An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. A Power System Example Starrett Mini-Lecture #3

  2. Power System Equations Start with Newton again .... T = I a We want to describe the motion of the rotating masses of the generators in the system

  3. The swing equation • 2H d2d = Paccwo dt2 • P = T w • a = d2d/dt2, acceleration is the second derivative of angular displacement w.r.t. time • w = dd/dt, speed is the first derivative

  4. Accelerating Power, Pacc • Pacc = Pmech - Pelec • Steady State => No acceleration • Pacc = 0 => Pmech = Pelec

  5. Classical Generator Model • Generator connected to Infinite bus through 2 lossless transmission lines • E’ and xd’ are constants • d is governed by the swing equation

  6. Simplifying the system . . . • Combine xd’ & XL1 & XL2 • jXT = jxd’ + jXL1 || jXL2 • The simplified system . . .

  7. Recall the power-angle curve • Pelec = E’ |VR| sin( d ) XT

  8. Use power-angle curve • Determine steady state (SEP)

  9. Fault study • Pre-fault => system as given • Fault => Short circuit at infinite bus • Pelec = [E’(0)/ jXT]sin(d) = 0 • Post-Fault => Open one transmission line • XT2 = xd’ + XL2 > XT

  10. Power angle curves

  11. Graphical illustration of the fault study

  12. Equal Area Criterion • 2Hd2d = Paccwo dt2 • rearrange & multiply both sides by 2dd/dt • 2 ddd2d = wo Paccdd dt dt2 H dt => d {dd}2 = wo Pacc dd dt {dt } H dt

  13. Integrating, • {dd}2 = wo Pacc dd{dt} H dt • For the system to be stable, d must go through a maximum => dd/dt must go through zero. Thus . . .dm • wo Pacc dd = 0 = { dd }2 • H { dt } • do

  14. The equal area criterion . . . • For the total area to be zero, the positive part must equal the negative part. (A1 = A2) • Pacc dd = A1 <= “Positive” Area • Pacc dd = A2 <= “Negative” Area dcl do dm dcl

  15. For the system to be stable for a given clearing angle d, there must be sufficient area under the curve for A2 to “cover” A1.

  16. In-class Exercise . . . • Draw a P-d curve • For a clearing angle of 80 degrees • is the system stable? • what is the maximum angle? • For a clearing angle of 120 degrees • is the system stable? • what is the maximum angle?

  17. Clearing at 80 degrees

  18. Clearing at 120 degrees

  19. What would plots of d vs. t look like for these 2 cases?