An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Fouling Factor: After a period of operation the heat transfer surfaces for a heat exchanger become coated with various deposits present in flow systems, or the surfaces may become corroded as a result of the interaction between the fluids and the material used for construction of the heat exchanger. This coating represents an additional resistance to the heat flow, and thus results in decreased performance. This effect is called “fouling factor”, or “fouling resistance”, Rf. The economic disadvantages of fouling can be attributed to 1) Energy losses due to thermal inefficiencies. 2)Additional costs associated with periodic cleaning of heat exchangers. 3) Loss of production during shutdown for cleaning. 4) Higher capital cost through oversized units.

  2. Epstein has specified the following six categories of fouling: 1) Scaling fouling : the crystallization from solution of dissolved substance onto the heat transfer surface. 2) Particulate fouling: the accumulation of finely divided solids suspended in the process fluid onto the heat transfer surface. 3) Chemical reaction fouling: the deposit formation on the heat transfer surface by chemical reaction. 4) Corrosion fouling : the accumulation of corrosion on the heat transfer surface. 5) Biological fouling: the attachment of microorganisms to a heat transfer surface. 6) Solidification fouling : the crystallization of a pure liquid or one component from the liquid phase on a sub-cooled heat transfer surface. 1- Initial cost 2- Shut-down 4- Energy loss 3- Cleaning costs Disadvantages

  3. When a new heat exchanger is put into service, its performance decreases progressively as a result of the buildup of fouling resistance. The main factors affecting the rate of fouling on the heat transfer surface of a heat exchanger besides length of service, are: 1)The fluid velocity : an increase in the velocity decreases both the rate of deposit and the ultimate amount of deposit on the surface. 2) The fluid temperature : increasing the fluid bulk temperature increases both the rate of buildup of fouling and its ultimate stable level. Fouling factor must be included for both inner and outer pipe sides along with the other thermal resistances in order to determine the overall heat transfer coefficient U. Thus,

  4. Fouling Factors

  5. Example 3: Determine the overall heat transfer coefficient Uo and Uibased on the outer and inner surfaces, respectively, of a steel pipe (k = 54 W/m.K) with an inner diameter of di = 2.5 cm and an outer diameter of do = 3.34 cm for the following flow and fouling conditions: hi = 1800 W/m2.K , ho = 1250 W/m2.K , Rf,i= Rf,o = 0.00018 m2.K/W Data: steel pipe, di = 2.5 cm, do = 3.34 cm, k = 54 W/m.K , hi =1800 W/m2.K, ho = 1250 W/m2.K, Rf,i= Rf,o = 0.00018 m2.K/W Find: Uo, Ui

  6. Solution: UoAo = UiAi Uo= Ai x ( ri/ro ) = 487.3x(2.5/3.34) = 364.75 W/m2.K

  7. Example 4: Engine oil is to be cooled from 80 to 50oC by using a single-pass, counter-flow, concentric tube heat exchanger with cooling water available at 20oC. Water flows inside a thin tube with an inner diameter of 2.5 cm at a rate of 0.08 kg/s, and oil flows through the annulus at a rate of 0.16 kg/s. The heat transfer coefficients for the water side and oil side are 1000 W/m2.K and 80 W/m2.K, respectively. The fouling factors on the water and oil sides are the same and equal to 0.00018 m2.K/W. If the tube wall resistance is negligible, calculate the rate of heat flow, the outlet temperature of cooling water and the overall heat transfer coefficient. Take cp,w = 4180 J/kg.K and cp,oil =2090 J/kg.K.

  8. Data:single-pass, counter-flow, concentric-tube heat exchanger. For oil, Toil,i = 80oC , Toil,o = 50oC, moil = 0.16 kg/s, ho = 80 W/m2.K , Rf,i = 0.00018 m2.K/W ,cp,oil =2090 J/kg.K . For water, Tw,i= 20oC, mw = 0.08 kg/s, hi = 1000 W/m2.K, Rf,o = 0.00018 m2.K/W, cp,w = 4180 J/kg.K. For tube, di= do = 0.025 m. Find: , Tc,o , U Solution:The rate of heat flow and the outlet temperature of water can be calculated from an overall energy balance

  9. The temperature profiles for the hot and cold fluids are shown in the figure. It can be noted that the temperature difference between the hot and cold Fluids is constant (T = 30oC) throughout the heat exchanger. The reason is the equal capacity rates for the hot and cold fluids. i.e. The overall heat transfer coefficient U is determined from the following equation, by neglecting the thermal resistance of the tube:

  10. Calculation of the heat transfer coefficient (h): Laminar, hydrodynamic boundary layer development in a pipe Laminar, thermal boundary layer development in a constant surface temperature pipe

  11. Variation of the friction factor and the convection heat transfer coefficient in the flow direction for flow in a tube (Pr ˃ 1) for laminar flow of viscous fluids e.g. oils. (opposite gross of the boundary layers is the case for liquid metals when 1 ˃ Pr).Note that 1- for gases the two boundary layers coincide, i.e. Pr = 12- for turbulent flow the two boundary layers are about the same and independent of Pr.3-hx, fx remain constant in fully developed laminar and turbulent flow.

  12. Hyrodynamic fully developed region: Darcy equation for pressure drop: Power=V.xΔP Laminar flow:

  13. Moody Chart

  14. Thermal fully developed region: For constant wall temperature:For constant heat flux: Nusselt number for fully developed laminar flow in a circular pipe annulus with one surface insulated and the other at constant temperature . (do= outer diameter of the inner tube, Di= inner diameter of the outer tube)

  15. Nusselt number and friction factor for fully developed laminar flow in pipes of different cross sections

  16. Thermal entry length only:Turbulent flow: Correlation of Hausen: Fully developed turbulent flow in a smooth pipe: Combined entry length: Correlation of Sieder and Tate: Blasius correlations: Petukhov correlation:

  17. Chilton-Colburn analogy ( j – factor): Dittus – Boelter correlation:

  18. Variation of local Nusselt number along a tube in turbulent flow for both uniform surface temperature and uniform surface heat flux.- values - length - similarity - equations

  19. Flow across a single circular cylinder (tube): Whitaker correlation: Whitaker correlated the average heat transfer coefficient hm for the flow of gases or liquids across a single cylinder (tube) by The properties are to be evaluated at the mean film temperature Tf : In the range of variables

  20. Example 5: A perfect insulated concentric pipe heat exchanger is used to cool unused lubricating oil at a mean temperature of 77oC for a large industrial gas turbine engine using water at an average temperature of 32oC. The flow rate of cooling water through the inner pipe (di = 25 mm, do = 30 mm, k = 16 W/m.K) is 0.2 kg/s, while the flow rate of oil through the annulus (Di = 45 mm) is 0.1 kg/s. Assuming fully developed conditions for both water and oil and constant fluid properties, calculate the convection heat transfer film coefficients and the overall heat transfer coefficient (Uo). Data:Fully developed conditions.

  21. Find: hi , ho , Uo Solution: From tables of properties, For unused engine oil at For water at For water flow through the inner pipe, Accordingly, the flow is turbulent and Nusselt number may be computed from Dittus – Boelter correlation:

  22. For the flow of oil through the annulus, the hydraulic diameter is The Reynolds number is The annular flow is therefore laminar. Nusselt number may be obtained from the table for annular flow. With do /Di = 0.667, linear interpolation provides

  23. The overall heat transfer coefficient is then

  24. Example 6: Water at a mean temperature of Tm = 80oC and a mean velocity of um = 0.15 m/s flows inside a 2.5 cm inner diameter, thin –walled copper tube. Atmospheric air at T∞= 20o C and a velocity u∞=10 m/s flows across the tube. Neglecting the tube wall resistance, calculate the inner and outer heat transfer coefficients, the overall heat transfer coefficient and the rate of heat loss per unit length ( one meter) of the tube. Data:A single tube, cross-flow heat exchanger for waterTm = 80oC, um = 0.15 m/s, for airT∞= 20o C, u∞ =10 m/s for tubed = di = do = 0.025 m , L = 1 m.

  25. Find: Solution:The physical properties of water at Tm = 80oC are The Reynolds number for water flow is We use the Dittus–Boelter correlation to determine hi for water flow: , with n = 0.3 (cooling of water)

  26. The physical properties of air at Tf = 50oC are The Reynolds number for the air flow becomes The Nusselt number for cross-flow of air across a single circular tube is determined from the Whitaker correlation:

  27. The heat loss per unit length of tube is

  28. Free Convection on the Outer Surface of a Tube: The free convection heat transfer coefficient (ho) at the outer surface of a tube can be calculated from the following simplified expression: where, ho = outer heat transfer coefficient [W/m2.K], do= outer diameter of the tube, Tw = wall temperature, T∞ = ambient temperature.