Modeling of HVAC System for Controls Optimization Using Modelica

Modeling of HVAC System for Controls Optimization Using Modelica. Wangda Zuo 1 , Michael Wetter 2 1 Department of Civil, Architectural and Environmental Engineering, University of Miami, Coral Gables, FL 2 Building Technology and Urban Systems Department,

clover
Download Presentation

Modeling of HVAC System for Controls Optimization Using Modelica

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Modeling of HVAC System for Controls Optimization Using Modelica Wangda Zuo1, Michael Wetter2 1 Department of Civil, Architectural and Environmental Engineering, University of Miami, Coral Gables, FL 2 Building Technology and Urban Systems Department, Lawrence Berkeley National Laboratory, Berkeley, CA Intelligent Building Operations Workshop 06/21/2013

  2. Outline Introduction Case 1: Modeling a Direct Expansion Coil Case 2: Optimization of Chiller Plant Control for Data Center Conclusion and Outlook 2

  3. Introduction • Motivation • Energy saving potential from better building control is about 30% • Computer tools can be used for the design, evaluation and optimization of HVAC control • Limitation of Current Tools • Idealized control • Time step too large • Fixed time step • Opportunity with Modelica • Equation-based object-oriented modular modeling • Fixed and variable time step solvers 3

  4. Case 1: Modeling of a DX Coli North Wing of Building 101, Philadelphia, PA DX Coil with 2 Condensing Units 4

  5. Measured Data Measured Power for August 2012

  6. Model Calibration Design Using measured data to calibrate the nominal COPs for performance curves of 6 stages so that calculated energy consumption is close to measured data.

  7. Calibration Model Measured Data Tout [degC] Power [W] Energy [J] 0.3% difference Variable Speed DX coil, 8/1-8/7/2012

  8. Validation Model Measured Data Tout [degC] Power [W] Energy [J] 4% difference Variable speed DX Coil, 8/15-8/21/2012

  9. Discrete vs. Continuous Time Control • Option 1: Variable Speed DX Coil • Control input: Real from 0 to 1 • Coil runs smoothly using performance curves for 6 speeds • Option 2: 6 Stage DX Coil • Control input: Integer from 0 to 6 • A time delay twai is used to prevent short cycling

  10. Discrete vs. Continuous Time Control Model Measured Data Tout Variable Speed DX Coil (Continuous) 6-Stage DX Coil, twai=120s (Discrete) 6-Stage DX Coil, twai=1s (Discrete) Simulation of 8/1-8/7/2012

  11. Discrete vs. Continuous Time Control Comparison of Numerical Performance Simulation of 8/1-8/7/2012

  12. Outline Introduction Case 1: Modeling of a Direct Expansion Coil Case 2: Optimization of Chiller Plant Control for Data Center Conclusion and Outlook 12

  13. Case 2: Chiller Plant for Data Center Cooling • Background: • 1.5 percent of the nation’s electricity. • halfof the electricity in data centers is used for cooling. Objective: Decrease Power Usage Effectiveness (PUE): PUE= Challenges in Optimization:

  14. Configurations Condenser Water Pump WSE Tchi,max Chilled Water Pump Fan Tair,set 14

  15. Modelica Models of Chiller Plant with WSE 15

  16. Setpoint Reset Control Chilled Water Loop Difference Pressure and Chiller Setpoint Temperature Reset Modelica Implementation 16

  17. Water Side Economizer Control Schematic of State Graph Modelica Implementation 17

  18. Results: With and Without WSE • How much does the 0.13 in PUE for a 500 kW data center mean? • 438,000 kWh / year • $87,600 if $0.2 / kWh 18

  19. Results: With and Without WSE Without WSE With WSE 19

  20. System With WSE: Hours of Chiller Operation Tair,set 18C 27C Tchi,max 6C 22C 20

  21. System with WSE: Control Actions in a Hot Day June 30 21

  22. Discrete vs. Continuous Time Control Discrete Time Control (Trim and Response Logic) Continuous Time Control (PI Control) 22

  23. Discrete vs. Continuous Time Control Comparison of Numerical Performance 23

  24. Outline Introduction Case 1: Modeling of a Direct Expansion Coil Case 2: Optimization of Chiller Plant Control for Data Center Conclusion and Outlook 24

  25. Conclusion and Challenges Conclusion The case studies demonstrate the potential of Modelica for the modeling and optimization of HVAC system control Model performance varies depending on how it is constructed Challenges How to ensure that the models can be stably and efficientlysolved? How to handle the fast transient in control system and slow response in building thermal system at the same time? 25

  26. Acknowledgements • Collaborators: • Purdue University: Donghum Kim, James Braun • EEB Hub: Ke Xu, Richard Sweetser, Tim Wagner • Funding Agencies: • Department of Energy • Energy Efficient Buildings Hub 26