1 / 15

High Voltage Insulation Diagnostics

High Voltage Insulation Diagnostics. WELCOME!. Presented by: Bostjan Flis bostjan.flis@metrel.si. Content overview. Application areas of HV insulation testing What influences insulation resistance Symptoms of bad insulation Testing methods

etana
Download Presentation

High Voltage Insulation Diagnostics

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. High Voltage Insulation Diagnostics WELCOME! Presented by: Bostjan Flis bostjan.flis@metrel.si

  2. Content overview • Application areas of HV insulation testing • What influences insulation resistance • Symptoms of bad insulation • Testing methods • Insulation testing with DC test voltage - insulation characteristics • Insulation testing with DC test voltage - test parameters • Limit values • Connection schemes • Test data evaluation i.e. statistics keeping • General requirements for HV insulation testers • Metrel HV insulation testers • Metrel's solution providing, services and development

  3. Application areas of HV insulation testing • Insulation resistance testing is part of predictive maintenance of: • Rotary machines (generators, motors) • Transformers (industry, utilities, power distribution) • Cables • Measuring transducers • Distribution boards • Benefits: • Lower TCO (total cost of ownership) • increased electrical safety • prevention against fire hazard

  4. What influences insulation resistance • Thermal exposure • Overload • Moisture • Electrical shocks • Mechanical shocks (vibrations, bad transportation) • Dirt (oil, dust, conductive materials) • General ageing of insulation Symptoms of bad insulation • Insulation breakdowns in a form of electrical short-circuits • Fire • Long-term downgrading values of insulation resistance • Insulation resistance values under by standards determined values

  5. Insulation testing methods • AC insulation testing (50/60Hz, 1 minute) • Insulation surge breakdown testing • Insulation testing with switching voltage • Insulation testing with DC voltage • Dielectric losses (tgδ) • Partial discharges • - U – I characteristics

  6. Insulation testing with DC test voltage- insulation characteristics

  7. Insulation parameters Polarisation Index (PI) PI = R tot (10 Min) / R tot (1Min) Dielectric absoption ratio (DAR) DAR = R tot (1 Min) / R tot (30 Sek) Dielectric discharge (DD) DD = I DIS (1 min) / (U * CISO ) I DIS ….a discharge current measured 1 minute after disconnecting the insulation system from the test voltage C ISO …. capacitance of the insulation system U …test voltage

  8. Limit values for insulation testing with DC voltage Insulation resistance Polarisationindex (PI) Thumb rule (motors and generators): Dielektric absorption ratio (DAR)

  9. Connection schemes • Precondition! • Measuring object has to be disconnected from power supply network (voltage – free) • Surface of the insulation system has to be dry and clean Power transformer HV vs LV HV vs G Multiple devices LV vs G

  10. Test data evaluation i.e. statistics keeping • Statistics • - Always assure the same measuring conditions • (connection, temperature, test voltage, diagnostics parameters) • Regular test intervals (6 months or one year) • Results keeping for the entire life period of the equipment • Observation of downgrading trends • Temperature coefficient • (all values are to be calculated on 75ºC)

  11. General requirements for HV insulation testers • Test functions: • Insulation resistance • Step voltage test • Capacitance • PI, DD, DAR • Current in µA and mA range • Voltage AC/DC • Other features: • Guard terminal to eliminate surface insulation currents • Automatic discharging of the test object after measurement • Built-in timer • On-Line graph R = f(t) • EM immunity for usage in HV environments • EM Filters for improved accuracy • Good charging system (accus or mains or both) • Accessories: • Shielded test leads • High quality test terminals (HV, antistatic, high surface resistance) • PC Software for downloading of test results and creating test reports

  12. Metrel HV insulation testers • Integrated features: • Test voltage up to 10kV DC • Resistance measuring range up to 10TΩ • Automated calculation of PI, DAR and DD for profound insulation diagnostics • On-Line R=f(t) display • Test voltage setting in 25V steps • Shielded 12kV test leads to reduce influence of external EM fields • CAT IV/600V over-voltage category for utilities and industrial applications • New TeraLink PRO Windows PC Software for TeraOhm 5kV Plus • Handbook “Modern insulation testing” on CD

  13. Metrel's solution providing, services and development • Product training in Metrel training centre • On-Line technical support • Application training and publications • Repair & Calibration training • Calibration equipment • Repair & Calibration services • Advanced technical solutions for all product‘s segments • (Hardware, Firmware, PC Software) • Customised solutions (Instruments, Software, Accessories)

  14. WHY NOT METREL?

  15. THANK YOU! You have already made a good decision