1 / 28

New Setting Free Algorithm for Out of Step Tripping

New Setting Free Algorithm for Out of Step Tripping. Sept. 2009 MOSCOW H Kang – ART Areva T&D B Cvorovic, P Horton- SAS Areva T&D. Introduction. Recoverable and non-recoverable power oscillations. Power Oscillations - Causes. What causes power oscillations?

carla-wynn
Download Presentation

New Setting Free Algorithm for Out of Step Tripping

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. New Setting Free Algorithm for Out of Step Tripping Sept. 2009 MOSCOW H Kang – ART Areva T&D B Cvorovic, P Horton- SAS Areva T&D

  2. Introduction Recoverable and non-recoverable power oscillations

  3. Power Oscillations - Causes • What causes power oscillations? • Imbalance in generation and load • Faults (internal and external) • Load/Line switching

  4. Power Oscillations – Definition (1) • Nature and definition of power oscillations • Power oscillation that leads to system split is called: • Out of step condition or pole slip or non-recoverable swing • Power oscillation that will not cause system split are called: • Stable swings or Recoverable swings

  5. Electrical . center Vs Vr Zs Zr OST condition : I =( Vs - Vr )/ ZT =( Vs - ( - Vr ))/ ZT ~ 2 Vn / ZT ZT = Zs + Zline + Zr Power Oscillations – Definition (3) • Out of step condition • Occurs when two internal voltages of equivalent sources are in opposite direction • At that point the phase (swing) current is maximum • The position of the electrical centre will depend on Zs/Zr ratio • Recoverable swings • Two voltages typically oscillate between up to 120deg

  6. Power Oscillations – Definition (4) • Elliptic shape: recoverable swing • Circle: OST condition

  7. Power Oscillations – Definition (5) Recoverable Non-Recoverable

  8. Traditional Out of Step Detection Methods

  9. Disadvantages • Conventional methods: • Conventional methods use blinders to determine speed of impedance crossing the ∆R region (R6-R5). They may predict or detect OST condition. • If polarity of ‘R’ has changed on exiting Z5, it is Out of Step condition (already happened) • If positive sequence impedance crosses ∆Z region faster than ‘delta T’ set time the predictive OST is declared • Disadvantages • Difficulties to set blinders due to heavy loading • Setting dependant on system topology, thus settings may be inaccurate • Comprehensive system study required – increases the engineering time • Prone to unstable operation in series compensated lines during MOV operation

  10. New Algorithm • New algorithm provides: • Setting free OST detection • CB tripping at a favourable angle

  11. New Algorithm - Principle Setting Free OST Detection Principle

  12. Setting Free OST Detection – Principle (1) • OST detection principle: • Recoverable swings: ∆R changes polarity when ∆I changes polarity • Non- recoverable swings: ∆R doesn’t change polarity when ∆I changes polarity

  13. Recoverable Swings Delta I and Delta R change polarity around same time Pole Slips When Delta I changes polarity , Delta R does not Setting Free OST Detection – Principle (2) Recoverable Swing Pole Slip

  14. Tripping Angle Control Circuit breaker tripping angle control

  15. Vs 0 Vr 90 ° ° 90 ° 270 ° 180 (minimum Z) ° 180 90 ° ° 270 ° Electrical Centre locus Vr locus 180 ° 270 ° Current Locus (I) X Tripping Angle Control • Current locus during oscillation is a circle • Drawing taken from Westinghouse book

  16. Tripping Angle Control (1) Current during oscillation can be defined as:I swing=IMAX sin (θ/2)where θ is the angle between internal voltages of sources

  17. Tripping Angle Control (2) • Maximum phase (swing) current is recorded at the point when ∆I changes polarity (that point corresponds to minimum impedance) • Favourable (safe) split angle entered, for example 240 degrees • Tripping command is issued when phase current drops to: I trip=IMAX sin (240/2)=0.866 IMAX

  18. Supporting Elements(1) Power Swing Detection and Blocking

  19. Supporting Elements(2)

  20. Supporting Elements(3)

  21. Proof of Concept • Pole slip COMTRADES captured by the relays for various system tests were used to prove that the basic principle was sound • Modifications were made to the original principle to make it more robust. • Logic implemented to account for difference between the frequency of I and V during swings • Logic to make the algorithms immune to system disturbances and faults

  22. Test Results (1) • Numerous cases from different systems were applied • Algorithm remains stable during power system faults or recoverable swings • Both, balanced and open pole oscillation tested • No mal-operation recorded during evolving faults, sudden change of power flow, cross country faults and frequency variations • Angle set tripping compared with actual angle across the breaker proved to be accurate

  23. Test Results (3)

  24. Test Results (4)

  25. Test Results (2)

  26. Conclusions

  27. Advantages • Setting free • All conventional methods require system studies and comprehensive settings • No blinders, no starters, thus no constraints on operating characteristics versus loading • Immune to topology changes • Security – Provides control over the angle at which the system is to be split. • Minimises chances of breaker opening at voltage maximum

  28. Thank You Questions?

More Related