300 likes | 411 Views
Members: Ryan Bigelow, MEEN Sr Adam Tallman, CVEN So Iris Hill, ISEN So Andrew Ingram, MEEL Fr Ricky Palacios, CHEL Fr Graduate Mentor: James Hardy, MEEN. STP Team End of Semester Report. Presentation Outline. Model Description Modeling Assumptions Model Validation Analytical Results
E N D
Members: Ryan Bigelow, MEEN Sr Adam Tallman, CVEN So Iris Hill, ISEN So Andrew Ingram, MEEL Fr Ricky Palacios, CHEL Fr Graduate Mentor: James Hardy, MEEN STP TeamEnd of Semester Report
Presentation Outline • Model Description • Modeling Assumptions • Model Validation • AnalyticalResults • Recommendations
Introduction • This semester attention was focused on simplifying the previous model, and expanding the model to the entire floor. • CFD efforts were focused on prioritizing techniques used to remove thermal energy from critical rooms on the floor.
Model Description • Model of floor 0 in SolidWorks • Floor 0 modeled as one part • Accurate dimensions per STP data • Each room contains: • A centrally located heat block that uses a specific heat generation rate provided by STP
Floor 0 Model Can we describe here each room where we have a heat source? How about showing the block where the heat source is applied? We need to describe here our modeling approach -what is included in our model ( all rooms and corridors? -where are the heat sources -are there any fans to bring in external air? Overall, this is a good picture to use to explain our modeling approach Penetration room Figure 1. “Floor 0” Model of EAB Building
CFD • Simulations were performed using various door and fan configurations to investigate the effect on room temperature. • A parametric analysis was carried out to determine the variables that had the greatest effect on room temperature. • Model assumptions were tested against results of the parametric analysis to produce a more accurate simulation.
ModelingAssumptions • Various assumptions were made in the following areas: • Adiabatic Wall Boundary Conditions • Heat Source Location and Size • Equipment Volumes • Fan Specifications
Boundary Conditions • Walls, Floor & Ceiling • Adiabatic walls (no heat loss through the internal/external walls, ceiling, and floors) • Frictionless walls • Penetration Room (adjacent to EAB room) • Ambient pressure & 68˚F
Heat Source Location and Size • Each heat source is modeled as a block that has a total surface area of 1 m2 on the five surfaces that have contact with the fluid • Each heat source is centrally located within each room
Last Year’s CFD Results • CFD model from last semester included thermal mass from equipment in SGR. • Time to reach critical temperature was found to be 22.5 minutes.
This Year’s Validation Run • The door lids were shut in the SGR and a 85700W heat load was applied to the room to mimic conditions of last semester’s model • This semester, CFD model did not include thermal mass from equipment. • Time to reach critical temperature was found to be 10.5 minutes
Analytical Verification of CFD Model • Switch Gear Room • Analytical Approach - Expected time to reach 104F • CFD Results - Time for model to reach tcrit: 10.5 min • Difference between CFD and analytical : 3%
Comparison of Results Spring 2009 Tc: 22.5 minutes Fall 2009 Tc: 10.5 minutes Percent Difference: 53%
CFD Analysis Case Descriptions • Case 1 – “Sealed Floor” Model. No air flow in from penetration room (PR) or flow out from stairwells. All internal doors open, no fans active. • Case 2 – “Sealed Floor” Model. No air flow in from PR or flow out from stairwells. All internal doors open, 6 fans with 6000CFM flow rate placed as per STP procedure. • Case 3 – Air flow is introduced into the EAB from the PR by assigning the PR lid a volumetric flow rate of 6000CFM. All internal doors open, 6 fans with 6000CFM flow rate placed as per STP procedure. • Case 4 – Air flow is introduced into the EAB from the PR by assigning the PR lid a ambient pressure, 68°F boundary. A 6000CFM fan was placed directly in front of lid to provide flow. All internal doors open, 6 fans with 6000CFM flow rate placed as per STP procedure. • Case 5 – Same as Case 4 with additional 6000CFM fan added at Switchgear Room (SGR) doorway. Fan blows air from hallway into SGR. • Case 6 – Same as Case 5, all fans now have 15,000CFM flow rates. • Case 7 – Same as Case 6, additional 15,000CFM fan added to SGR at other doorway. Fan blows air from SGR to hallway.
Sealed Floor SimulationsCases 1 & 2 • Initial conditions: All air is at initial temperature of 64°F • No penetration room air flow in • Case 1 – no fans • Case 2 – six identical fans (6000CFM) placed in model as shown on right.
Sealed Floor Simulations • Case 1- Time to reach 104°F (average room) with no forced circulation (no fans): 8.22 minutes • Case 2- Time to Reach 104°F with six fans configured as per STP procedure: 8.62 minutes • 5% Difference
Critical Rooms • Case 2- ( with fans) From the sealed heat up analysis, the following rooms showed fastest temperature rise SGR heated up 60% faster than any other room
Cases 3 & 4Introducing Flow From Penetration Room Case 3 - Air flow from penetration room was modeled in two ways. A specified volume flow rate boundary condition was established at the lid as seen in figure below. Fan placed in front of lid Time to reach 104°F: 8.66 min Case 4 - In second method, lid was assigned ambient pressure and temperature (68°F). A fan was placed directly in front of the lid. Differences were negligible. Second method was used in subsequent tests. Volume flow rate assigned to lid Time to reach 104°F: 8.60 min
Case 4 - Results • Introducing flow from the penetration room did not have great effect on the heat up rate. • Time to reach 104°F with no PR flow: 8.62 min • Time to reach 104°F with PR flow: 8.60 min • 8.60 minutes is the estimated time to reach critical temperature with current “Loss of EAB HVAC Response Improvements” document procedures. • It was found that there was minimal air exchange in the SGR
Case 5 - Adding a Fan to SGR • Although not in the current procedure, the team investigated adding a fan to the entrance of the SGR. It was found that the heat up rate was decreased by approximately 15% • Time to 104°F without fan in front of SGR: 8.66 min • Time to 104°F with fan in front of SGR: 10.05 min • Strong correlation was found between air velocity and fluid temperature
Case 6 - Increasing Fan size Case 6 investigated increasing all fan sizes to 15,000 cfm Case 5 - Time to reach 104°F with 6,000 cfm fan: 10.05 min Case 6 - Time to reach 104°F with 15,000 cfm fan: 10.37 min Increasing fan size reduced heat up rate by 3% Velocity profile of EAB floor with 15,000 cfm fan
Case 7 - Adding Second Fan to SGR • A second fan was added that pulled air from SGR. • Time to 104°F fan in front of SGR: 10.37 min • Time to 104°F with fan in front and at exit of SGR: 11.12 min • Time to reach critical temperature was increased by 7%
Case 7: Results Figure on left shows velocity profile with all fans set to 15,000 cfm. Figure on right shows an additional fan added to draw air from switchgear room.
Conclusions • Current fan placement by STP procedure had minimal effect on SGR heat up rate. • Addition of fans to Switch Gear Room produced greatest effect on heat up rate of critical rooms. • Modeling approach is very conservative. However results can be used to update the safety procedures.
Future Work • Future work will focus on improving the accuracy of the model • Evaluate more case studies • Conduct further sensitivity analyses on parameters • Add thermal mass to the rooms. • Accurate equipment volumes and weights are needed
Special Thanks • Matt King, STP • Mrs. Lagoudas, SEI • Ernie Kee, STP