Fieldbus Foundation Safety Instrumented Systems (FF-SIS) ____________________ Dave Glanzer Fieldbus Foundation Director of Technology Development. FF-SIS Scope. Extends FF Technology to Safety Instrumented Systems Based on the IEC 61508 International Standard.
E N D
Fieldbus Foundation • Safety Instrumented Systems • (FF-SIS) • ____________________ • Dave Glanzer • Fieldbus Foundation • Director of Technology Development
FF-SIS Scope • Extends FF Technology to Safety Instrumented Systems • Based on the IEC 61508 International Standard. • Example Application Areas: • Burner Management Systems • Fire & Gas • Fuel Engineering
International Development Team ABB AS Norway ABB Instrumentation Italy BIFFI Italy E.I. DuPont de Nemours, Inc. USA ExxonMobil Research & Engineering USE Emerson Process Management USA Flowserve USA HIMA Germany Honeywell SMS The Netherlands ice-PROS Canada Infraserv Höchst Technik GmbH & Co. KG Germany Invensys/Triconex USA Metso Automation Finland Rockwell Automation USA Rotork Control Systems UK Saudi Aramco Saudi Arabia Smar Brazil and Singapore Shell Global Solutions The Netherlands Softing AG Germany TÜV Germany Westlock Controls Corporation USA Yokogawa Electric Corporation Japan Yokogawa - SCE The Netherlands Yokogawa UK Limited UK
FF-SIS End User Requirements • Reduced Total Cost of Ownership for FF-SIS applications. • CAPEX • Hardware, Footprint, Commissioning, Power Consumption • OPEX • Advanced diagnostics, Reduced test interval via increased DCF. • SIL 2 and 3 applications • Password protected access to FF-SIS field devices • Additional Function Blocks (e.g. logic, 2 out of 3 voting) • Definable actions on diagnosed failures – trip, message • Handle discrete signals (e.g. switches, motor trips, lights, push buttons, etc.) where H1 dynamic performance is acceptable
FF-SIS End User Requirements • Total system approach • Total Asset Management – FF-SIS and Non-SIS • Modular Logic Solver –centralized and distributed option • Diagnostics • Hybrid system architecture – FF-SIS & traditional hardware • Guidance to manual proof test • Signalling/procedures for auto proof test • Awareness of opportunity-based proof test • Logging/documentation of results • Failure rate updates
FF-SIS Extension Areas • Communication • Meet IEC 61508 part 2 clause 7.4.8 Communication Diagnostics • User Application • Meet IEC 61508 part 3 clause 7.4.4 Function Block Diagnostics CRC on Device Description Files
FF-SIS Communication Extensions • Black Channel Approach • H1 Communication System (Black Channel) is unchanged. • A new FF-SIS protocol above the Black Channel detects network faults and appropriate action is taken without human intervention. New FF-SIS Communication Diagnostics IEC 61508 Black Channel IEC 61508
FF-SIS User Application Extensions • User Application • New Function Blocks for FF-SIS Applications – FBAP Part 6 • New FBAP diagnostics detect application faults and appropriate action is taken without human intervention. New FF-SIS Function Blocks & Function Block Diagnostics IEC 61508 Black Channel IEC 61508
FF-SIS User Application Extensions • Function Block Application Process – Part 6 • SIS Write Lock • SIS Discrete Input • SIS Analog Input • SIS Discrete Output • SIS Analog Voter • SIS Discrete Voter • SIS AND/OR/XOR FF-SIS Diagnostics and Statistics added to device Resource Block
Today’s Proprietary SIS Operation Engineering Proprietary Network SIS Logic Hardwired
Tomorrow’s Open FF-SIS Total Asset Management Operation Engineering Operation Engineering Proprietary Network HSE Ethernet Switch SIS Logic Linking Device Linking Device . . . . H1 H1 Hardwired Non-SIS FF Devices FF-SIS Devices
Example FF-SIS Application SIS_ WL SIS_ RB SIS_ AI SIS_ DO SIS_ WL SIS_ RB SIS_ AI SIS_ AVTR SIS_ DI SIS_ WL SIS_ RB SIS_ WL SIS_ RB SIS_ AI Write Lock S
Estop Example FF-SIS Application SIS_ WL SIS_ RB SIS_ DI SIS_ DO SIS_ LOGIC SIS_ WL SIS_ RB SIS_ DI SIS_ DVTR SIS_ DI SIS_ WL SIS_ RB SIS_ WL SIS_ RB SIS_ DI SIS_ WL SIS_ RB SIS_ DI PS PS PS Write Lock S
Target Schedule • 2002 • 4Q FF Board of Director Approval for SIS Project • 2003 • 1Q Project Kickoff Meeting • 2Q Architecture Completed • 3Q Draft Preliminary Specifications (DPS) Version 0.4 • 4Q TÜV Concept Approval for SIS 2004 • 1Q DPS Version 0.5 External Review • 2Q Release DPS Version 1.0 • 3Q Develop Lab Test Tools and Lab Prototypes • 4Q Begin Specification Validation Lab Testing @ Infraserve in Frankfurt 2005 – Release Final SIS Specifications and Final TÜV Type Approval 2006 – First Safety-Certified, FF-Registered Devices
USER LAYER DD – IEC 61804-2 USER LAYER DD – IEC 61804-2 FF-SIS IEC 61508 USER LAYER DD – IEC 61804-2 7 USER LAYER OSI Model IEC 61158 - FDA IEC 61158 - FMS 6 7 APPLICATION LAYER 5 6 PRESENTATION LAYER COMMUNICATION STACK COMMUNICATION STACK SESSION LAYER 5 4 IETF TCP/UDP TRANSPORT LAYER 4 IETF IP 3 3 NETWORK LAYER IEEE 802.3 MAC 2 2 IEC 61158 - DLL DATA LINK LAYER IEEE 802.3u @ 100 Mbit/s PHYSICAL LAYER IEC 61158 @ 31.25 kbit/s 1 1 PHYSICAL LAYER PHYSICAL LAYER H1/HSE HSE H1 FF-SIS – New Kid on the Block