Leslee Shumway Olympic Pipeline Control Center Events. 3 PM. New Records Entered into SCADA Computer OLY02. 3:10. 3:17. Computer Error Messages Begin. Controller Begins to Change Delivery Points from Renton to Seattle. 3:18. 3:22. Computer Becomes Unresponsive.

elana
Download Presentation

Leslee Shumway Olympic Pipeline Control Center Events

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Leslee Shumway Olympic Pipeline Control Center Events

  2. 3 PM New Records Entered into SCADA Computer OLY02 3:10 3:17 Computer Error Messages Begin Controller Begins to Change Delivery Points from Renton to Seattle 3:18 3:22 Computer Becomes Unresponsive Pipeline Begins To Shut Down: Bayview Booster Pump Goes Down Timeline of Control Center Events 10 June 1999

  3. 3:28 3:27-3:34 Pipeline Rupture 3:23 SCADA Computer OLY01 On Line Allen Station Pump Shutdown Manually 3:24 3:35 SCADA Computer OLY02 Taken Off Line Controller Requests Arco Stop Product Flow Timeline of Control Center Events,continued

  4. 3:48 SCADA Computer OLY02 Operational After Records Deleted 4:04 4:11 SCADA Computer OLY01 Standby Operational Controller Begins Pipeline Restart 4:15 3:44 Olympic Requests ARCO Begin Product Flow SCADA Computer OLY02 On Line Timeline of Control Center Events,continued

  5. Bayview Pressure Trend Data

  6. 4:29 4:30 Leak Detection Alert Call from Arco Asking for Status 4:31 4:32 4:35 Telephone Call to Control Center Advising of Gasoline in Whatcom Creek Pipeline Shutdown Initiated Olympic Requests Arco Refinery Stop Product Flow 5:02 Fire Ignition Timeline of Control Center Events, Continued

  7. Computer Operations • The system administrator in the computer room had no formal SCADA training.

  8. The system administrator should have notified his supervisor and the controllers when computer error messages first appeared. • He should not have left the computer room until his supervisor became available.

  9. Computer Database Revisions • New records added to the primary on-line SCADA computer caused both computers to fail. • These SCADA database revisions were performed without prior testing.

  10. SCADA computer changes should be implemented and thoroughly tested on an off-line system.