EMERGENCY POWER SUPPLIES. Problems of Power Failure in Industries. Primary intention of Power Utility - Provide uninterrupted power Causes for interruption: Equipment failures and line faults System instability leading to tripping
E N D
Problems of Power Failure in Industries • Primary intention of Power Utility - Provide uninterrupted power • Causes for interruption: • Equipment failures and line faults • System instability leading to tripping • Deliberate tripping (usually automatically) to save system collapse • Natural causes - Hurricane, earthquake, flood
Problems of Power Failure in Industries • No power system can be guaranteed to be free from interruptions • Transmission line faults • Equipment malfunctions • Weather related failures • Failures due to other external causes in exposed parts of system • Human errors • System instability due to major disturbances
Problems of Power Failure in Industries • Outages more likely in a system without adequate generation reserve • No buffer storage possible for Electrical energy • Frequency drop due to system overload • Complete system collapse due to inadequate system reserves
Implications of Power Failure • Accidents involving death or injury • Damage to equipment • Creation of potentially hazardous conditions • Loss of production (not only for duration of interruption, also time required to bring process to its pre-failure state) Accidents that can result from a sudden interruption • Dropping of loads lifted by electromagnets • Release of toxic materials • Spillage of hot metal • Explosions • Runaway reactions
Implications of Power Failure Can cause Potentially Hazardous situations • Loss of control power • Loss of lighting in operational areas or exit routes • Loss of ventilation/exhaust systems • Loss of signaling and alarms • Loss of fire-fighting systems
Costs of Power Interruption • Direct Costs • Costs due to lost man-hours • Direct expenses due to death/injury • Cost of repairs to damaged equipment • Lost production • Indirect Costs • Legal costs - Accidents involving third parties/ quality problems/ non-fulfillment of contract commitments • Loss of good will
Power Failure Problem Mitigation • Problem mitigation • Installation and use of adequate reserves • Deliberate tripping by islanding schemes • Advance preparation during natural calamities • Proper equipment selection, maintenance • Power supply restoration • Auto-reclose operations (self clearing of transient faults) • Switching to redundant feeders • Starting standby generating sources
Solutions for Power Failure • Distributed generation capacity - Owned by Utility, Industries or third parties • Engine generators, gas turbines - Quick start, can take up peak demands Advantages • Closer to load, not affected by transmission circuit problems • Capable of being started, brought up to load faster • Serve as standby sources • Provide uninterrupted power when synchronized with utility • Improve voltage profile in end-of-line distribution circuits
Industrial Plant - Emergency Generation • Capacity to feed critical loads only • Break before make Switch – Brief interruption during transfer
Tolerance for Interruptions & Voltage/Freq. Excursions • Electrical equipment designed with tolerances in input voltage parameters – Can take care of limited variations • Desktop computers - Tolerate voltage fluctuations to some extent • By virtue of large capacitances • Internal regulation circuitry • Tolerance for voltage fluctuations - General industrial equipment • –10 to +6% for slow/sustained variations (sag/swells) • Considerably more for short time disturbances
CBEMA, ITIC and ANSI - Voltage Sensitivity Curves • Random data errors in computers due to voltage variations • Standard Curves • Indicating voltage limits causing no ill effects, plotted against time • Earliest curves developed by Computer and Business Equipment Manufacturers Association (CBEMA)
ITIC Voltage Sensitivity Curves(Information technology industry council)
Uninterrupted Power, Emergency Power and Standby Power • Uninterrupted Power - Guarantees continuous power without even a momentary break to connected loads • Emergency Power - Minimum backup power for emergency applications (emergency lighting, emergency shut down systems, alarm systems, elevators, life safety and security systems). Brief interruption can be tolerated • Standby Power - Provision of substantial power to maintain all production, business processes during short/ long power outages
Different Solutions for Different Needs Needs of Equipment • Careful consideration for power quality or continuity needed • Questions to be asked • Can the load tolerate power interruption? If yes, for how long? • What is the effect of a power failure? • Are there associated costs? • Are there safety hazards associated with a failure?
Static UPS Systems • Widely used for feeding lower capacity, low voltage loads - Instrumentation equipment, process control computers, general computing equipment, critical lubrication drives and emergency lighting • Improves power quality to critical loads • Prone to component failures like any other electronic system • Redundant modules for critical loads to improve reliability
Subsystems of typical Static UPS • Backup source (storage battery) • Rectifier (also used as charger for battery) • DC bus (link between rectifier output, battery and inverter input) • Inverter for synthesis of AC output from DC • Regulation and conditioning of mains power supply • Static transfer switch or static bypass (optional) • Maintenance bypass (optional) • Isolation transformer (optional)
Static UPS System • Storage battery as power source - Critical component for reliability • Rectifier • Converts power from mains into DC - Charges storage battery • Configured to cause minimum harmonics in mains AC • Provided with filters to ensure ripple free output
Static UPS System • Battery - Maintains voltage of DC bus when mains power fails • Voltage keeps falling as battery continues to discharge • Low DC voltage alarm • Cutout to trip inverter to avoid over-discharging
Static UPS System • Inverter converts voltage of DC bus to synthesized AC output • Low capacity inverters - Partial square or trapezoidal waveform • Higher capacity inverters - Pulse-width modulated sinusoidal AC output • Input protection - Surge protection devices to protect sensitive components • Output protection - Fuses/MCCBs with overload protectors, surge protection devices
Static UPS System • Voltage regulating device between AC mains and UPS where very wide fluctuations of input voltage expected • To keep battery from going into discharge mode at low mains voltage conditions (sustained sag) • To regulate output voltage when mains power is directly connected to loads • Static switch - Automatic load transfer from mains power to inverter or vice versa • Filter - Control communication of noise, harmonics from power mains to loads
Static UPS System • Maintenance bypass • Optional component • Manually operated external switch • For undertaking UPS maintenance • Isolation transformer - To avoid surges, common mode noise from being conveyed to loads
Types of Static UPS Systems • Passive (offline) • Line interactive • Double conversion (online)
Passive UPS Power flow under normal (mains power available) condition Power flow under mains failure condition
Passive UPS • Definite delay involved in changeover - 8 to 10 ms • Loads must be able to tolerate break of supply • Mechanical relay instead of static switch in cheaper designs – Slower than static switch • Needs attention while selecting UPS
Passive UPS • Advantages • Cost effective - Rectifier sized only for battery current, Inverter sized only for short duration • Limited losses in inverter (only during its operation) • Generally restricted to lower capacities (2 kVA or less) • Unsuitable where break in output not acceptable • Limited power quality improvement
Passive UPS • Some UPS designs - Changeover not just for mains failure conditions, also during supply voltage, frequency drift Disadvantages • Frequent battery discharge-charge cycles - Reduced battery life • Lower backup time during actual mains failure
Line Interactive UPS • Static switch positioned differently from Passive UPS • Not involved in switching of load from mains to inverter
Line Interactive UPS • Static switch connects mains supply to load when it is present • Inverter module connected to load in parallel • When mains power fails, inverter module operates as inverter, power flow direction is reversed • Static switch opens to prevent flow of power back to mains • Limited to smaller ratings only
Double Conversion UPS • Primary mode of power flow from mains to rectifier to inverter and to loads • Rectifier supplies power for loads, also charges battery • When mains power fails battery supplies power • No break of supply at UPS output • Higher rectifier current – Battery charging current plus load current • Most designs provided with static switch - Automatic transfer of loads from inverter to mains in case of inverter module failure
Double Conversion UPS • Static switch omitted in some low output UPS designs • Reduced UPS cost • Carries risk of power loss if inverter fails
Double Conversion UPS Advantages • Harmonics, surges and noise not get reflected at output • Inverter can operate at own frequency independent of mains frequency Disadvantages • Higher cost • Rectifier for load current plus battery charging current • Inverter rated for continuous operation • Increased power losses
Double Conversion UPS • Standby batteries normally sized for providing backup for short periods only - 15 minutes to 1 hour • Higher duration power outages - Appropriate standby power source for UPS before battery gets fully discharged • UPS designed for ensuring safe, orderly shutdown of equipment in event of mains failure • Batteries charged at high rate to ensure quick restoration after power interruption
Other types of UPS Systems • Passive UPS with Ferro-resonant output transformer • 3-winding Ferro-resonant transformer at UPS output • Two windings for input (one from mains, one from inverter) one common output winding • Hybrid passive UPS system
UPS with ferro resonant transformer • Similar in concept to passive UPS system • Loads fed from mains through static switch, Ferro-resonant transformer when mains available • Static switch opens, inverter takes up load through transformer when mains fails • Ferro-resonant transformer - Acts as output filter, can regulate slow voltage changes • Can minimize break of output when mains fail and inverter takes up load • Problems • Unstable output when load has power factor correction capacitors • Low efficiency at part loads • May interfere with fuse protection • May call for surge protection on output side
Hybrid passive Configuration • Load directly connected to mains when it is present, switched to battery when mains power fails • Inverter always in circuit • Switching delay between mains and battery eliminated by proper setting of regulator • Behaves like double conversion UPS except there are two different rectifiers, one for charging battery and another for supplying load • Disadvantage - Any failure of inverter module can cause failure of UPS output
Hybrid UPS System Combines advantages Static and Rotary Systems
Redundant UPS Configuration • UPS systems also prone to failure just like any other electronic equipment • Failures also caused by battery problems • Redundancy to prevent interruptions due to failure
Redundant UPS Configuration • Usually referred to as N+1 redundant configuration • N modules can supply total power requirement by equal load sharing • One additional parallel module for little extra capacity Continued operation when one module fails • Redundancy not just for electronic components but also for battery • Additional static switch fed from separate source to switch to alternate supply during multiple module failure
UPS - Installation • To be done by experienced personnel • Read, understand manufacturer’s instructions fully before installation and commissioning • Follow Safety procedures strictly to avoid danger to personnel and equipment • Batteries are heavy – Take care during handling, transportation • Acid is corrosive – Take care in handling, storage
Batteries Different Types, Pros and Cons • Energy storage device used for UPS • Energy stored in form of chemical energy during charging, converted back to electrical energy during discharge phase • DC of battery converted to AC by UPS and delivered to loads • Most commonly used battery types • Lead acid battery (Lead Calcium and Lead Antimony) • Nickel Cadmium battery
Lead Acid, Nickel Cadmium Batteries • Lead Acid Battery - Use lead electrodes, Sulphuric acid as electrolyte • Lead Calcium Type • Not suitable for charge-discharge cycling applications • Can undergo 30-50 deep discharges over life • Lead Antimony Type • Can tolerate up to 300-500 deep discharge cycles • Nickel Cadmium Battery - Electrodes made of nickel- cadmium, potassium hydroxide as electrolyte • Lead acid and Nickel-Cadmium batteries designed both in flooded and valve regulated versions
Batteries • Flooded cell batteries - Have liquid electrolyte like sulphuric acid • Valve regulated type (maintenance free batteries) • Do not have free liquid electrolyte • Do not require specially designed room with dedicated temperature control, dedicated exhaust and ventilation system or hazardous area equipment • Less maintenance intensive • Can be oriented in any direction without electrolyte spillage problems • Incorporate following technologies • AGM - Absorbed glass matte technology • Gelled electrolyte technology • Oxygen recombination technology
Batteries • AGM (Absorbed glass matte technology) - Electrolyte completely absorbed in glass matte • Gel cell - Electrolyte in gel form • Valve regulated battery • Smaller in size compared to flooded cell battery. Typically AGM battery has app. 40% less electrolyte than flooded cell, Gel cell about 15% less electrolyte • Also use recombination technology - Gases evolved during charging recombine to form water (eliminates need for adding water)