An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Planning Electrical Circuits Written by: Ryan Talton

  2. Planning for the SEP and/or Sub panel • SEP should always be located near the service entrance • Might want to place the SEP close to large appliances and equipment that will require most electricity • Should be accessible at all times • Try to anticipate future needs when finding site • Never have SEP in clothes closet or bathroom • Box Should be installed 40-48 inches above floor level • Can be installed flush or surface mount.

  3. Outlet Spacing • Overhead Lighting • May be placed in discretion of owner • In single overhead light should be in center of room • Wall Outlets (Receptacles) • No point on a unbroken wall measures greater than 6 feet • This includes wall space of 2 feet or more in width • Unbroken by doorways, fireplace, etc. • Most receptacles should be 12 and 16 inches above floor level

  4. Kitchen Countertop Outlets (Receptacles) • Should always be installed at each counterpace no wider than 12 inches • Should be installed within 24 inches of each other on countertops • No more than 18 inches above countertops • All kitchen Receptacles should be GFCI protected • We will learn more about this later

  5. Closet and Storage lighting Outlets • Surface mounted incandescent fixtures should be located 12 inches between fixtures and storage area • Surface mounted fluorescent- may be mounted within 6 inches of storage area • If recessed- both can be 6 inches from storage area.

  6. Determine the number of circuits necessary to meet wiring plan requirements Larger homes may call for more circuits Planning Small Appliance Branch Circuits

  7. What is a Small Appliance Branch Circuit • Generally supply power to kitchen counter top surfaces and dining room areas where small appliances are commonly used • Coffee makers, fry pans, blenders, toaster ovens, waffle irons

  8. Planning General Purpose Branch Circuits • Make up the largest portion of the home wiring system • Include all ceiling and wall mounted lighting outlets and most receptacles • Not ones for a specific purpose • All circuits originate in SEP

  9. How do I Calculate the Required Number of General Purpose Circuits • General Rule: • One General Purpose Circuit for every 500 square feet • 2500 sq ft house= 5 gpc • What about a house that is 2240 sq ft • 2240/500=4.48 • This equals 4.48 gpc • Always go to the next highest number when figuring the number of circuits • So: 2240/500=5 gpc • Only figure the amount of heated space • Not garage or porch space

  10. Balancing a Load • Why is it important to balance a load? • General rules are: • 10 outlets per 15 amp circuit General Purpose • 13 outlets per 20 amp circuit General Purpose • If the above 10 or 13, add another circuit

  11. Example Problem 40’ 50’ Determine the number of general purpose circuits. (1 circuit for every 500’)

  12. Answer to Example 1 • 40’x50’=2000 sq ft. • 2000/500=4 GPC

  13. Example 2 • 45’ 65’ • 20 amp GPC • 75 outlets

  14. Answer to example 2 • 45’ x 65’=2925sq ft • 2925/500=5.85 • Need 6 circuits • 75 outlets / 6 circuits= 12.5 • Do we need to add another circuit?

  15. Example 3 35’ Two story house 15 amp GP 55’ 96 outlets

  16. answer • 35’ x 55’=1925 sq ft • 1925 x 2=3850 sq ft for both floors • 3850 / 500= 7.7 • Need 8 circuits • 96 outlets / 8 = 12 outlets per circuit • Do we need another circuit • Add 2 circuits • Need 10 general purpose circuits which would make it 9.6 outlets per circuit