of Users must be covered implies • a Factor up to 3 • Emergency Supply System Design and Costing allows for 5 to 10 MW • System Design mainly based on ability to supply over • several km. • RDR Table could be corrected to show Value including inrush Capability : about 4 MVA • To be compared to 5 MVA for LHC at CERN GDE Meeting, Beijing, 4-7 February 2007
Clarification on Specified Emergency Power (2) • List of Main Users (Non Exhaustive) • Emergency Ventilation • Emergency Lighting • Emergency Pumps (Drainage – Firefighting) • Lifts • Alarms and Signaling Systems • Access Control Systems • Supply of Battery back up Systems • etc … GDE Meeting, Beijing, 4-7 February 2007