Consider a circuit with a source, a load, & appropriate meters.

Relationship between P, Q, & S. Consider a circuit with a source, a load, & appropriate meters. P and Q are positive, so the load absorbs both active and reactive power. The line current I lags behind E ab by an angle .

desma
Download Presentation

Consider a circuit with a source, a load, & appropriate meters.

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Relationship between P, Q, & S • Consider a circuit with a source, a load, & appropriate meters. • P and Q are positive, so the load absorbs both active and reactive power. The line current I lags behindEab by an angle . • Current I has two components Ip & Iq. Value Ip = P/E & Iq = Q/E • The apparent powerS = EI, from which I = S/E • The phasor diagram shows • S =apparent power [VA|:P =active power [W]:Q =reactive power [var] • The angle  = arctanIq / Ip = arctan Q/P Electro Mechanical System

  2. Power factor • The power factor of an ac device or circuit is the ratio of the active power P to the apparent power S. given by the equation: • power factor =P / S = EIP / EI = IP / I = cos  • Where: • P = active power delivered or absorbed by circuit or device [W] • S = apparent power of the circuit or device [VA] • Power factor is expressed as a simple number, or a percentage. • The power factor can never be greater than unity (or 100 percent). • The power factor of a resistor is 100 percent because the apparent power it draws is equal to the active power. • The power factor of an ideal coil having no resistance is zero, because it does not consume any active power. • The power factor of a circuit or device is simply a way of stating what fraction of its apparent power is real, or active, power. • In a single-phase circuit the power factor is also a measure of the phase angle  between the voltage and current • If we know the power factor, we can calculate the angle. The power factor is said to be lagging or leading. Electro Mechanical System

  3. Power triangle • Relationship S2 = P2 + Q2 is right-angle triangle, known as a power triangle. • Following rules apply: • Active power P absorbed by a circuit or device is considered to be positive and is drawn horizontally to the right • Active power P that is delivered by a circuit or device is considered to be negative and is drawn horizontally to left • Reactive power Q absorbed by a circuit or device is considered to be positive and is drawn vertically upwards • Reactive power Q that is delivered by a circuit or device is considered to be negative and is drawn vertically downwards • The concept of the power triangle is useful when solving ac circuits that comprise several active and reactive power components. Electro Mechanical System

  4. Sources and loads • A resistor and capacitor are connected to the source. • Capacitor acts as a reactive source. • A wattmeter connected into the circuit will give a positive reading P = Elp watts, but a varmeter will give a negative readingQ = EIq . • Source G delivers active power P but receives reactive power Q. • Two powers flowing in opposite directions over the same line. • An electrical outlet can act not only as an active or reactive source, but it may also behave as an active or reactive load. • It depends upon the type of device connected to the receptacle. Electro Mechanical System

  5. System with several loads • Consider, a group of loads connected in an unusual way to a 380 V source . • We wish to calculate the apparent power absorbed & current supplied by source. • We simply draw a block diagram of the individual loads, indicating the direction of active and reactive power flow • Add all the active powers in a circuit to obtain the total active power P. • We can add the reactive powers to obtain the total reactive power Q. • Total apparent power S is then found by: • Adding reactive powers, we assign a +ve value to those that are absorbed by the system and a –ve value to those that are generated (such as by a capacitor) Electro Mechanical System

  6. System with several loads • Similarly we assign a +ve value to active powers that are absorbed and –vevalue to those that are generated (by an alternator) • we cannot add the apparent powers to obtain the total apparent power S. Add them only if their power factors are same • Let us now solve the circuit : • 1. Active power absorbed by the system: • P = (2 + 8 + 14) = +24 kW • 2. Reactive power absorbed by the system: • Q1 = (5 + 7 + 8) = +20 kvar • 3. Reactive power supplied by the capacitors: • Q2 = (–9 –16) = – 25 kvar • 4. Net reactive power Q absorbed by the system: • Q = ( + 20 –25) = – 5 kvar Electro Mechanical System

  7. System with several loads • Apparent power of the system: • 6. Because the 380 V source furnishes the appaentpower, the line current is • I = S/E = 24 500/380 = 64.5 A • 7. The power factor of the system is • cosL = P/S= 24/24.5 = 0.979 (leading) • The 380 V source delivers 24 kW of active power, but it receives 5 kvar of reactive power. • This reactive power flows into the system of the electrical company, where it is available to create magnetic fields. • The magnetic fields may be associated with distribution transformers, transmission lines, relays etc. Electro Mechanical System

  8. System with several loads • Let us make power triangle for the system. • It is the graphical solution to our problem. • Starting with the 5 kvar load, we move from one device to the next around the system. • We draw the magnitude and direction (up, down, left, right) of each power vector. • At the end, we can draw a power vector from the starting point to the end point. • Vector having a value of 24.5 kVA. • The horizontal component of this vector has a value of 24 kW and, because it is directed to the right, we know that it represents power absorbed by the system. • The vertical component of 5 kvar is directed downward, so it represents reactive power generated by the system. Electro Mechanical System

  9. Reactive power without magnetic fields • Loads sometime absorb reactive power without creating any magnetic field at all. • This can happen in electronic power circuits when the current flow is delayed by means of a rapid switching device. • Consider, a circuit in which a 100 V, 60 Hz source is connected to a 10 Ω resistive load by means of a mechanical switch. • The switch opens and closes its contacts so that current only flows during the latter part of each half cycle. • This forced delay causes the current to lag behind the voltage. • If we connect a wattmeter and varmeter, they would read +500 W and + 318 var. • This corresponds to a lagging power factor (sometimes called displacement power factor) of 84.4 percent. • Reactive power is associated with the rapidly operating switch rather than with the resistor itself. Electro Mechanical System