SMF Fractional HP Manual Motor Starter Page 6/3 to 6/4. SMF Fractional Motor Starters. Class SMF Fractional HP Starters are provided with Melting Alloy Overloads, and the used on AC single-phase motors up to 1 HP.Manual Starters are used when the motor is in sight of the controller (Guideline @ 50ft.)Applications: Fans, conveyors, pumps and small machine tools. .
E N D
3. SMF Fractional Motor Starters Class SMF Fractional HP Starters are provided with Melting Alloy Overloads, and the used on AC single-phase motors up to 1 HP.
Manual Starters are used when the motor is in sight of the controller (Guideline @ 50ft.)
Applications: Fans, conveyors, pumps and small machine tools.
4. Fractional Horsepower Manual Starters Product Class SMF:
Open Type
NEMA Type 1B General Purpose Flush Mounting (No Enclosure Provided)
NEMA Type 1 General Purpose Enclosure, Surface Mounting.
NEMA Type 3R, 4, & 12
5. SMF Fractional Horsepower Manual Motor Starters
7. MMS & MRS Manual Switches Class MMS & MRS Fractional HP Switches provide ON-OFF control where overload protection is not required.
These switches are rated for use on 3-phase motors up to 10 HP @ 460V.
Manual Switches are used when the motor is in sight of the controller (Guideline @ 50ft.)
Applications: Fans, conveyors, pumps and small machine tools.
8. Fractional Manual Switches Product Class MMS & MRS:
Open Type
NEMA Type 1B General Purpose Flush Mounting (No Enclosure Provided)
NEMA Type 1 General Purpose Enclosure, Surface Mounting.
NEMA Type 3R, 4, & 12
9. MMS & MRS Fractional Horsepower Switches
11. Manual Starters & Switches Product Class 11 Family:
Open Type 3RV
NEMA Type 1
NEMA Type 7 & 9
Class I Flammable gasses may ignite Group C & D list of chemicals
Class II Combustible dust Group E, F & G list of metals, carbons, grain
NEMA Type 3 & 4, NEMA Type 7 & 9
12. Manual Starters & Switches
13. Manual Starters & Switches
14. Manual Starters & Switches
15. Manual Starters & Switches Across the line provide local control only.
1Ø, 2Ø or 3Ø up to 15HP @ 460 V
Ambient compensation Bimetal prevents nuisance tripping
Built-in Phase loss trip, protects Motors
Can be used for Type E application (self-protected Combo Starter). Saves Money!
16. Manual Starters & Switches LVP low voltage protection optional. Reduces Potential injuries. Meets OSHA
ON/OFF handle lock out with visible trip indicator.
Prevents unauthorized entry
Short Circuit trip at 13 times FLA for rated current.
Test trip function.
UL listed CSA Certified, and CE
17. Product Nomenclature
18. Manual Starters & Switches Applications include:
Grinders
Power Saws
Conveyors
Fans
Pumps
Blowers
Machinery
19. Manual Starters & Switches Field Modifications
LVP mounted on the right
Shunt trip mounted on the right
Front Plug-in or side mounted Auxiliary Contacts
Pilot lights for NEMA 1 only
Red, Green or Amber, 24-600V
20. Manual Starters & Switches
21. Manual Starter
22. Open Contactors & Starters
23. Overload Relays
What is the Difference:
Between A Short Circuit & An Overload ?
24. Overload Relays What Is A Short Circuit?
An Extreme Amount Of Current Usually Caused By A Fault To Another Phase Or To Ground.
Fault Currents Can Exceed Several Thousand Amps For A Very Short Period Of Time Which Can Cause Very Extensive Equipment Damage. Fault Currents May Even Reach Up To 200,000 Amps On Some Systems.
25. Overload Relays What Is An Overload?
1. An Operating Condition Where The Load Current Exceeds Normal Operation.
2. A Motor That Is Overloaded May Draw 6 Times Its Normal Operating Current (Full Load Current).
3. An Overload For Even Several Minutes May Cause Severe Motor Damage.
26. Overload Relays What Are The Differences Between …
A Fuse Or A Circuit Breaker And An Overload Relay?
27. Overload Relays Short Circuit Protection Devices
Fuses - One Time Use Only
Magnetic Circuit Breakers - Reusable After Reset
Overload Protection Devices
Time Delay Fuses -One Time Use Only
Overload Relays - Able To Reset
Thermal Magnetic Circuit Breakers - Also Able To Reset
28. Overload Relays How Overload Relays Work
Monitors Over-current Condition On Motor Power Leads
Indirectly Thermal Type Overload Relay
Directly Magnetic or Electronic Type Overload Relay
Turns Off Control Circuit During Overload Condition
OL Relay NO Contact Turns Off Motor Starter Coil Circuit
29. Overload Relays
30. Bimetal Overload
31. Bimetal Temp Comp. OLR
32. Electronic OLR
33. Electronic OLR
34. OLR Class 10, 20, 30
35. Motor Starter Circuit
37. Enclosed NEMA StartersProduct Lines
39. Enclosed NEMA StartersNon-Combination Starter Products
40. Enclosed NEMA StartersNon-Combination Starter - Features and Benefits Heavy Duty Industrial Construction
Enclosure Types:
NEMA 1 Lift-Off Type “Clamshell” (Manufactured with TOX process)
NEMA 1, 4x, 7&9, 12 (field convertible to 3/3R) Hinged
Standard Width and Extra Wide Enclosures
Removable Door/Cover
Siemens offers ten NEMA Size Starters from Size 00 up to Size 8 rated 900HP 600V.
Siemens also offers three Heavy Duty Half-Size Starters in 1 ¾, 2 ½ & 3 ½ for Cost and Space Savings.
Overloads - ESP100 and Bimetal Ambient Compensated
Pilot Device Mounting Holes in enclosures
41. Enclosed NEMA StartersNon-Combination Starter - Features and Benefits Factory & Field Modifications Pages 6/71 to 6/87.
Control Power Transformer (CPT)
Pilot Devices
Control Relays
Control Fuses
Auxiliary Contacts
Meters (Hinged Enclosures Only)
Terminal Blocks
Etc…
42. Enclosed NEMA Starters Non-Combination Starter Nomenclature
43. Enclosed NEMA StartersNEC Requirement for Combination Starter
45. Enclosed NEMA Starters Combination Starter Products
46. Enclosed NEMA Starters Combination Starter Products
47. Enclosed NEMA Starters Combination Starter Products
48. Enclosed NEMA Starters Combination Starter Products
49. Enclosed NEMA Starters Combination Starter Products
50. Enclosed NEMA StartersCombination Starter - Features and Benefits Heavy Duty Industrial Construction
Manufactured with TOX process on Most Enclosures
Standard Width and Extra Wide Enclosures
Four Enclosure Types: NEMA 1, 4x, 7&9, 12 (field convertible to 3/3R and 4)
Removable Door
Disconnect Types are Field Convertible to Fusible Disconnects
100KA Amp Fault Protection with Class R Fuses to 600V or MCP (Mag Only) to 480V
Panel Pre-Drilled for 230V or 600V Fuses
51. Enclosed NEMA StartersCombination Starter - Features and Benefits Up to 900HP 600V - NEMA Size 8 with ESP100 Solid State Overload Relay
Half Size Starters for Cost and Space Savings
Overloads - ESP100 and Bimetal Ambient Compensated
White Mounting Panel Pre-Drilled for CPT, Relays, Primary Fuse Kit,
Pilot Device Mounting Holes in enclosures
52. Enclosed NEMA StartersCombination Starter - Features and Benefits Factory & Field Modifications
Control Power Transformer (CPT)
Pilot Devices
Control Relays
Control Fuses
Auxiliary Contacts
Meters
Terminal Blocks
Etc…
53. Enclosed NEMA Starters Combination Starter Nomenclature
54. Enclosed NEMA StartersApplications Pumps
Fans
Material Handling & Conveyor Systems
Machine Tools
HVAC Equipment
Compressors
Construction Projects
Used in Commercial and Industrial facilities
55. Enclosed NEMA StartersOptions/Modifications - Definitions Page 6/83 to 6/87 covers Factory Modifications that are added to the product, per sales order, at the Siemens factory or distribution Center.
Page 6/71 to 6/81covers Field Modifications that are added to the product by distributor/customer with standard catalog field mod kits. This applies to both pre and post installation of base product.
56. Enclosed NEMA StartersField Modification Kits
57. Enclosed NEMA StartersField Modification Kits
58. Enclosed NEMA Starters
59. Half Sizes
60. NEMA Sizes
61. NEMA Starter Family up to size 4
62. Open NEMA Starter
63. Open Starter Features
64. ESP100 Electronic OLR True phase loss protection
Overload trips within 3 seconds on phase loss, even on lightly loaded motors (60% of minimum dial setting)
Customer Benefit: Saves Motors!!!
Thermal overloads just can’t provide this degree of protection
65. Electronic OLR Heaterless Construction
No heaters to install, stock, or maintain
Customer Benefit:
Heaters require time and labor to install
66. ESP Self - Powered
Generates its own low voltage control power through the same sensors that read motor current
Customer Benefit:
Separate 120VAC control power is not required
67. ESP100 OLR Ambient Insensitive
Overload not affected by temperature, rated -30 °C to 70 °C
Customer Benefit:
No nuisance tripping on hot days. No open panel doors with fans blowing on controls.
68. ESP100 OLR 99% of heat generated by thermal overload removed
Customer Benefit:
Other electronic equipment in panel runs cooler, energy savings. More equipment could go into panel due to lower heat rise.
69. ESP100 OLR Energy Savings
Thermal overloads generate 9 to 24 watts per relay
Based on 10 watts per overload and $0.10 per kW/hr, ESP100 will save $7.88 per year in energy costs
This can really be significant if user has hundreds of starters!!!
70. ESP100 ORL Self protected from short circuits
Upon the event of a short circuit, the current transformers saturate before any damage is done to the overload
Customer Benefit:
No need to replace overload relay or heater elements after a short circuit as is required with thermal overloads
71. ESP100 OLR ± 2 % repeat accuracy
Customer Benefit:
Under the same conditions, trip time on the overload will be the same within ± 2%
72. ESP100 OLR Circuit boards have conformal coating on them.
Customer Benefit:
Rugged design that will hold up in humid, corrosive environments
73. ESP100 OLR No two labels are the same
Every ESP100 overload is individually calibrated and a custom label is printed for that overload.
Customer Benefit:
Superior accuracy of dial setting - no competitor does this!
74. ESP100 OLR Thermal Memory
“Remembers” the heat buildup in hot or overloaded motors
Customer Benefit:
Trips faster on a restart since the motor windings are hot
75. ESP100 OLR Simple Installation
Mount it, wire it, dial in FLA
Customer Benefit
Fewer connections, saves installation time
76. ESP100 OLR Retrofit Capabilities
Direct Replacement for:
Cutler Hammer Citation Line and Freedom Series
GE 300 Line
Square D Type S
An additional “piggy-back” plate is available to retrofit the following:
Allen Bradley Bulletin 509 and Bulletin 709
Westinghouse Series A200
77. ESP100 OLR
78. Starters with ESP100 Family
79. Auxiliary Contact.
80. Applications Machine tools
Material Handling
Compressors
Hoists
Automotives
Industrial Equipment
81. Starters Kits (for use with ESP100 only)
82. Starters Kits – Customer Benefits Reduced lead-time – From Days to Minutes
Reduce Inventory – Instead of stocking scores of different starters, simply stock a few starter kits, ESP100 kits and coil kits. With these basic “building blocks” you virtually have hundreds of products on-hand.
Quality – Same high quality you are accustomed to with our products found in these new starter kits.
UL Listed - By correctly following the instructions included with the kits, the product you build is UL Listed.
Standard 110-120/220-240VAC dual voltage coil - Standard dual voltage coil, easily swapped with different voltage coil if required.
Available in Non-Reversing sizes 00-4 and reversing sizes 0-2
83. Product Lines Class 14 Non-Reversing starters
From fractional HP up to 900 HP (NEMA size 00 – 8 including half-sizes)
Operating voltages up to 575 V
Overloads - ESP100 and Bimetal Ambient Compensated
Class 22 Reversing starters
From fractional HP up to 900 HP (NEMA size 00 – 8 including half-sizes)
Operating voltages up to 575 V
Overloads - ESP100 and Bimetal Ambient Compensated
84. Product Lines Class 30 Two Speed
One and Two Windings
Constant or Variable Torque
Constant Horsepower
From fractional HP up to 100 HP (NEMA size 0 – 4 including half-sizes)
Operating voltages up to 575 V
Overloads - ESP100 and Bimetal Ambient Compensated
Class 40 (Non-Reversing) & 43 (Reversing) Contactors
From fractional HP up to 900 HP (NEMA size 00 – 8 including half-sizes)
Operating voltages up to 575 V
Vacuum contactors NEMA sizes 4,5 & 6 (Non-Reversing only)
85. Nomenclature
86. FLA 3Ø AC Motors
87. Select Heater Select Heater for the following BiMetal Overload Relays Class 10 & 20. From the table in the catalog
14CP32A*81 SZ0, FLA 4.8, 460V
14GP32A*81 SZ2½, FLA 54, 230V
14DP12A*81 SZ1, FLA 20, 115V
3ø, 10HP, 460V, 60Hz, 3Pole
1ø, 2HP, 115V, 60Hz, 2Pole
88. Heater Elements Catalog # CL10 CL20
14CP32A*81 K36 E46
14GP32A*81 K77 E78
14DP12A*81 K60 E61
14DP32A*81 K56 E57
14DP12A*81 K62 E65
90. Lighting ContactorProduct Lines
91. Lighting Contactor Non-Combination
92. Lighting Contactor Combination
93. Lighting Contactor Features and Benefits Compact Design
Enclosure Types:
NEMA 1 Lift-Off Type “Clamshell” (Manufactured with TOX process)
NEMA 1, 4x, 12 (field convertible to 3/3R) Hinged
Standard Width and Extra Wide Enclosures
Removable Door/Cover
Up to 400Amps (20 – 60 available up to 12 poles, 100 – 400Amps 3 poles)
Available in Combination form with choice of:
Fusible Disconnect
Non-Fusible Disconnect
Circuit Breaker
Pilot Device Mounting Holes in enclosures
94. Lighting Contactor Non-Combination Starter - Features and Benefits Factory & Field Modifications
Control Power Transformer (CPT)
Pilot Devices
Control Relays
Control Fuses
Auxiliary Contacts
Terminal Blocks
Control Modules
Etc…
95. Lighting Contactor Electrically Held Nomenclature
96. Lighting Contactor Mechanically & Magnetically Held Nomenclature
97. Lighting Contactor Field Modification Kits
98. Lighting Contactor Field Modification Kits
99. Lighting and Heating Contactors
100. (CPTs)