An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Final Project for Introduction to Plasma Processing Instructor: Prof. Kasra Etemadi STUDENT: Hosny, Ahmed A. Study SF6 Thermal Plasma generated during/after power interruption EE403/503, Fall 2005

  2. Outline • Introduction • Plasma characteristics • Advantages and Disadvantages of SF6 • Residual SF6 plasma species • Gas Insulated Switchgear (GIS) • Conclusion • Future work • References Hosny, Ahmed

  3. Electric Sub-circuit A V, I Circuit Breaker (CB) ON/Off V, I Electric Sub-circuit B What is Circuit Breaker (CB)? • CB is one of the most essential safety mechanisms in electric networks. • Interrupt short circuit currents (~ 60kA, low pf ~ 0.1). • Fault clearance time is very important for power system stability and avoid equipment damage for itself and the rest of the network. • CB can be characterized by, short circuit current, Rated voltage, … Figure 1: A schematic of Circuit Breaker Conditions Hosny, Ahmed

  4. Power Source materials Plasma + + + + + + Coupling Breakdown + + + Impulse Voltage, Transient Recovery Voltage (TRV) Manmade Plasmas Gas ( SF6) Plasma Elements… Extinguish Figure 2: A plot shows plasma elements. Hosny, Ahmed

  5. 105 Thermonuclear Plasmas Debye Length 1 cm 104 Electron Beam 1 m [m] 103 Solar Corona Average Electron Energy, [eV] 1 nm 1 m 102 P = 100 MHz P = 10 GHz P = 10 KHz P = 1 MHz P = 1 THz P = 100 Hz 1 mm Plasma Frequency Glow Discharge 1 Å 101 Gaseous Nebulae Interstellar Gas Arc Discharge 100 MHD Generator Ionosphere Solid 10-1 100 102 104 108 1010 1012 1014 1016 1018 1020 1022 1024 106 Electron Number density, [cm-3] Plasma Parameters… Hosny, Ahmed

  6. Plasma … Power Source Transient Recovery Voltage (TRV) • TRV is the voltage that builds up across a circuit breaker after the interruption of a fault current. • It consists of oscillations of lumped elements and of traveling waves. • It stresses the circuit breaker contacts and depends on the type and location of the fault in addition to the CB it self. Figure 3:(a) Single-phase equivalent circuit, (b) Transient recovery voltage [10] Hosny, Ahmed

  7. Arc Quenching Mechanism Figure 4: A Schematic representation of the puffer interrupter indicating some important physical processes. [2] Hosny, Ahmed

  8. Pros & Cons of SF6 • SF6 has a dielectric strength of about two to three times that of air. • It is nontoxic. • It is nonflammable. • It is noncorrosive; it doesn’t react with other materials because it is inert gas. However, when it is heated to 5000C it decomposes and its decomposition products react with other materials. • It exhibits excellent properties for arc quenching. So, it used as an interrupting medium in circuit breakers instead of air or oil. Hosny, Ahmed

  9. SF6 Circuit Breaker Figure 6: SF6 Circuit breaker, 36kV, 4000A, SC 50kA. [12] Figure 5: A plot of the thermal conductivity of SF6 and N2 [11] Hosny, Ahmed

  10. Residual SF6 Plasma Species • Ionization • Associative detachment • Dissociative attachment Table 1: Particle densities of residual SF6 plasma at 3000 K, 105 Pa [1] Hosny, Ahmed

  11. Electron Velocity Distribution Function Normalization Factor Collision frequency Energy loss due to collisions Hosny, Ahmed

  12. SF6CB applications … GIS Advantages of Gas-insulated switchgear (GIS) are: • Compact size. • Totally isolated from the atmospheric conditions such as air pollution, high temperature, snow, etc. • High degree of reliability and safety precaution. •  Easy to install. • SF6 has a dielectric strength much higher than air which is the insulated gas for conventional switchgear type. Figure 7: Gas-insulated substations (the picture shows a typical example) are very compact in size and reliable in operation Hosny, Ahmed

  13. Conclusion • The primary Cause of high transient over-voltage is the generation of multiple re-ignitions during the interrupting period by some types of CB. This TRV are the most likely cause of CB damage. • The design of CB can be determined using the thermal flow characteristics near current zero. • The critical field strength for the breakdown of the residual plasma has been found to be proportional to the pressure and is equal to 2.0V/(m.Pa), which is only ~ (1/45)th of that of SF6 at room temperature. Hosny, Ahmed

  14. Future Work • Further study on calculation of TRV and post-arc current just after current zero. • Advanced arc model and measurement techniques, which can support the physical phenomena in CBs. • Study the theory of positive corona in SF6 due to impulse voltage. Hosny, Ahmed

  15. References • J.D. Yan, M.T.C. Fang and Q.S. Liu, “Dielectric Breakdown of a Residual SF6 Plasma at 3000K under Diatomic Equilibrium”, IEEE Transaction on Dielectrics and Electrical Insulation, Vol. 4 No.1, February 1997. • D.W. Shimmin and et al, “Transient Pressure Variations in SF6 Puffer Circuit breakers”, Applied Physics, 23 (1990) pp. 533-541. • P.H. Schavemaker and L. Van der Sluis, “ The influence of the Topology of Test Circuits on the Interrupter Performance of Circuit Breakers”, IEEE Transaction on Power Delivery, Vol. 10, No. 4, October 1995. • M. T. C. Fang and M. Y. Shent, “A comparative study of two computational methods for the simulation of discharge development in SF6”, Appl. Phys. 28 (1995) 364-370. • Z. Ma and et al, “ An Investigation of Transient Over voltage Generation when switching high voltage shunt reactors by SF6 circuit Breaker”, IEEE Transaction on Power Delivery, Vol. 13, No. 2, April 1998. • Jong-Chul Lee and Youn J. Kim, “ Numerical Modeling of SF6 thermal plasma generated during the switching process”, Science Direct, Elsevier, 2005, pp. 72-80. Hosny, Ahmed

  16. References (Cont.) • Richard Morrow, “ Theory of Positive Corona in SF6 Due to a Voltage Impulse”, IEEE Transaction on Plasma Science, Vol. 19, No. 2, April 1991. • J. D. Yan, M. T. C. Fang and Q. S. Liu, “Dielectric Breakdown of a Residual SF6 Plasma at 3000 K under Diatomic Equilibrium”, IEEE Transaction on Dielectrics and Electric Insulation, Vol. 4, N0. 1, February 1997. • Gerd Duning and Manfred Lindmayer,” Plasma Density Decay of Vacuum Discharge After Current Zero”, IEEE Transaction on Plasma Science, Vol. 27, No. 4, August 1999. • Mazen Abdel-Salam and et al, High-Voltage Engineering: Theory and Practice, Marcel Dekker, Inc., New York, 2000 • http://www.metatechcorp.com/aps/cold_weather_operating_problems_.htm. • http://www.abb.com/global/abbzh/abbzh251.nsf!OpenDatabase&db=/global/seitp/seitp328.nsf&v=9AAC720001&e=us&c=C1256CCB004E3ABBC125699F0042734E. Hosny, Ahmed