Complex Power • Designate as S • Magnitude of S = Apparent Power • Units are Volt-Amperes • The complex sum of Real Power (P) and Reactive Power (Q) ECE 201 Circuit Theory I
Graphical Interpretation of SPower Triangle ECE 201 Circuit Theory I
Summary ECE 201 Circuit Theory I
Summary -- 2 Apparent Power – the volt-amp capacity required to supply P Q = Power exchanged between source and load P = Useful Output from the device being powered (Watts) ECE 201 Circuit Theory I
Summary -- 3 If the power factor angle is = 0, Apparent Power = Average Power (and Reactive Power = 0). ECE 201 Circuit Theory I
Example 10.4 Calculating Complex Power • An electrical load operates at 240 V rms. The load absorbs an average power of 8 kW at a lagging power factor of 0.8. • Calculate the complex power of the load. • Calculate the impedance of the load. ECE 201 Circuit Theory I
The power factor is “Lagging”, so we have an inductive load. The Reactive Power, Q, is Positive. ECE 201 Circuit Theory I