20 likes | 306 Views
“Annex A”. DETAILS OF PANEL BOARDS. SPECIFICATIONS:. All Panel enclosures shall be made Ga.#16 B.I. sheet dip phospating process For free standing braces shall be made of Ga. # 14 B.I. sheet
E N D
“Annex A” DETAILS OF PANEL BOARDS SPECIFICATIONS: • All Panel enclosures shall be made Ga.#16 B.I. sheet dip phospating process • For free standing braces shall be made of Ga. # 14 B.I. sheet • All Circuit Breakers shall be Molded Case Circuit Breakers, UL Listed and shall be product of only one electrical manufacturer • The Main distribution Panel Board shall be stand alone MAIN DISTRIBUTION PANEL BOARD (MDP) SUB DISTRIBUTION PANEL (DP-2A) 800 AT/1200 AF 240V, 42 KAIC, 3Ø 200 AT/250 AF 240V, 22 KAIC, 3Ø A B C A B C 3 X 250 mm² Terminal Lugs per Pole Copper Busbar rated not less than 1200 Amps. per Pole Copper Busbar rated not less than 250 Amps. per Pole 60 AT, 3Ø 240V, 18 KAIC 60 AT, 3Ø 240V, 18 KAIC 200 AT, 3Ø 240V, 22 KAIC 150 AT, 3Ø 240V, 22 KAIC 125 AT, 3Ø 240V, 22 KAIC 125 AT, 3Ø 240V, 22 KAIC 60, AT, 3Ø 240V, 18 KAIC 60 AT, 3Ø 240V, 18 KAIC 60, AT, 3Ø 240V, 18 KAIC 100 AT, 3Ø 240V, 22 KAIC 60 AT, 3Ø 240V, 18 KAIC 125 AT, 3Ø 240V, 22 KAIC 40, AT, 1Ø 240V, 10 KAIC 40 AT, 1Ø 240V, 10 KAIC 100 AT, 3Ø 240V, 22 KAIC 100 AT, 3Ø 240V, 22 KAIC Certified correct: Approved by: Prepared by: SUPPLY AND INSTALLATION OF PANEL BOARDS AND FEEDERS FOR THE ELECTRICAL LOAD GROWTH AT BIR-NOB GEALDINA E. REYES Assistant Commissioner Administrative Service RODOLFO D. AURENCIO Chief, Building & Facilities Maintenance Section BOBBY U. LABAJO Chief, General Services Div.
SUB DISTRIBUTION PANEL (DP-5) SUB DISTRIBUTION PANEL (DP-2B) 125 AT/150 AF 240V, 22 KAIC, 3Ø 125 AT/150 AF 240V, 22 KAIC, 3Ø A B C A B C Copper Busbar rated not less than 150 Amps. per Pole Copper Busbar Rated not less than 150 Amperes per Pole 40 AT, 1Ø 240V, 10 KAIC 40 AT, 1Ø 240V, 10 KAIC 60 AT, 3Ø 240V, 18 KAIC 60 AT, 3Ø 240V, 18 KAIC 40 AT, 1Ø 240V, 10 KAIC 40 AT, 1Ø 240V, 10 KAIC 40, AT, 1Ø 240V, 10 KAIC 40 AT, 1Ø 240V, 10 KAIC 30 AT, 1Ø 240V, 10 KAIC 40 AT, 1Ø 240V, 10 KAIC 40, AT, 1Ø 240V, 10 KAIC 40 AT, 1Ø 240V, 10 KAIC 30 AT, 1Ø 240V, 10 KAIC 30 AT, 1Ø 240V, 10 KAIC 30 AT, 1Ø 240V, 10 KAIC 30 AT, 1Ø 240V, 10 KAIC SUB DISTRIBUTION PANEL (DP-9) SUB DISTRIBUTION PANEL (DP-11) 125 AT/150 AF 240V, 22 KAIC, 3Ø 150 AT/150 AF 240V, 22 KAIC, 3Ø A B C A B C Copper Busbar Rated not less than 200 Amperes per pole Copper Busbar Rated not less than 150 Amperes per Pole 40 AT, 1Ø 240V, 10 KAIC 40 AT, 1Ø 240V, 10 KAIC 60 AT, 3Ø 240V, 18 KAIC 60 AT, 3Ø 240V, 18 KAIC 40 AT, 1Ø 240V, 10 KAIC 40 AT, 1Ø 240V, 10 KAIC 60 AT, 3Ø 240V, 18 KAIC 60, AT, 3Ø 240V, 18 KAIC 30 AT, 1Ø 240V, 10 KAIC 40 AT, 1Ø 240V, 10 KAIC 30 AT, 1Ø 240V, 10 KAIC 40, AT, 1Ø 240V, 10 KAIC 30 AT, 1Ø 240V, 10 KAIC 40 AT, 1Ø 240V, 10 KAIC 30 AT, 1Ø 240V, 10 KAIC 30 AT, 1Ø 240V, 10 KAIC Certified correct: Approved by: Prepared by: SUPPLY AND INSTALLATION OF PANEL BOARDS AND FEEDERS FOR THE ELECTRICAL LOAD GROWTH AT BIR-NOB GEALDINA E. REYES Assistant Commissioner Administrative Service RODOLFO D. AURENCIO Chief, Building & Facilities Maintenance Section BOBBY U. LABAJO Chief, General Services Div.