Complex Algebra and Load Power EE341 Ali Keyhani Circuit Theory Lecture #3
Complex Numbers i b b a a 0 0 r r A complex number is a quantity of the form of (1) Where a and b are real numbers, and a: real part b: imaginary part is called the conjugate of z
Complex Numbers A complex number can also be written in phasor form: (2) (3) (4) where - Modulus (or norm) - Argument (or phase)
Complex Numbers b a 0 r Conversion between two forms: i (5) (6) (8) (7)
Complex Numbers Operation Addition / Subtraction: (9) Multiplication: (10) (11) A complex number times its conjugate the square of its modulus.
Complex Numbers Operation Division: (12) Addition and subtraction can be easily done in regular form. While multiplication and division are a little bit complicated.
Complex Numbers Operation Multiplication: (13) Division: (14) Multiplication and division are much easier to be done in phasor form.
Electric Power For DC circuit: (15) For single-phase AC circuit: (16) Let Impedance angle So (17)
Electric Power Since We have (18) (19) For three-phase AC circuit: (20)
Electric Power For AC circuit: (21) Complex power: VA, kVA, MVA Active power: W, kW, MW Reactive power: Var, kVar, MVar (22) (24) (23) (25)
Power Factor Power factor is defined as: (26) Lagging: Q > 0, > 0, inductive Leading: Q < 0, < 0, capacitive
Electric Load Example 1 Consider a three-phase 480V, 300kVA load with p.f. = 0.9 lagging, what is the active, reactive, and complex power of the load? Solution: Known: To compute: P, Q, from S lagging
Electric Load Example 1 According to eqn (24), According to eqn (25), Q > 0 because p.f. is lagging.
Electric Load Example 2 Consider a three-phase 480V,240kW load with pf = 0.8 lagging, what is the active, reactive, and complex power of the load? Solution: Known: To be compute:Q, S from P lagging
Electric Load Example 2 According to eqn (24), According to eqn (25), Q > 0 because p.f. is lagging.
Electric Load Example 3 Consider a three-phase 480V,180kVA load with pf = 0.0 leading, what is the active, reactive, and complex power of the load? Solution: Known: Compute be:P, Q, from S leading
Electric Load Example 3 According to eqn (24), According to eqn (25), Q < 0 because p.f. is leading.