1 / 6

Blondel Compliance

Blondel Compliance. Blondel Compliance. Update to IMO Wholesale Revenue Metering Standard V2.0 Section 4.3.3 - Considerations for non-Blondel Meter Installations a. 3 CT’s and 2 PT’s (phase-N) using 2.5 element meter b. 3 CT’s (delta connected) and 2 PT’s (phase-N) using 2 element meter

eagan
Download Presentation

Blondel Compliance

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Blondel Compliance

  2. Blondel Compliance • Update to IMO Wholesale Revenue Metering Standard V2.0 • Section 4.3.3 - Considerations for non-Blondel Meter Installations a. 3 CT’s and 2 PT’s (phase-N) using 2.5 element meter b. 3 CT’s (delta connected) and 2 PT’s (phase-N) using 2 element meter c. 2 CT’s and 3 PT’s (69V phase-N) using a 2 element meter d. 2 CT’s and 2 PT’s using 2 element meter where Neutral is not available • Section 4.4.1 - Registration of non-Blondel Meter Installations • At seal expiry, MI registered under 4.3.3b must be upgraded to 4.3.3a with a conforming 2.5 element Main meter that calculates the missing voltage and records the missing voltage (V2h) in channel 6 (ION Meter)

  3. Blondel Compliance • Section 4.3.2 - Compliance with Measurement Canada Rulings Existing installations shall comply with any future Measurement Canada rulings on two and one-half element metering (or two-element metering, using three delta connected current transformers and two voltage transformers connected phase to ground). As per Measurement Canada Bulletin E-24E (rev.1) dated 2002-11-29, “5.1 Effective April 1, 2003, all new and all reconstruction of existing 3- phase 4-wire wye configured metering installations shall use metering that is compliant to Blondel’s theorem such as 3-element metering. An example of a reconstructed metering installation may include service upgrades and, or instrument transformer replacement. Reconstruction of existing metering installation, sites that do not have sufficient physical space to accommodate the additional voltage transformer will not be required to meet 5.1 above”

  4. Blondel Compliance

  5. Blondel Compliance • In some cases, the Metering requirements may differ depending on the location of the Meter Installation • Within a facility (TS) • Grounded system requires 3 element metering. PT’s connected phase-neutral for 4 distribution system or phase-ground for 3 wire distribution system. • Ungrounded system requires 2 element metering* • Within a distribution system (outside of TS) • 4-Wire distribution requires 3 element metering - 27.6 kV Wye • 3-Wire distribution requires 2 element metering - 46 kV (Wye or Delta)

  6. Blondel Compliance • What happens when meter is not located at the defined Meter Point (feeder meter located outside of the TS)? • Meter Installation is 2 element but declared non-Blondel • Non-Blondel MEC’s apply • Do we need to simplify the metering requirements for NEW meter installations? • 3 element meter installation irregardless of the # of wires (3 or 4) or meter location. • Research industry practices and develop standard. • IMO and NRC to perform study on non-Blondel installations (2 element metering on a grounded system).

More Related