530 likes | 614 Views
1. Power and RMS Values. + −. Circuit in a box, two wires. + −. Circuit in a box, three wires. + −. Instantaneous power p(t) flowing into the box. Any wire can be the voltage reference.
E N D
+ − Circuit in a box, two wires + − Circuit in a box, three wires + − Instantaneous power p(t) flowing into the box Any wire can be the voltage reference Works for any circuit, as long as all N wires are accounted for. There must be (N – 1) voltage measurements, and (N – 1) current measurements.
Two-wire sinusoidal case zero average Power factor Average power
compare Root-mean squared value of a periodic waveform with period T Compare to the average power expression The average value of the squared voltage Apply v(t) to a resistor rms is based on a power concept, describing the equivalent voltage that will produce a given average power to a resistor
Root-mean squared value of a periodic waveform with period T For the sinusoidal case
Given single-phase v(t) and i(t) waveforms for a load • Determine their magnitudes and phase angles • Determine the average power • Determine the impedance of the load • Using a series RL or RC equivalent, determine the R and L or C
Determine voltage and current magnitudes and phase angles Using a cosine reference, Voltage cosine has peak = 100V, phase angle = -90º Current cosine has peak = 50A, phase angle = -135º Phasors
Thanks to Charles Steinmetz, Steady-State AC Problems are Greatly Simplified with Phasor Analysis (no differential equations are needed) Time Domain Frequency Domain Resistor voltage leads current Inductor current leads voltage Capacitor
Complex power S Projection of S on the imaginary axis Q P Projection of S on the real axis is the power factor Active and Reactive Power Form a Power Triangle
Consider a node, with voltage (to any reference), and three currents IA IB IC Question: Why is there conservation of P and Q in a circuit? Answer: Because of KCL, power cannot simply vanish but must be accounted for
Voltage and Currentin phase Q = 0 Voltage leads Current by 90° Q > 0 Current leads Voltage by 90° Q < 0 Voltage and Current Phasors for R’s, L’s, C’s Resistor Inductor Capacitor
Complex power S Projection of S on the imaginary axis Q P Projection of S on the real axis
Resistor also so Use rms V, I ,
Inductor also so Use rms V, I ,
Capacitor also so , Use rms V, I
Active and Reactive Power for R’s, L’s, C’s (a positive value is consumed, a negative value is produced) Active Power P Reactive Power Q Resistor Inductor Capacitor source of reactive power
Now, demonstrate Excel spreadsheet EE411_Voltage_Current_Power.xls to show the relationship between v(t), i(t), p(t), P, and Q
0.05 + j0.15 pu ohms PL + jQL PR + jQR /0 ° VR = 1.010 / - 1 0 ° VL = 1.020 IS IcapL IcapR j0.20 pu mhos j0.20 pu mhos A Transmission Line Example Calculate the P and Q flows (in per unit) for the loadflow situation shown below, and also check conservation of P and Q.
0.05 + j0.15 pu ohms PL + jQL PR + jQR /0 ° VR = 1.010 / - 1 0 ° VL = 1.020 IS IcapL IcapR j0.20 pu mhos j0.20 pu mhos
V 0 0 < D < 1 DT T RMS of some common periodic waveforms Duty cycle controller By inspection, this is the average value of the squared waveform
RMS of common periodic waveforms, cont. Sawtooth V 0 T
V 0 V 0 V 0 V 0 V 0 V 0 0 -V RMS of common periodic waveforms, cont. Using the power concept, it is easy to reason that the following waveforms would all produce the same average power to a resistor, and thus their rms values are identical and equal to the previous example
a b c n Three-phase, four wire system Reference Three Important Properties of Three-Phase Balanced Systems • Because they form a balanced set, the a-b-c currents sum to zero. Thus, there is no return current through the neutral or ground, which reduces wiring losses. • A N-wire system needs (N – 1) meters. A three-phase, four-wire system needs three meters. A three-phase, three-wire system needs only two meters. • The instantaneous power is constant
Observe Constant Three-Phase P and Q in Excel spreadsheet 1_Single_Phase_Three_Phase_Instantaneous_Power.xls
3 Z l ine c c I c 3Z 3Z load load a a b b Z l ine I 3Z a load – V + ab Z l ine I b Balanced three - phase systems, no matter if they are delta connected, wye connected, or a mix, are easy to solve if you follow these steps : Z l ine 1. Convert the entire circuit to an equivalent wye with a a a I a ground ed neutral . 2. Draw the one - line diagram for phase a , recognizing that phase a has one third of the P and Q . 3. Solve th e one - line diagram for line - to - neutral voltages and + line currents . The “One - Line” Z load Van 4. If needed, compute l ine - to - neutral voltages and line currents Diagram – for phases b and c using the ±120° relationships. 5. If needed, compute l ine - to - line voltages and delta currents n using the and ± 30 ° relationships. n
Now Work a Three-Phase Motor Power Factor Correction Example • A three-phase, 460V motor draws 5kW with a power factor of 0.80 lagging. Assuming that phasor voltage Van has phase angle zero, • Find phasor currents Ia and Iab and (note – Iab is inside • the motor delta windings) • Find the three phase motor Q and S • How much capacitive kVAr (three-phase) should be connected in • parallel with the motor to improve the net power factor to 0.95? • Assuming no change in supply voltage, what will be the new • after the kVArs are added?
Φ jXs Rs Ideal Transformer jXm Rm 7200:240V Turns ratio 7200:240 (30 : 1) (but approx. same amount of copper in each winding) 7200V 240V Single-Phase Transformer
Isc + Vsc - Short circuit test: Short circuit the 240V-side, and raise the 7200V-side voltage to a few percent of 7200, until rated current flows. There is almost no core flux so the magnetizing terms are negligible. Calculate Φ Turns ratio 7200:240 (but approx. same amount of copper in each winding) Short Circuit Test jXs Rs Ideal Transformer jXm Rm 7200:240V 7200V 240V
Ioc + Voc - Open circuit test: Open circuit the 7200V-side, and apply 240V to the 240V-side. The winding currents are small, so the series terms are negligible. Calculate Φ Turns ratio 7200:240 (but approx. same amount of copper in each winding) Open Circuit Test jXs Rs Ideal Transformer jXm Rm 7200:240V 7200V 240V
jXs Rs Ideal Transformer jXm Rm 7200:240V 7200V 240V Ideal Transformer 7200:240V 7200V 240V Single-Phase TransformerImpedance Reflection by the Square of the Turns Ratio
Φ jXs Rs Ideal Transformer jXm Rm 7200:240V Turns ratio 7200:240 (30 : 1) (but approx. same amount of copper in each winding) 7200V 240V See Grady 2007, pp. 76-77 Now Work a Single-Phase Transformer Example Open circuit and short circuit tests are performed on a single - phase, 7200:240V, 25kVA, 60Hz distribution transformer. The results are: · Short circuit test (short circuit the low - voltage side, energize the high - voltage side so that rated current flows , an d measure P and Q ). Measure d P = 400W, Q = 200VAr . s c s c s c s c · Open circuit test (open circuit the high - voltage side, apply rated voltage to the low - voltage side , and measure P and Q ). Measure d P = 100W, Q = 250VAr . oc oc oc oc Determine the four impedance val ues (in ohms) for the transformer model shown.
Wye-Equivalent One-Line Model A N jXs Rs Ideal Transformer jXm Rm N1 : N2 • Values for one of the transformer windings, on side 1 • Can reflect to side 2 using either individual transformer turns ratio N1:N2, or three-phase bank line-to-line turns ratio (which are identical ratios) A three-phase transformer can be three separate single-phase transformers, or one large transformer with three sets of windings N1:N2 N1:N2 N1:N2 Y - Y
Wye-Equivalent One-Line Model A N Ideal Transformer • Converting side 1 impedances from delta to equivalent wye • Can reflect to side 2 using either individual transformer turns ratio N1:N2, or three-phase • bank line-to-line turns ratio (which are identical ratios) For Delta-Delta Connection Model, Convert the Transformer to Equivalent Wye-Wye N1:N2 N1:N2 N1:N2 Δ - Δ