1 / 29

Sensor presentation

Sensor presentation. Product Scope. A Sensor is a device intended to transmit a signal corresponding to the primary current or voltage to the secondary equipment. Power IT Sensors are typically used in MV switchgears and switches for measuring, protection and indication.

barney
Download Presentation

Sensor presentation

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Sensor presentation

  2. Product Scope • A Sensor is a device intended to transmit a signal corresponding to the primary current or voltage to the secondary equipment. • PowerIT Sensors are typically used in MV switchgears and switches for measuring, protection and indication.

  3. Sensors vs. Instrument Transformers . . . but not in transformers! Trends in electrical engineering Size Performance Standardisation

  4. Sensors vs. Instrument Transformers Reason: The properties of material used Saturation Unlinear range Linear range Unlinear range Remedy: Absence of iron

  5. Why did ABB choose Rogowski coil • IEC-requirements • Cost effective • Low life cycle cost • Size Rogowski coil

  6. Rogowski coil • First published in1912 by Rogowski and Steinhous • Uniformly wound coil with non-magnetic core • Output signal is proportional to the derivate of primary current • IEC 60044-8

  7. Why did ABB choose voltage dividers • IEC-requirements • Cost effective • Safe • Low life cycle cost • Size Capacitive voltage divider Resistive voltage divider

  8. Voltage divider Resistive divider • Matched resistor pair • 1:10 000 divider ratio • Today accuracy up to class 1 Capacitive divider • Zc = 1/C • 1:10 000 divider ratio • Accuracy up to class 3 • Small size ideal for bushings IEC 60044-7

  9. Sensors vs. Instrument Transformers Rated primary current (CT)  Ip (log) Ipr = 240 A

  10. Sensors vs. Instrument Transformers Rated primary current range (sensor)  Ip (log) Ipr = 80 A....240 A.........…1250 A

  11. Sensors vs. Instrument Transformers Accuracy limit factor (Kalf) c Protection class 10P CS Ip (log) CT Ipr

  12. Sensors vs. Instrument Transformers Linearity Typical error, voltage sensor

  13. Sensors vs. Instrument Transformers Transmitted signal level Voltage transformer (ku=1,9) Voltage sensor 1,2 - 110 V, 25 VA At free potential, must be earthed Secondary losses =I2R 12 - 1100 mV, 80 mVA Always earthed in the sensor Secondary losses negligible Current transformer (Kalf =20) Current sensor 0,25 - 100 A, 5 VA At free potential, must be earthed Secondary losses = I2R 7,5 - 3000 mV, 6 mVA At free potential Secondary losses negligible High power Low power Low signal SAFE

  14. Sensors vs. Instrument Transformers Short-circuited secondary Voltage transformer Voltage sensor 250 M Isc Isc 25 k Isc/Acu = 160 A/mm2 Temp.500 C Explosion within 30 s Isc = Inormal

  15. Sensors vs. Instrument Transformers Open secondary Current transformer Current sensor Uopen Isc 0 - 10 kV Isc/Acu = 40 mA/mm2

  16. Sensors vs. Instrument Transformers Frequency response rel CT F/Hz 10 100 1000 10 000 VS (Cap.) VS (Res.) VT CS

  17. Sensors vs. Instrument Transformers Secondary wiring Terminal blocks Instr. transf. IED Wiring and screw connections Testing of connections Sensor IED Integrated cable and connector

  18. Secondary cabling of sensors Sensor IED S1 S2

  19. Sensors vs. Instrument Transformers Compactness Current transformer Combi Sensor Voltage transformer Small size of active parts Only one core

  20. Sensor Technology - CT/VT vs. Sensors CT / VT Sensors Signal 1/5A / 100/110 V 150mV / 2V Secondary cables Excluded Incl. and tested Linearity No Yes Saturation Yes No Ferroresonance Yes (VT) No Temperature coefficient No Incl. in accuracy EMC No Shielded Short-circuited secondary Destructive (VT) Safe Open secondary Destructive (CT) Safe Weight 40-60 kg (CT + VT) 2-25 kg (Combi) Standardisation possible No Yes

  21. Standards for Sensors Sensors from ABB are designed, manufactured and tested according to international standards when applicable. Voltage Sensors: IEC 60044-7 (1999-12) Instrument transformers – Part 7: Electronic voltage transformers Current Sensors: IEC 60044-8 (2002-07) Instrument transformers – Part 8: Electrical current transducers Combi Sensors: IEC 60044-3 (1980-01) Instrument transformers – Part 3: Combined transformers

  22. Sensor, type KEVCD_ • Current Sensor or Combi Sensor • Measurement and protection by one sensor • Dimensions and primary connections same as DIN-type CTs (DIN 42600) • 12, 17.5, 24 kV, two types: • A. </= 1250 A • B. > 1250 A (max. 3200 A) • Including coupling electrode for voltage indication

  23. Selection Guide for KEVCD type Sensors Nominal voltage Rated current range (first row) Functions included (second row) < 1250 A 1600...3200 A I + U + Uind I + Uind I + U + Uind I + Uind Upto 12 kV KEVCD 12 AE3 KEVCD 12 AG3 KEVCD 12 BE2 KEVCD 12 BG2 Upto 17.5 kV KEVCD 17.5 AE3 KEVCD 17.5 AG3 KEVCD 17.5 BE2 KEVCD 17.5 BG2 Upto 24 kV KEVCD 24 AE3 KEVCD 24 AG3 KEVCD 24 BE2 KEVCD 24 BG2

  24. Technical Information in KEVCD Sensor KEVCD 12 AE3 I-sensor Ipn: 1250 A • Ipr (to be advised), options: 80 A (Ir of switchgear: 80-160 A) • 240 A (Ir of switchgear: 160-480 A), with adapter • 640 A (Ir of switchgear: 480-1250 A), with adapter Output signal: 150 mV (50 Hz), 180 mV (60 Hz) Accuracy: Class 1* / 3 (*with correction factor) U-sensor Division ratio: 10.000/1 Accuracy: Class 1/3P Ith / Idyn: 40 kA, 3s / 100 kA Insulation level: 12/28/75 kV Frequency: 50/60 Hz With ribs on top Secondary cable (length to be advised), options: 5 m, 6.5 m or 7.5 m Primary polarity (to be advised), options: Normal or reversed Coupling electrode for voltage indication included

  25. Sensor concept

  26. Sensors in use around the world In use in 56 countries More than 20 000 sensors in operation

  27. Sensors in use around the world

  28. Arguments for Sensors Safety Short delivery time Smart integration

More Related