An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. HVACR318 – Refrigeration II Charging Refrigerants

  2. Charging Defined • Charging a system is to add or replace refrigerant in a system. • Refrigerant is never used up. It either leaks out or it is contaminated by: • Water • Acid • Noncondensibles.

  3. Charging Refrigerants - Methods • Weighing • Using scales to check the amount added • Measuring • Using a dial-a-charge cylinder • Superheat and Subcooling • Most accurate • Combine with weighing in the charge. • Allow system to run for 10 minutes before taking readings.

  4. Charging Refrigerants - Methods • Sight Glass • Never used to check the charge • Not accurate • Varies based on system conditions • Amperage or Wattage • Not accurate at all • Do not use unless you have no other options.

  5. States of Refrigerant Charging • Refrigerant can be charged as a: • Vapor • Liquid

  6. Vapor Charging - Overview • Entails taking vapor refrigerant out of a refrigerant drum and putting it into the low side of the system. • If the system is not operating, you can add vapor to both the low and the high side of the system until the pressures equalize.

  7. Vapor Charging

  8. Vapor Charging • If the system is running, add vapor to the low side ONLY. • High side is under a higher pressure than the drum. • Opening the high side on a running system can put too much pressure on the refrigerant cylinders and cause them to explode.

  9. Vapor Charging

  10. Vapor Charging • In some cases, the refrigerant drum may be cold and cause it to have a lower pressure than the low side of the system. • Warm up the drum or the cylinder. • Warm water bath • Heater blanket

  11. Vapor Charging

  12. Vapor Charging - Advantages • Advantages • Easiest way of adding refrigerant to top off a running system. • Liquid refrigerant cannot enter the suction side of the compressor. Vapor is allowed.

  13. Vapor Charging - Disadvantages • Disadvantages • Slow process for adding large quantities of refrigerant. • High drum pressures can force oil out of the compressor. • Blended refrigerants may fractionate (or separate) as they are charged.

  14. Liquid Charging - Overview • Entails adding refrigerant in the liquid state into a system. • In a non-operating system, you can add liquid refrigerant through the king valve on the receiver. • King Valve = Service Valve.

  15. Liquid Charging • On an operating system you can front seat the king valve. • Jump out low pressure control • Be careful not to overcharge

  16. Liquid Charging

  17. Liquid Charging

  18. Liquid Charging • Liquid charging on an operating system through the low side: • Must be careful • Experienced technicians only • Flooding may result

  19. Liquid Charging • There are commercially available charging devices for charging liquid in the suction line; it acts like a metering device. • If the compressor becomes cold or frost starts to develop, stop charging with a liquid. Let it boil off.

  20. Liquid Charging - Advantages • Advantages: • Fast • Convenient (through low side)

  21. Liquid Charging - Disadvantages • Disadvantages • System may have to be turned off • Easy to overcharge

  22. Weighing Refrigerants - Overview • Usually accomplished using various scales: Dial, Electronic and Electronic Charging Scales. • Dial Scales • Can be difficult to use and inaccurate. • Set the charge on a dial and the scale shuts off when complete. • Not digital, and have faded from popularity.

  23. Weighing Refrigerants • Electronic Scales • Portable • Less Expensive • Accurate • You cannot walk away and allow charging to occur without youthere – must watch scale.

  24. Weighing Refrigerants • Electronic Charging Scales • Combination of electronic scale and old ‘dial-a-charge.’ • Accurate • Automatic

  25. Weighing Refrigerants

  26. Measuring Refrigerants - Overview • Graduated Cylinder • Dial-A-Charge • Put refrigerant into cylinder up to the line and then charge the system. • Not used much anymore, as they are not safe. • Tech must handle liquid refrigerant.

  27. Measuring Refrigerants

  28. Measuring Requirements

  29. Steps to Charge • Make sure system is in a vacuum and do not remove gauges. • Connect cylinder to the small center hose on the manifold. • Open refrigerant cylinder • Purge the air out of the center line.

  30. Steps to Charge 1 • Open the center manifold valve and allow the refrigerant into the charging manifold. • Decide on low or high side charging. • Place the cylinder onto the scale and zero the scale out. • Open the high or low side valve on the manifold and weigh the refrigerant in.

  31. Steps to Charge Diagram

  32. Steps to Charge 2 • While charging system, watch amperage of compressor. • If amperage goes above FLA (Full Load Amperage) shut off valve and wait for the amperage to stabilize and drop. • Never walk away from a unit while charging system.

  33. Steps to Charge Diagram

  34. Steps to Charge 3 • Once system is charged, check superheat and subcooling prior to removing the gauges. • Close all valves and remove the gauges. • Double check for leaks and clean up your work area. • Record the quantity of refrigerant you have added to the system.

  35. Steps to Charge 4 • Watch the difference in gauge pressure as you are charging. The gauges can be misleading.

  36. Troubleshooting • Low Charge: • Insufficient Cooling (low capacity) • Long Running Time • Continuous Running Time • High Operating Costs • Evaporator Icing Up • Superheat Higher than normal • Subcooling high

  37. Troubleshooting • Low Charge, cont’d • Low wattage • Volts x Amps • Suction pressure low, discharge pressure low. • Compressor temperature higher than normal.

  38. Troubleshooting • Overcharge • High suction pressure • High discharge pressure • Compressor sweating all over • Flooding - liquid in compressor • High wattage • Volts x Amps

  39. Troubleshooting • Overcharge, cont’d: • High current draw • Low or no superheat • Flooded evaporator • Liquid filled evaporator