Electrical Safety in LVDC Distribution System. Pasi Salonen Researcher - Working towards Ph.D. degree Lappeenranta University of Technology Finland Electrical safety analysis focusing on human safety Contact voltage and touch current Indirect customer-end insulation faults

darci
Download Presentation

SALONEN–FI–RIFS2–1270

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Electrical Safety in LVDC Distribution System Pasi Salonen Researcher - Working towards Ph.D. degree Lappeenranta University of Technology Finland • Electrical safety analysis focusing on human safety • Contact voltage and touch current • Indirect customer-end insulation faults • Single and double fault situations SALONEN–FI–RIFS2–1270

  2. Electrical Safety in LVDC Distribution System • Low voltage direct current (LVDC) system • Low voltage directive (LVD) 2006/95/EC • Maximum allowed voltage 1500 VDC • Bipolar system with ± 750 VDC pole voltages • Neutral isolated system SALONEN–FI–RIFS2–1270

  3. Electrical Safety in LVDC Distribution System • Simulation environment • PSCAD based LVDC simulation model • 35 kVA transformer (Ddy) with two secondary outputs • ± 750 VDC network length 200 m, AXMK 4x35 mm2 cable • Two 10 kVA customers with 1-phase 230 VAC inverters • Installation cable length 25 m, MMJ 3x2.5 mm2 cable • PE circuit created with equivalent resistance against ground SALONEN–FI–RIFS2–1270

  4. Electrical Safety in LVDC Distribution System • Equivalent human impedance • Parameters for normal conditions Zhuman = Human total impedance, RP = human skin impedance, 500 Ω, CP = Human skin impedance, 1.5 μF, RI = Human internal impedance, 600 Ω. • Parameters for hard conditions R = Equivalent resistance, 250 Ω. SALONEN–FI–RIFS2–1270

  5. Electrical Safety in LVDC Distribution System • Indirect faults at customer-end • All galvanic parts (sinks etc.) are grounded • Human contact in parallel with PE-conductor RP = 500 Ω CP = 1.5 μF RI = 600 Ω SALONEN–FI–RIFS2–1270

  6. Electrical Safety in LVDC Distribution System • To ensure human safety during faults • Std. contact voltage limit for DC is 120 V • Contact current for DC (at 5 % risk) is 150 mA (1000 ms) • Std. contact voltage limit for AC is 50 V • Contact current for AC (at 5 % risk) is 40 mA (1000 ms) • LVDC system voltage and current are mixed values • AC limits should be used for LVDC system SALONEN–FI–RIFS2–1270

  7. Electrical Safety in LVDC Distribution System • Single fault • Normal condition • Results, RE=5 Ω • Ihuman = 1.9 mA • Uhuman = 1.2 V • Icircuit = 6.2 A • Results, RE=1 Ω • Ihuman = 2.6 mA • Uhuman = 1.6 V • Icircuit = 8.3 A U I SALONEN–FI–RIFS2–1270

  8. Electrical Safety in LVDC Distribution System • Single fault • Hard condition • Results, RE=1 Ω • Ihuman = 6.0 mA • Uhuman = 1.6 V • Icircuit = 8.4 A U I SALONEN–FI–RIFS2–1270

  9. Electrical Safety in LVDC Distribution System • Double fault • Normal condition • Results, RE=5 Ω • Ihuman = 19.0 mA • Uhuman = 27.0 V • Icircuit = 146.0 A • Results, RE=1 Ω • Ihuman = 37.0 mA • Uhuman = 54.0 V • Icircuit = 293.0 A U I SALONEN–FI–RIFS2–1270

  10. Electrical Safety in LVDC Distribution System • Double fault • Hard condition • Results, RE=1 Ω • Ihuman = 220.0 mA • Uhuman = 54.0 V • Icircuit = 293.0 A U I SALONEN–FI–RIFS2–1270

  11. Electrical Safety in LVDC Distribution System • Conclusions • Safety analysis made in PSCAD simulation environment • Single faults are not dangerous even at hard conditions • Double faults can introduce values above dangerous limits • Possibility of double fault is relatively small compared to single fault • Fault clearance always at first fault situation • Current restriction in converter decreases values • Current limiting to 140 AAC value in customer-end converter • Contact current and voltage value below dangerous limits • Future work • Analytical calculation of currents and voltages SALONEN–FI–RIFS2–1270

  12. Electrical Safety in LVDC Distribution System Thank you for your intrest! Questions? Pasi Salonen Researcher LUT Energy / Department of Electrical Engineering Lappeenranta University of Technology, Finland Email: pasi.salonen@lut.fi SALONEN–FI–RIFS2–1270