3nd Quarter 2014 VRL Report

3nd Quarter 2014 VRL Report. Gentry Tubbs gtubbs@spp.org. TEMP48_20358. Monitored Element- LONGWOO – OAK_PHEC 138 kV LN Contingent Element- SWSHREV XFR MIDI S 345/138 KV

Download Presentation

3nd Quarter 2014 VRL Report

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. 3nd Quarter 2014VRL Report Gentry Tubbsgtubbs@spp.org

  2. TEMP48_20358 • Monitored Element- LONGWOO – OAK_PHEC 138 kV LN • Contingent Element- SWSHREV XFR MIDI S 345/138 KV • Reason for Violating: Ongoing outage of xfmr; high load in area and a resource was offline, relieving resource was maxed out; it took some time to get into a good ramp range for unit to provide relief.

  3. NPPD NPPD Iowa OPPD MEC LES Missouri SECI KCPL WR West MPS East Colorado EDE AECI New Mexico SPA WFEC AECC/EES OKGE CSWS SPS SPS EES EES Arkansas T48 LONOAKSWSXFR Texas

  4. TEMP05_20411 • Monitored Element- Bell – KSCO3 69kV LN:230 • Contingent Element- SUMNER – OXFO 138kV LN: OXFO_SUMNER • Reason for Violating: Local issue; Local generation came offline and relieving generation was not fixing the issue; Local generation brought back on line.

  5. TEMP05_20411 • Monitored Element- Bell – KSCO3 69kV LN:230 • Contingent Element- SUMNER – OXFO 138kV LN: OXFO_SUMNER • Reason for Violating: One-day outage of 138kV line; generation able to control the constraint, but a low ramp rate and the unit not staying right on dispatch led to a lot of violations.

  6. Wyoming NPPD Iowa OPPD MEC LES Missouri SECI KCPL WR MPS Colorado EDE AECI T5 BELMILSUMOXF New Mexico SPA WFEC AECC/EES OKGE CSWS SPS EES Arkansas Texas

  7. SHAHAYKNOXFR • Monitored Element- South Hayes • Contingent Element- Knoll1 XFR • Reason for Violating: High load in NW Kansas/Hays area, violated until a local resource came online after noon and another came online around 16:00

  8. SHAHAYKNOXFR • Monitored Element- South Hayes • Contingent Element- Knoll1 XFR • Reason for Violating: High load in NW area; Unit shut down, effective limit was lower than SOL and we violated until load in the area dropped off.

  9. Wyoming NPPD Iowa OPPD MEC LES Missouri SHAHAYKNOXFR SECI KCPL WR MPS Colorado EDE AECI New Mexico SPA WFEC AECC/EES OKGE CSWS SPS EES Arkansas Texas

  10. TEMP50_20450 • Monitored Element- Ogalala – Brule 115kV • Contingent Element- Stegall 345/230 kV Xfmr • Reason for Violating: Planned outage of a Line; normal reconfigurations were not an option. TLR needed to control external impacts on the flowgate; low GSFs on SPP market resources contributed to needing to violate the flowgate up to 102% of the effective limit just to start dispatching down the primary Decrement unit. During the violations on 7/30, we ran out of dispatchable room and had to create a post-contingent load shed plan.

  11. Wyoming NPPD Iowa T50 OGABRUSTEXFR OPPD MEC LES Missouri SECI KCPL WR MPS Colorado EDE AECI New Mexico SPA WFEC AECC/EES OKGE CSWS SPS EES Arkansas Texas

  12. TEMP63_20466 • Monitored Element- Mustang – Denver 115kV C.1 • Contingent Element- Mustang – Denver 115kV C.2 • Reason for Violating: A CA requested more of a resource to be brought online after a unit tripped. The plant was operating with a high Eco Min due to testing for HE 15, and the others were dispatched to their Eco Min and we had no more room to move down on the resources.

  13. Wyoming NPPD Iowa OPPD MEC LES Missouri SECI KCPL WR MPS Colorado EDE AECI New Mexico SPA WFEC AECC/EES OKGE CSWS SPS EES Arkansas T63 MUSDENMUSDEN 13 Texas

  14. OSGCANBUSDEA • Monitored Element-OSAGE CANYON 115 kV • Contingent Element-BUSHLAND DEAFSMITH 230 kV • Reason for violating: We shut down two resources, and wind in north SPS increased as well; it took some time for RTBM to resolve the loading.

  15. OSGCANBUSDEA • Monitored Element-OSAGE CANYON 115 kV • Contingent Element-BUSHLAND DEAFSMITH 230 kV • Reason for violating: Ran out of room to move down on nearby Dec units; had room to move up on Inc units but prices at the time required a violation to 101% to get those units to move up

  16. OSGCANBUSDEA • Monitored Element-OSAGE CANYON 115 kV • Contingent Element-BUSHLAND DEAFSMITH 230 kV • Reason for Violating: Resource came offline very fast; took some time for RTBM to solve and more generation at another was brought on shortly after

  17. NPPD Iowa OPPD MEC LES Missouri SECI KCPL WR West MPS East Colorado EDE AECI New Mexico SPA WFEC AECC/EES OSGCANBUSDEA OKGE CSWS SPS SPS EES Arkansas Texas

  18. TEMP67_20472 • Monitored Element- Renfrow7 – RenfrowWF 138kV • Contingent Element- Hunters – Woodring 345kV • Reason for Violating: Ran out of room to move up on generation; low shift factors and other flowgates binding were competing for Incs/Decs coming across peak load. Nearby wind had very low offers, so prices did not get low enough to dispatch them down.

  19. TEMP67_20472 • Monitored Element- Renfrow7 – RenfrowWF 138kV • Contingent Element- Hunters – Woodring 345kV • Reason for Violating:Online generation maxed out; high wind at windfarm, forced outage on a line made Dec GSFs a little bit lower, making it more difficult for RTBM to solve the constraint; also, this flowgate was fighting with another flowgate as well.

  20. Wyoming NPPD Iowa OPPD MEC LES Missouri SECI KCPL WR MPS Colorado T67 RENRENHUNWOO EDE AECI New Mexico SPA WFEC AECC/EES OKGE CSWS SPS EES Arkansas 20 Texas

  21. TEMP09_20424 • Monitored Element- GORD 345/138 XFR: WICH_12 • Contingent Element- GORD 345/138 XFR: WICH_11 • Reason for Violating: Initially not much generation online in Wichita with high load, but generation came online to relieve that constraint, but it hurt Temp43 (which was also loading up due to increasing load and wind dropping in west Kansas). Temp43 violated until generation came online to support the load in the area

  22. TEMP09_20424 • Monitored Element- GORD 345/138 XFR: WICH_12 • Contingent Element- GORD 345/138 XFR: WICH_11 • Reason for Violating: Outage on 138kV line; all online local generation maxed out; generation brought online to resolve loading

  23. TEMP09_20424 • Monitored Element- GORD 345/138 XFR: WICH_12 • Contingent Element- GORD 345/138 XFR: WICH_11 • Reason for Violating: Ongoing outage of line and the return of another; high load in area; resource committed to relieve the loading

  24. Wyoming NPPD Iowa OPPD MEC LES Missouri SECI KCPL WR MPS Colorado T9 WICXFRWICXFR EDE AECI New Mexico SPA WFEC AECC/EES OKGE CSWS SPS EES Arkansas 24 Texas

  25. TEMP43_20311 • Monitored Element- RENO 345/1kV XF: 2P • Contingent Element- SUMM 345/15kV • Reason for Violating: Initially not much generation online in Wichita with high load, but generation came online to relieve that constraint, but it hurt Temp43 (which was also loading up due to increasing load and wind dropping in west Kansas). Temp43 violated until generation came online to support the load in the area

  26. Wyoming NPPD Iowa OPPD MEC LES Missouri SECI KCPL WR MPS T43 RENXFRSUMXFR Colorado EDE AECI New Mexico SPA WFEC AECC/EES OKGE CSWS SPS EES Arkansas 26 Texas

  27. TEMP22_2092 • Monitored Element- CRSW – KSCO4 69kV • Contingent Element- HAYS – PECK 69kV • Reason for Violating: Load pocket issue; generation is the only generation that can help this constraint, and they were not following the dispatch up, so the market couldn't drive them up high enough to relieve the loading.

  28. Wyoming NPPD Iowa OPPD MEC LES Missouri SECI KCPL WR MPS Colorado T22 CREROMPECHAY EDE AECI New Mexico SPA WFEC AECC/EES OKGE CSWS SPS EES Arkansas 28 Texas

  29. NORXFRNORXFR • Monitored Element- NOWST1 • Contingent Element- NOWST1 • Reason for Violating: Increasing load all the nearby Inc generation was already maxed out, no relief left available across afternoon peak

  30. NORXFRNORXFR • Monitored Element- NOWST1 • Contingent Element- NOWST1 • Reason for Violating: High/increasing load. Online generation in the city was already maxed out, nothing left to move up/down to relieve the flowgate

  31. NORXFRNORXFR • Monitored Element- NOWST1 • Contingent Element- NOWST1 • Reason for Violating: Approved derate of generation and resources already at max; other generation brought online, but still not enough generation with short enough lead times; directed wind farm to 0 to try to get relief, then came up with post-contingent load shed plan

  32. Wyoming NPPD Iowa OPPD MEC LES Missouri SECI KCPL WR MPS Colorado EDE AECI New Mexico SPA WFEC NORXFRNORXFR AECC/EES OKGE CSWS SPS EES Arkansas Texas

  33. TEMP119_20525 • Monitored Element- Tarby1 161/69kV • Contingent Element- AES5 – BONTP 161kV • Reason for Violating: Outage of 161kV line; this is an outlet for issue for generation. We initially violated the flowgate because unit was OOMEd (in preparation for the outage) and not dispatchable. Once we released the OOME, they did not follow dispatch or their ramp rate, so they were OOMEdagain.

  34. TEMP119_20525 • Monitored Element- Tarby1 161/69kV • Contingent Element- AES5 – BONTP 161kV • Reason for Violating: Outage of line; this is an outlet for issue for generation. Unit did not follow dispatch or their ramp rate, they had to be called to tell them to go down to resolve the loading.

  35. Wyoming NPPD Iowa OPPD MEC LES Missouri SECI KCPL WR MPS Colorado EDE AECI New Mexico SPA WFEC AECC/EES T119 TARXF2AESBON OKGE CSWS SPS EES Arkansas 35 Texas

  36. TEMP125_20532 • Monitored Element- Rose – El Paso 138kV • Contingent Element- Rose – Weaver 138kV • Reason for Violating: Ongoing outage of a line; no generation online in area. Units were committed to relieve the loading, but it took a while for load to drop and the constraint to be relieved.

  37. Wyoming NPPD Iowa OPPD MEC LES Missouri SECI KCPL WR MPS Colorado T125 ROSELPROSWEA EDE AECI New Mexico SPA WFEC AECC/EES OKGE CSWS SPS EES Arkansas 37 Texas

  38. TEMP127_20536 • Monitored Element- Seward – St. John 115kV • Contingent Element- Finney – Hitch 345 kV • Reason for Violating: Sharp increase in the area wind; wind farms limited themselves, which resolved most of the loading.

  39. Wyoming NPPD Iowa OPPD MEC LES Missouri SECI KCPL WR T127 SEWSTJFINHIT MPS Colorado EDE AECI New Mexico SPA WFEC AECC/EES OKGE CSWS SPS EES Arkansas 39 Texas